Multinozzle diffuser for duct mounting on circular ducts. Available with 3 to 10 nozzles in 1 or 2 rows.
- JET-MC, 1R6N, 600 X 100, RAL 9006
Expanation
JET-MC : Type of diffuser
1R6N : 1 Row, 6 Nozzles
625 X 125 : Size L X H
RAL 9006 : Aluminium finish
Dimensions
|
300 X 100 1R3N | 300 | 100 | 350 | 3 | 400 X 100 1R4N | 400 | 100 | 450 | 4 | 500 X 100 1R5N | 500 | 100 | 550 | 5 | 600 X 100 1R6N | 600 | 100 | 650 | 6 | 800 X 100 1R8N | 800 | 100 | 850 | 8 | 1000 X 100 1R10N | 1000 | 100 | 1050 | 10 | 300 X 200 2R3N | 300 | 200 | 350 | 6 | 400 X 200 2R4N | 400 | 200 | 450 | 8 | 500 X 200 2R5N | 500 | 200 | 550 | 10 | 600 X 200 2R6N | 600 | 200 | 650 | 12 | 800 X 200 2R8N | 800 | 200 | 850 | 16 | 1000 X 200 2R10N | 1000 | 200 | 1050 | 20 |
Quick selection
|
Q | Ak | 0.0038 | 0.005 | 0.0063 | 0.0075 | 0.0101 | 0.0126 | 100 | Vk | 7.4 | 5.5 | 4.4 | 3.7 | | | X0,25 | 12.4 | 9.7 | 7.6 | 6 | | | Ps | 35 | 19 | 12 | 9 | | | Lw(A) | <20 | <20 | <20 | <20 | | | 150 | Vk | 11.1 | 8.3 | 6.6 | 5.5 | 4.1 | 3.3 | X0,25 | 16.2 | 13.5 | 11.4 | 9.7 | 7 | 5 | Ps | 78 | 44 | 28 | 19 | 11 | 7 | Lw(A) | 23 | <20 | <20 | <20 | <20 | <20 | 200 | Vk | | 11.1 | 8.8 | 7.4 | 5.5 | 4.4 | X0,25 | | 16.2 | 14 | 12.4 | 9.7 | 7.6 | Ps | | 78 | 49 | 35 | 19 | 12 | Lw(A) | | 24 | <20 | <20 | <20 | <20 | 300 | Vk | | | 13.3 | 11.1 | 8.3 | 6.6 | X0,25 | | | 17.9 | 16.2 | 13.5 | 11.4 | Ps | | | 111 | 78 | 44 | 28 | Lw(A) | | | 30 | 26 | <20 | <20 | 400 | Vk | | | | | 11.1 | 8.8 | X0,25 | | | | | 16.2 | 14 | Ps | | | | | 78 | 49 | Lw(A) | | | | | 27 | 22 | 600 | Vk | | | | | | 13.3 | X0,25 | | | | | | 17.9 | Ps | | | | | | 111 | Lw(A) | | | | | | 33 | |
Q | Ak | 0.0075 | 0.0101 | 0.0126 | 0.0151 | 0.0201 | 0.0251 | 100 | Vk | 3.7 | | | | | | X0,25 | 6 | | | | | | Ps | 9 | | | | | | Lw(A) | <20 | | | | | | 150 | Vk | 5.5 | 4.1 | 3.3 | | | | X0,25 | 9.7 | 7 | 5 | | | | Ps | 19 | 11 | 7 | | | | Lw(A) | <20 | <20 | <20 | | | | 200 | Vk | 7.4 | 5.5 | 4.4 | 3.7 | | | X0,25 | 12.4 | 9.7 | 7.6 | 6 | | | Ps | 35 | 19 | 12 | 9 | | | Lw(A) | <20 | <20 | <20 | <20 | | | 300 | Vk | 11.1 | 8.3 | 6.6 | 5.5 | 4.1 | 3.3 | X0,25 | 16.2 | 13.5 | 11.4 | 9.7 | 7 | 5 | Ps | 78 | 44 | 28 | 19 | 11 | 7 | Lw(A) | 26 | <20 | <20 | <20 | <20 | <20 | 400 | Vk | | 11.1 | 8.8 | 7.4 | 5.5 | 4.4 | X0,25 | | 16.2 | 14 | 12.4 | 9.7 | 7.6 | Ps | | 78 | 49 | 35 | 19 | 12 | Lw(A) | | 27 | 22 | <20 | <20 | <20 | 600 | Vk | | | 13.3 | 11.1 | 8.3 | 6.6 | X0,25 | | | 17.9 | 16.2 | 13.5 | 11.4 | Ps | | | 111 | 78 | 44 | 28 | Lw(A) | | | 33 | 29 | 23 | <20 | 800 | Vk | | | | | 11.1 | 8.8 | X0,25 | | | | | 16.2 | 14 | Ps | | | | | 78 | 49 | Lw(A) | | | | | 30 | 25 | 1000 | Vk | | | | | 13.8 | 11.1 | X0,25 | | | | | 18.2 | 16.2 | Ps | | | | | 120 | 78 | Lw(A) | | | | | 36 | 31 | 1200 | Vk | | | | | | 13.3 | X0,25 | | | | | | 17.9 | Ps | | | | | | 111 | Lw(A) | | | | | | 36 |
Symbols and specifications
- Above values are for multi-nozzlediffusers in 1 or 2 rows
- LxH = Width L and height H in mm
¾ Q = Air volume in m³/h
- Ak = Effective surface (free area) in m²
- Vk = Average effective velocity through the grille in m/s
- X0.25 = Horizontal throw in m at an end velocity Vt of 0.25 m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The throw X0.25 is given without deflection of the airstream at an end velocity of 0.25m/s. For all special requirements,
please contact our engineering office.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by
deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to
the given X0.25 value.
- Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
Placement instruction
|