Square swirl ceiling diffusers with adjustable blades
- Square plenum box, type REV-B
- Square insulated plenum box, type REV-B ISO
- Circular plenum box, type RER-B
- Insulated circular plenum box, type RER-B ISO
- Regulating valve for plenum box, type CRC
- Polystyrene plenum box, type PPS-P with duct connection PPS-APD and mounting
bar PPS-MB
(When using PPS-P plenum, a screw of at least 8cm must be provided by the installer himself)
- VWR-3A, 600, 24 + REV-B 600 + CRC 250
Explanation
VWR-3A = Diffuser type
600 = Plate size
24 = Slot quantity
Accessories
REV-B 600 = Plenum box for diffuser with 24 slots
CRC = Regulating valve for plenum box
250 = Plenum box connection diameter 250
Dimensions
|
400/16
| 16
| 395x395
| 500/16 | 16
| 495x495
| 600/16 | 16
| 595x595
| 600/24 | 24
| 595x595
| 625/24 | 24
| 623x623
|
Flow patterns deflectors
Quick selection
|
Q | Ak | 0.01548 | 0.03718 | |
150 | | H= | 2.7 | 0.09 | 0.12 | 0.08 | | | | Vz | H= | 3.2 | 0.06 | 0.07 | 0.05 | | | | | H= | 3.8 | 0.04 | 0.05 | 0.04 | | | | Vk | 2.7 | | X0,25 | 1.1 | | Ps | 4 | | Lw(A) | <20 | | 200 | | H= | 2.7 | 0.12 | 0.15 | 0.11 | 0.09 | 0.11 | 0.09 | Vz | H= | 3.2 | 0.08 | 0.1 | 0.07 | 0.06 | 0.07 | 0.05 | | H= | 3.8 | 0.05 | 0.07 | 0.05 | 0.04 | 0.05 | 0.04 | Vk | 3.6 | 1.5 | X0,25 | 1.5 | 0.9 | Ps | 8 | 2 | Lw(A) | 22 | <20 | 250 | | H= | 2.7 | 0.15 | 0.19 | 0.13 | 0.11 | 0.14 | 0.11 | Vz | H= | 3.2 | 0.1 | 0.12 | 0.08 | 0.07 | 0.09 | 0.07 | | H= | 3.8 | 0.07 | 0.08 | 0.06 | 0.05 | 0.06 | 0.05 | Vk | 4.5 | 1.9 | X0,25 | 1.8 | 1.2 | Ps | 12 | 4 | Lw(A) | 29 | <20 | 300 | | H= | 2.7 | 0.18 | 0.23 | 0.16 | 0.13 | 0.17 | 0.13 | Vz | H= | 3.2 | 0.12 | 0.15 | 0.1 | 0.08 | 0.1 | 0.08 | | H= | 3.8 | 0.08 | 0.1 | 0.07 | 0.06 | 0.07 | 0.06 | Vk | 5.4 | 2.2 | X0,25 | 2.2 | 1.4 | Ps | 18 | 5 | Lw(A) | 35 | <20 | 350 | | H= | 2.7 | | | | 0.16 | 0.19 | 0.15 | Vz | H= | 3.2 | | | | 0.1 | 0.12 | 0.09 | | H= | 3.8 | | | | 0.07 | 0.08 | 0.07 | Vk | | 2.6 | X0,25 | | 1.7 | Ps | | 7 | Lw(A) | | <20 | 400 | | H= | 2.7 | | | | 0.18 | 0.22 | 0.17 | Vz | H= | 3.2 | | | | 0.11 | 0.14 | 0.11 | | H= | 3.8 | | | | 0.08 | 0.1 | 0.08 | Vk | | 3 | X0,25 | | 1.9 | Ps | | 9 | Lw(A) | | 24 | 500 | | H= | 2.7 | | | | 0.22 | 0.28 | 0.21 | Vz | H= | 3.2 | | | | 0.14 | 0.17 | 0.14 | | H= | 3.8 | | | | 0.1 | 0.12 | 0.09 | Vk | | 3.7 | X0,25 | | 2.4 | Ps | | 14 | Lw(A) | | 30 | 600 | | H= | 2.7 | | | | 0.27 | 0.33 | 0.26 | Vz | H= | 3.2 | | | | 0.17 | 0.21 | 0.16 | | H= | 3.8 | | | | 0.12 | 0.15 | 0.11 | Vk | | 4.5 | X0,25 | | 2.8 | Ps | | 20 | Lw(A) | | 36 |
Symbols and specifications
- Q = Air volume in m³/h
- Ak = Effective surface (free area) in m²
- B = Distance between the diffusers in m
- H = Installation height of the diffusers in m
- Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
- Vk = Average effective velocity through the diffuser in m/s
- X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
- In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
- The pressure losses Ps are given for diffusers without damper of with fully opened damper.
- The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For all special requirements, please contact our engineering office.
Placement instruction
|