PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

RWR-2C (RAL9005) • Black circular swirl ceiling diffusers with clip mounting

  • Swirl diffusers
  • Circular
  • Steel
  • Black, RAL 9005
  • Clipsmounted

Round swirl ceiling diffusers with flat frame and fixed blades, mounted by clips

Brand

  • Cairox

Application

  • For air supply and exhaust in ventilation and air conditioning systems.

Material

  • Steel

Colour

  • Black, RAL 9005
  • Other colours available upon request

Composition

  • Fixed blades
  • Clip mounting

Mounting

  • Fixing directly on the collar without plenum box

Order example

  • RWR-2C (RAL 9005), 200

Explanation

RWR-2C = Diffuser with clip mounting type

200 = Neck size of diffuser

Dimensions

RWR-2C

ØD1 [mm]

ØD2 [mm]

ØD3 [mm]

H [mm]

H1 [mm]

#Blades

100

98

134

150

74

45

10
125123

170

190

86

55

10
160158

220

250

86

55

10
200198

270

300

86

55

10

Quick selection

RWR-2C100125160200
QAk0.00560.00860.01410.0224
B1.22.43.61.22.43.61.22.43.61.22.43.6
40 H=2.70.510.250.150.280.130.07      
VzH=3.20.280.160.10.140.080.05      
 H=3.80.160.10.070.080.050.03      
Vk21.3  
X0,252.11.6  
Ps2410  
Lw(A)25<20  
60 H=2.70.770.380.220.40.180.10.310.140.08   
VzH=3.20.420.240.160.210.110.070.160.090.05   
 H=3.80.240.160.110.110.070.050.090.050.04   
Vk31.91.2 
X0,252.61.81.7 
Ps54216 
Lw(A)3822<20 
100 H=2.7   0.680.310.170.520.240.130.390.170.09
VzH=3.2   0.350.190.120.260.140.090.190.10.06
 H=3.8   0.190.120.080.140.090.060.10.060.04
Vk 3.221.2
X0,25 2.321.8
Ps 59175
Lw(A) 3830<20
150 H=2.7      0.780.350.20.610.270.15
VzH=3.2      0.40.210.130.310.160.1
 H=3.8      0.210.130.090.160.10.07
Vk  31.9
X0,25  2.42.2
Ps  3713
Lw(A)  4325
200 H=2.7         0.810.360.2
VzH=3.2         0.40.220.13
 H=3.8         0.220.130.09
Vk   2.5
X0,25   2.4
Ps   23
Lw(A)   33
250 H=2.7         10.450.24
VzH=3.2         0.50.270.16
 H=3.8         0.270.160.11
Vk   3.1
X0,25   2.7
Ps   35
Lw(A)   40

Symbols and specifications

  • Q = Air volume in m³/h
  • Ak = Effective surface (free area) in m²
  • B = Distance between the diffusers in m
  • H = Installation height of the diffusers in m
  • Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
  • Vk = Average effective velocity through the diffuser in m/s
  • X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
  • Ps = Static pressure loss given in Pa
  • Lw(A) = Acoustic power in dB(A)


  • The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
  • The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
  • In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
  • The pressure losses Ps are given for diffusers without damper of with fully opened damper.
  • The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
  • For all special requirements, please contact our engineering office.

Placement instruction

HELPCopyrightSales conditionsCookie policyfujitsu-airco.be

Requesting information. Please wait a moment...