Linear slot diffusers with adjustable deflector and volume control damper
- ASM25 2 MD, 1500 + PR25 2 1500 + ASM25-CON
Explanation
ASM25 = Diffuser type
2 = Slot quantity
MD = With deflector and volume control damper
1500 = Length of diffuser
Accessories (optional)
PR25 2 1500 = Not-insulated plenum box for diffuser of 2 slots with a length of 1500mm
ASM25-CON = Connection piece to mount several diffusers in line
Dimensions
|
ASM25 1 MD | 66 | 53 | 260 | 75 | 160 | 25 | ASM25 2 MD | 110 | 97 | 300 | 119 | 200 | 25 | ASM25 3 MD | 154 | 141 | 300 | 163 | 200 | 25 | ASM25 4 MD | 198 | 185 | 350 | 207 | 250 | 25 |
Flow patterns deflectors
Quick selection
|
Q | Ak | 0.0067 | 0.0101 | 0.0112 | 0.0134 | 0.0168 | 0.0202 | 0.0224 | 0.0269 | 0.0302 | 0.0336 | 0.0403 | 0.0448 | 0.0504 | 0.0538 | 0.0672 | 0.0896 | 50 | Vk | 2.1 | 1.4 | 1.2 | 1 | | | | | | | | | | | | | X0,25 | 2.6 | 2.3 | 2.3 | 2.2 | | | | | | | | | | | | | Ps | 9 | 4 | 3 | 2 | | | | | | | | | | | | | Lw(A) | 27 | <20 | <20 | <20 | | | | | | | | | | | | | 100 | Vk | | 2.8 | 2.5 | 2.1 | 1.7 | 1.4 | 1.2 | 1 | | | | | | | | | X0,25 | | 3.5 | 3.4 | 3.2 | 3 | 2.8 | 2.7 | 2.6 | | | | | | | | | Ps | | 17 | 13 | 9 | 6 | 4 | 3 | 2 | | | | | | | | | Lw(A) | | 35 | 33 | 29 | 24 | <20 | <20 | <20 | | | | | | | | | 150 | Vk | | | 3.7 | 3.1 | 2.5 | 2.1 | 1.9 | 1.6 | 1.4 | 1.2 | 1 | | | | | | X0,25 | | | 4.5 | 4.2 | 3.9 | 3.6 | 3.5 | 3.3 | 3.2 | 3.1 | 2.9 | | | | | | Ps | | | 29 | 21 | 13 | 9 | 8 | 5 | 4 | 3 | 2 | | | | | | Lw(A) | | | 43 | 39 | 34 | 30 | 27 | 23 | 20 | <20 | <20 | | | | | | 200 | Vk | | | | | 3.3 | 2.8 | 2.5 | 2.1 | 1.8 | 1.7 | 1.4 | 1.2 | 1.1 | 1 | | | X0,25 | | | | | 4.8 | 4.4 | 4.3 | 4 | 3.8 | 3.7 | 3.5 | 3.4 | 3.3 | 3.2 | | | Ps | | | | | 23 | 17 | 13 | 9 | 7 | 6 | 4 | 3 | 3 | 2 | | | Lw(A) | | | | | 41 | 36 | 34 | 30 | 27 | 25 | 21 | <20 | <20 | <20 | | | 250 | Vk | | | | | | 3.4 | 3.1 | 2.6 | 2.3 | 2.1 | 1.7 | 1.6 | 1.4 | 1.3 | 1 | | X0,25 | | | | | | 5.3 | 5 | 4.7 | 4.5 | 4.3 | 4.1 | 3.9 | 3.8 | 3.7 | 3.4 | | Ps | | | | | | 25 | 21 | 14 | 11 | 9 | 6 | 5 | 4 | 4 | 2 | | Lw(A) | | | | | | 42 | 40 | 35 | 33 | 30 | 26 | 24 | 21 | 20 | <20 | | 300 | Vk | | | | | | | 3.7 | 3.1 | 2.8 | 2.5 | 2.1 | 1.9 | 1.7 | 1.6 | 1.2 | | X0,25 | | | | | | | 5.8 | 5.4 | 5.2 | 5 | 4.6 | 4.5 | 4.3 | 4.2 | 3.9 | | Ps | | | | | | | 29 | 21 | 17 | 13 | 9 | 8 | 6 | 5 | 3 | | Lw(A) | | | | | | | 44 | 40 | 37 | 35 | 31 | 28 | 26 | 24 | <20 | | 350 | Vk | | | | | | | | 3.6 | 3.2 | 2.9 | 2.4 | 2.2 | 1.9 | 1.8 | 1.4 | 1.1 | X0,25 | | | | | | | | 6.1 | 5.8 | 5.6 | 5.2 | 5 | 4.8 | 4.7 | 4.3 | 3.9 | Ps | | | | | | | | 28 | 22 | 18 | 12 | 10 | 8 | 7 | 4 | 3 | Lw(A) | | | | | | | | 44 | 41 | 39 | 35 | 32 | 30 | 28 | 23 | <20 | 400 | Vk | | | | | | | | | 3.7 | 3.3 | 2.8 | 2.5 | 2.2 | 2.1 | 1.7 | 1.2 | X0,25 | | | | | | | | | 6.5 | 6.2 | 5.8 | 5.6 | 5.3 | 5.2 | 4.8 | 4.3 | Ps | | | | | | | | | 29 | 23 | 17 | 13 | 10 | 9 | 6 | 3 | Lw(A) | | | | | | | | | 44 | 42 | 38 | 35 | 33 | 31 | 26 | <20 | 500 | Vk | | | | | | | | | | | 3.4 | 3.1 | 2.8 | 2.6 | 2.1 | 1.6 | X0,25 | | | | | | | | | | | 6.9 | 6.6 | 6.3 | 6.2 | 5.6 | 5 | Ps | | | | | | | | | | | 25 | 21 | 17 | 14 | 9 | 5 | Lw(A) | | | | | | | | | | | 43 | 41 | 38 | 37 | 32 | 25 | 600 | Vk | | | | | | | | | | | | | 3.3 | 3.1 | 2.5 | 1.9 | X0,25 | | | | | | | | | | | | | 7.4 | 7.2 | 6.5 | 5.8 | Ps | | | | | | | | | | | | | 23 | 21 | 13 | 8 | Lw(A) | | | | | | | | | | | | | 43 | 41 | 36 | 30 | 800 | Vk | | | | | | | | | | | | | | | 3.3 | 2.5 | X0,25 | | | | | | | | | | | | | | | 8.3 | 7.4 | Ps | | | | | | | | | | | | | | | 23 | 13 | Lw(A) | | | | | | | | | | | | | | | 43 | 37 |
Symbols and specifications
- Q = Air Volume in m³/h
- Ak = Effective surface (free area) in m²
- Vk = Average effective velocity through the grill in m/s
- X0.25 = Throw length in m at an endvelocity Vt of 0,25m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The horizontal throw X0.25 is given at an end velocity of 0.25m/s with all deflectors positioned for a maximal horizontal one-way throw installed in smooth ceiling without any obstacles.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by deviding the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
- The pressure losses Ps are given for grilles without damper.
- The acoustic power Lw(A) are given for grilles without damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For all special requirements, please contact our engineering office.
Placement instruction
|