Manually adjustable JET design nozzles
Finished in grey alu-look RAL 9006
Explanation
JET-GDA = Diffuser type
315 = Connection diameter
Dimensions
|
125 | 125 | 123 | 61 | 170 | 70 | 100 | 150 | 150 | 148 | 75 | 200 | 85 | 113 | 160 | 160 | 158 | 80 | 200 | 85 | 115 | 200 | 200 | 197 | 105 | 266 | 109 | 143 | 250 | 250 | 248 | 128 | 315 | 135 | 180 | 315 | 315 | 313 | 165 | 395 | 173 | 230 | 400 | 400 | 398 | 210 | 495 | 217 | 285 |
Quick selection
|
Q | Ak | 0.0028 | 0.0044 | 0.005 | 0.0087 | 0.0129 | 0.0214 | 0.0346 | 75 | Vk | 7.4 | 4.7 | 4.2 | | | | | X0,25 | 16.3 | 14.5 | 14.1 | | | | | Ps | 35 | 14 | 11 | | | | | Lw(A) | <20 | <20 | <20 | | | | | 100 | Vk | 9.9 | 6.3 | 5.6 | 3.2 | | | | X0,25 | 19 | 17.4 | 16.9 | 13.7 | | | | Ps | 62 | 25 | 20 | 7 | | | | Lw(A) | <20 | <20 | <20 | <20 | | | | 150 | Vk | | 9.5 | 8.3 | 4.8 | 3.2 | | | X0,25 | | 21.4 | 20.7 | 17.5 | 14.9 | | | Ps | | 57 | 44 | 15 | 7 | | | Lw(A) | | 21 | <20 | <20 | <20 | | | 200 | Vk | | 12.6 | 11.1 | 6.4 | 4.3 | | | X0,25 | | 24.1 | 23.5 | 20.3 | 17.6 | | | Ps | | 100 | 78 | 26 | 12 | | | Lw(A) | | 28 | 26 | <20 | <20 | | | 300 | Vk | | | | 9.6 | 6.5 | 3.9 | | X0,25 | | | | 24.1 | 21.4 | 18.2 | | Ps | | | | 58 | 27 | 10 | | Lw(A) | | | | 26 | <20 | <20 | | 400 | Vk | | | | 12.8 | 8.6 | 5.2 | 3.2 | X0,25 | | | | 26.8 | 23.9 | 20.7 | 19 | Ps | | | | 103 | 47 | 17 | 7 | Lw(A) | | | | 33 | 25 | <20 | <20 | 500 | Vk | | | | | 10.8 | 6.5 | 4 | X0,25 | | | | | 26 | 22.6 | 21 | Ps | | | | | 74 | 27 | 10 | Lw(A) | | | | | 31 | <20 | <20 | 600 | Vk | | | | | 12.9 | 7.8 | 4.8 | X0,25 | | | | | 27.6 | 24.2 | 22.6 | Ps | | | | | 105 | 39 | 15 | Lw(A) | | | | | 35 | 20 | <20 | 700 | Vk | | | | | | 9.1 | 5.6 | X0,25 | | | | | | 25.6 | 24 | Ps | | | | | | 53 | 20 | Lw(A) | | | | | | 24 | <20 | 800 | Vk | | | | | | 10.4 | 6.4 | X0,25 | | | | | | 26.8 | 25.2 | Ps | | | | | | 68 | 26 | Lw(A) | | | | | | 28 | <20 | 1000 | Vk | | | | | | 13 | 8 | X0,25 | | | | | | 28.7 | 27.2 | Ps | | | | | | 107 | 41 | Lw(A) | | | | | | 34 | 23 | 1200 | Vk | | | | | | | 9.6 | X0,25 | | | | | | | 28.9 | Ps | | | | | | | 58 | Lw(A) | | | | | | | 29 | 1400 | Vk | | | | | | | 11.2 | X0,25 | | | | | | | 30.3 | Ps | | | | | | | 79 | Lw(A) | | | | | | | 33 | 1500 | Vk | | | | | | | 12 | X0,25 | | | | | | | 30.9 | Ps | | | | | | | 91 | Lw(A) | | | | | | | 36 |
Symbols and specifications
- The throw X0.25 is given without deflection of the airstream at an end velocity of 0.25m/s. The distances are given without coanda effect.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
- The acoustic power Lw(A) are given for grilles without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For special requirements, please contact our engineering office.
Placement instruction
|