Round ceiling diffusers with fixed diffusion rings in plate for system ceiling 600 X 600 for radial air discharge
- PS/PRN, 200 + RER-LB + CRC 160
Explanation
PS/PRN = Diffuser type
200 = Diffuser size (Ø diffuser neck connection)
Accessories
RER-LB = Plenum box
CRC = Plenumbox connection valve
160 = Plenumbox connection diameter 160
Dimensions
|
150 | 595 | 210 | 149 | 200 | 595 | 260 | 199 | 250 | 595 | 300 | 249 | 300 | 595 | 350 | 314 |
Quick selection
|
Q | Ak | 0.0092 | 0.0138 | 0.0206 | 0.0312 | |
50 | | H= | 2.7 | 0.38 | 0.13 | 0.08 | | | | | | | | | | Vz | H= | 3.2 | 0.14 | 0.08 | 0.06 | | | | | | | | | | | H= | 3.8 | 0.08 | 0.06 | 0.04 | | | | | | | | | | Vk | 1.5 | | | | X0,25 | 1.7 | | | | Ps | 1 | | | | Lw(A) | <20 | | | | 100 | | H= | 2.7 | 0.77 | 0.26 | 0.15 | 0.63 | 0.21 | 0.13 | | | | | | | Vz | H= | 3.2 | 0.29 | 0.16 | 0.11 | 0.23 | 0.13 | 0.09 | | | | | | | | H= | 3.8 | 0.16 | 0.11 | 0.09 | 0.13 | 0.09 | 0.07 | | | | | | | Vk | 3 | 2 | | | X0,25 | 2.1 | 2 | | | Ps | 4 | 2 | | | Lw(A) | <20 | <20 | | | 150 | | H= | 2.7 | 1.15 | 0.38 | 0.23 | 0.94 | 0.31 | 0.19 | 0.77 | 0.26 | 0.15 | | | | Vz | H= | 3.2 | 0.43 | 0.25 | 0.17 | 0.35 | 0.2 | 0.14 | 0.29 | 0.16 | 0.12 | | | | | H= | 3.8 | 0.25 | 0.17 | 0.13 | 0.2 | 0.14 | 0.11 | 0.16 | 0.12 | 0.09 | | | | Vk | 4.5 | 3 | 2 | | X0,25 | 2.6 | 2.3 | 2.1 | | Ps | 8 | 4 | 2 | | Lw(A) | <20 | <20 | <20 | | 300 | | H= | 2.7 | 2.3 | 0.77 | 0.46 | 1.88 | 0.63 | 0.38 | 1.54 | 0.51 | 0.31 | 1.25 | 0.42 | 0.25 | Vz | H= | 3.2 | 0.86 | 0.49 | 0.34 | 0.7 | 0.4 | 0.28 | 0.58 | 0.33 | 0.23 | 0.47 | 0.27 | 0.19 | | H= | 3.8 | 0.49 | 0.34 | 0.27 | 0.4 | 0.28 | 0.22 | 0.33 | 0.23 | 0.18 | 0.27 | 0.19 | 0.14 | Vk | 9.1 | 6 | 4 | 2.7 | X0,25 | 4 | 3.5 | 3 | 2.7 | Ps | 32 | 14 | 6 | 3 | Lw(A) | 39 | 29 | <20 | <20 | 400 | | H= | 2.7 | | | | 2.5 | 0.83 | 0.5 | 2.05 | 0.68 | 0.41 | 1.66 | 0.55 | 0.33 | Vz | H= | 3.2 | | | | 0.94 | 0.54 | 0.38 | 0.77 | 0.44 | 0.31 | 0.62 | 0.36 | 0.25 | | H= | 3.8 | | | | 0.54 | 0.38 | 0.29 | 0.44 | 0.31 | 0.24 | 0.36 | 0.25 | 0.19 | Vk | | 8.1 | 5.4 | 3.6 | X0,25 | | 4.2 | 3.7 | 3.2 | Ps | | 26 | 11 | 5 | Lw(A) | | 39 | 29 | <20 | 500 | | H= | 2.7 | | | | | | | 2.56 | 0.85 | 0.51 | 2.08 | 0.69 | 0.42 | Vz | H= | 3.2 | | | | | | | 0.96 | 0.55 | 0.38 | 0.78 | 0.45 | 0.31 | | H= | 3.8 | | | | | | | 0.55 | 0.38 | 0.3 | 0.45 | 0.31 | 0.24 | Vk | | | 6.7 | 4.5 | X0,25 | | | 4.3 | 3.7 | Ps | | | 18 | 8 | Lw(A) | | | 37 | 27 | 600 | | H= | 2.7 | | | | | | | 3.07 | 1.02 | 0.61 | 2.5 | 0.83 | 0.5 | Vz | H= | 3.2 | | | | | | | 1.15 | 0.66 | 0.46 | 0.94 | 0.53 | 0.37 | | H= | 3.8 | | | | | | | 0.66 | 0.46 | 0.35 | 0.53 | 0.37 | 0.29 | Vk | | | 8.1 | 5.3 | X0,25 | | | 4.9 | 4.2 | Ps | | | 26 | 11 | Lw(A) | | | 43 | 33 | 800 | | H= | 2.7 | | | | | | | | | | 3.33 | 1.11 | 0.67 | Vz | H= | 3.2 | | | | | | | | | | 1.25 | 0.71 | 0.5 | | H= | 3.8 | | | | | | | | | | 0.71 | 0.5 | 0.38 | Vk | | | | 7.1 | X0,25 | | | | 5.2 | Ps | | | | 20 | Lw(A) | | | | 43 |
Symbols and specifications
- Q = Air Volume in m³/h
- Ak = Effective surface (free area) in m²
- B = Distance between diffusers in m
- H = Installation height of the diffusers in m
- Vz = Maximum velocity at the occupied zone regarding distance between diffusers and installation height in m/s
- Vk = Average effective velocity through the grill in m/s
- X0.25 = Throw length in m at an endvelocity Vt of 0,25m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
- In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
- The pressure losses Ps are given for grilles without damper of with fully opened damper.
- The acoustic power Lw(A) are given for grilles without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For all special requirements, please contact our engineering office.