Circular adjustable swirl ceiling diffuser for high ceiling
Explanation
RWR-4 = Diffuser type
400 = Neck size of diffuser
Dimensions
|
RWR-4 200 | 198 | 248 | 96 | 350 | 180 | 20 | 40 | 30 | RWR-4 250 | 248 | 298 | 133 | 400 | 205 | 30 | 40 | 30 | RWR-4 315 | 313 | 398 | 175 | 500 | 230 | 30 | 40 | 30 | RWR-4 400 | 398 | 465 | 175 | 615 | 270 | 45 | 60 | 60 | RWR-4 500 | 498 | 565 | 225 | 780 | 320 | 35 | 60 | 80 | RWR-4 630 | 628 | 665 | 273 | 935 | 390 | 25 | 80 | 100 |
Quick selection
|
Q | Ak | 0.0305 | 0.0479 | 0.0765 | 0.1238 | 0.194 | 0.3088 | |
300 | B(min) | 2.4 | 1.6 | | | | | Vk | 2.7 | 1.7 | | | | | Ps | 7 | 3 | | | | | Lw(A) | 33 | 22 | | | | | 400 | B(min) | 3 | 2.2 | | | | | Vk | 3.6 | 2.3 | | | | | Ps | 12 | 5 | | | | | Lw(A) | 42 | 30 | | | | | 500 | B(min) | 3.8 | 2.8 | 2 | | | | Vk | 4.6 | 2.9 | 1.8 | | | | Ps | 19 | 7 | 3 | | | | Lw(A) | 49 | 37 | 22 | | | | 600 | B(min) | | 3.4 | 2.4 | 2.8 | | | Vk | | 3.5 | 2.2 | 1.3 | | | Ps | | 11 | 4 | 2 | | | Lw(A) | | 42 | 27 | 20 | | | 800 | B(min) | | | 3 | 2.8 | | | Vk | | | 2.9 | 1.8 | | | Ps | | | 8 | 3 | | | Lw(A) | | | 36 | 23 | | | 1000 | B(min) | | | 3.8 | 2.8 | 3.4 | | Vk | | | 3.6 | 2.2 | 1.4 | | Ps | | | 12 | 5 | 2 | | Lw(A) | | | 43 | 30 | 20 | | 2000 | B(min) | | | | 5.4 | 4 | 4.2 | Vk | | | | 4.5 | 2.9 | 1.8 | Ps | | | | 19 | 7 | 3 | Lw(A) | | | | 51 | 38 | 22 | 3000 | B(min) | | | | | 6 | 4.4 | Vk | | | | | 4.3 | 2.7 | Ps | | | | | 17 | 7 | Lw(A) | | | | | 50 | 33 | 4000 | B(min) | | | | | | 5.8 | Vk | | | | | | 3.6 | Ps | | | | | | 12 | Lw(A) | | | | | | 42 | 5000 | B(min) | | | | | | 7.2 | Vk | | | | | | 4.5 | Ps | | | | | | 19 | Lw(A) | | | | | | 49 |
Symbols and specifications
- Q = Air volume in m³/h
- Ak = Effective surface (free area) of the neck of the diffuser in m²
- Hm = Advised minimum - maximum mounting height in m
- Bmin = Advised minimum distance between diffusers in m
- Vk = Air velocity trough the neck of the diffuser in m/s
- Ps = Static pressure loss in Pa
- Lw(A) = Acoustic power in dB(A)
- The values are given for isothermal supply air without Coanda effect.
- The values in the table are given at an inclination angle α of the vanes of the diffuser set at 45°.
- In order to achieve a high comfort level, the angle of the blades can be set according to the temperature difference Δt between the supply air and room air temperature. (see selection graphs)
- Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
Placement instruction
Noise selection table
Placement height selector
Minimum distance selection
Angle setting size 200
Angle setting size 250
Angle setting size 315
Angle setting size 400
Angle setting size 500
Angle setting size 630
|