Multinozzle ceiling diffusers with high induction rate, consisting of a square plate with individual adjustable nozzles arranged in a square pattern and to be equipped with a plenum box.
The nozzles are designed for high Coanda effect at both low and high flow rates.
PS/SNS-1A = diffuser SNS-1A in plate 596 X 596
- SNS-1A, 600 + REV-B 600 + CRC 250
Explanation
SNS-1A= Diffuser type
600 = Diffuser size
Accessories
REV-B = Plenum box
600 = Size plenum box
CRC = Regulating valve for plenum box
250 = Plenum box connection diameter
Dimensions
|
SNS-1A 300-36 | 296x296 | 36 | SNS-1A 400-64 | 396x396 | 64 | SNS-1A 500-80 | 496x496 | 80 | SNS-1A 600-100 | 596x596 | 100 | SNS-1A 600-144 | 596x596 | 144 | SNS-1A 625-100* | 621x621 | 100 | PS/SNS-1A 300/596-36 | 596x596 | 36 | PS/SNS-1A 400/596-64 | 596x596 | 64 | PS/SNS-1A 500/596-80 | 596x596 | 80 | * niet meer verkrijgbaar / n'est plus disponible / no longer available |
Quick selection
|
| Ak | 0.0093 | 0.0165 | 0.0206 | 0.0258 | 0.0372 | |
75 | | H= | 2.7 | 0.42 | 0.2 | 0.12 | 0.38 | 0.18 | 0.11 | 0.35 | 0.17 | 0.1 | | | | | | | Vz | H= | 3.2 | 0.23 | 0.13 | 0.08 | 0.2 | 0.12 | 0.07 | 0.19 | 0.1 | 0.07 | | | | | | | | H= | 3.8 | 0.13 | 0.08 | 0.06 | 0.12 | 0.07 | 0.05 | 0.1 | 0.07 | 0.05 | | | | | | | Vk | 2.2 | 1.3 | 1 | | | | | X0,25 | 1.9 | 1.8 | 1.7 | | | | | Ps | 5 | 2 | 1 | | | | | Lw(A) | 21 | <20 | <20 | | | | | 100 | | H= | 2.7 | 0.53 | 0.27 | 0.17 | 0.46 | 0.23 | 0.14 | 0.42 | 0.21 | 0.12 | 0.37 | 0.18 | 0.11 | | | | Vz | H= | 3.2 | 0.3 | 0.18 | 0.12 | 0.26 | 0.15 | 0.1 | 0.23 | 0.13 | 0.09 | 0.2 | 0.11 | 0.07 | | | | | H= | 3.8 | 0.18 | 0.12 | 0.08 | 0.15 | 0.1 | 0.07 | 0.13 | 0.09 | 0.06 | 0.11 | 0.07 | 0.05 | | | | Vk | 3 | 1.7 | 1.3 | 1.1 | | | | X0,25 | 2.1 | 2 | 1.9 | 1.8 | | | | Ps | 10 | 4 | 2 | 2 | | | | Lw(A) | 28 | <20 | <20 | <20 | | | | 150 | | H= | 2.7 | 0.72 | 0.4 | 0.26 | 0.6 | 0.33 | 0.21 | 0.57 | 0.31 | 0.19 | 0.49 | 0.25 | 0.15 | 0.38 | 0.18 | 0.11 | Vz | H= | 3.2 | 0.44 | 0.28 | 0.2 | 0.36 | 0.22 | 0.15 | 0.34 | 0.21 | 0.14 | 0.28 | 0.17 | 0.11 | 0.2 | 0.12 | 0.07 | | H= | 3.8 | 0.28 | 0.2 | 0.15 | 0.22 | 0.15 | 0.11 | 0.21 | 0.14 | 0.1 | 0.17 | 0.11 | 0.08 | 0.12 | 0.07 | 0.05 | Vk | 4.5 | 2.5 | 2 | 1.6 | 1.1 | X0,25 | 2.7 | 2.4 | 2.3 | 2.1 | 1.8 | Ps | 22 | 8 | 5 | 3 | 2 | Lw(A) | 37 | 25 | <20 | <20 | <20 | 200 | | H= | 2.7 | | | | 0.75 | 0.43 | 0.28 | 0.7 | 0.4 | 0.26 | 0.61 | 0.33 | 0.21 | 0.46 | 0.24 | 0.14 | Vz | H= | 3.2 | | | | 0.47 | 0.3 | 0.21 | 0.43 | 0.28 | 0.2 | 0.36 | 0.23 | 0.16 | 0.26 | 0.15 | 0.1 | | H= | 3.8 | | | | 0.3 | 0.21 | 0.16 | 0.28 | 0.2 | 0.15 | 0.23 | 0.16 | 0.12 | 0.15 | 0.1 | 0.07 | Vk | | 3.4 | 2.7 | 2.2 | 1.5 | X0,25 | | 2.8 | 2.7 | 2.4 | 2 | Ps | | 14 | 9 | 6 | 3 | Lw(A) | | 33 | 28 | 23 | <20 | 250 | | H= | 2.7 | | | | 0.87 | 0.52 | 0.35 | 0.83 | 0.49 | 0.33 | 0.7 | 0.4 | 0.26 | 0.54 | 0.29 | 0.18 | Vz | H= | 3.2 | | | | 0.56 | 0.37 | 0.27 | 0.53 | 0.35 | 0.25 | 0.43 | 0.28 | 0.2 | 0.32 | 0.19 | 0.13 | | H= | 3.8 | | | | 0.37 | 0.27 | 0.21 | 0.35 | 0.25 | 0.19 | 0.28 | 0.2 | 0.15 | 0.19 | 0.13 | 0.1 | Vk | | 4.2 | 3.4 | 2.7 | 1.9 | X0,25 | | 3.3 | 3.1 | 2.7 | 2.2 | Ps | | 21 | 14 | 9 | 4 | Lw(A) | | 38 | 34 | 28 | <20 | 300 | | H= | 2.7 | | | | | | | 0.93 | 0.56 | 0.39 | 0.79 | 0.46 | 0.31 | 0.62 | 0.34 | 0.22 | Vz | H= | 3.2 | | | | | | | 0.61 | 0.41 | 0.3 | 0.5 | 0.33 | 0.24 | 0.37 | 0.23 | 0.16 | | H= | 3.8 | | | | | | | 0.41 | 0.3 | 0.24 | 0.33 | 0.24 | 0.18 | 0.23 | 0.16 | 0.12 | Vk | | | 4 | 3.2 | 2.2 | X0,25 | | | 3.5 | 3 | 2.4 | Ps | | | 20 | 13 | 6 | Lw(A) | | | 39 | 33 | 23 | 350 | | H= | 2.7 | | | | | | | 1.04 | 0.65 | 0.46 | 0.89 | 0.54 | 0.37 | 0.69 | 0.39 | 0.25 | Vz | H= | 3.2 | | | | | | | 0.7 | 0.48 | 0.36 | 0.58 | 0.39 | 0.29 | 0.42 | 0.27 | 0.19 | | H= | 3.8 | | | | | | | 0.48 | 0.36 | 0.29 | 0.39 | 0.29 | 0.22 | 0.27 | 0.19 | 0.14 | Vk | | | 4.7 | 3.8 | 2.6 | X0,25 | | | 4 | 3.4 | 2.6 | Ps | | | 28 | 18 | 9 | Lw(A) | | | 43 | 37 | 27 | 400 | | H= | 2.7 | | | | | | | | | | 0.97 | 0.6 | 0.42 | 0.75 | 0.44 | 0.29 | Vz | H= | 3.2 | | | | | | | | | | 0.65 | 0.44 | 0.33 | 0.47 | 0.31 | 0.22 | | H= | 3.8 | | | | | | | | | | 0.44 | 0.33 | 0.26 | 0.31 | 0.22 | 0.17 | Vk | | | | 4.3 | 3 | X0,25 | | | | 3.7 | 2.9 | Ps | | | | 23 | 11 | Lw(A) | | | | 41 | 31 | 450 | | H= | 2.7 | | | | | | | | | | 1.05 | 0.66 | 0.47 | 0.82 | 0.48 | 0.33 | Vz | H= | 3.2 | | | | | | | | | | 0.71 | 0.49 | 0.37 | 0.52 | 0.35 | 0.25 | | H= | 3.8 | | | | | | | | | | 0.49 | 0.37 | 0.29 | 0.35 | 0.25 | 0.19 | Vk | | | | 4.8 | 3.4 | X0,25 | | | | 4.1 | 3.1 | Ps | | | | 29 | 14 | Lw(A) | | | | 44 | 34 | 500 | | H= | 2.7 | | | | | | | | | | | | | 0.88 | 0.53 | 0.36 | Vz | H= | 3.2 | | | | | | | | | | | | | 0.57 | 0.39 | 0.28 | | H= | 3.8 | | | | | | | | | | | | | 0.39 | 0.28 | 0.22 | Vk | | | | | | | | | | | | | 3.7 | X0,25 | | | | | | | | | | | | | 3.4 | Ps | | | | | | | | | | | | | 17 | Lw(A) | | | | | | | | | | | | | 37 | 600 | | H= | 2.7 | | | | | | | | | | | | | 1 | 0.62 | 0.44 | Vz | H= | 3.2 | | | | | | | | | | | | | 0.67 | 0.46 | 0.34 | | H= | 3.8 | | | | | | | | | | | | | 0.46 | 0.34 | 0.27 | Vk | | | | | | | | | | | | | 4.5 | X0,25 | | | | | | | | | | | | | 3.9 | Ps | | | | | | | | | | | | | 25 | Lw(A) | | | | | | | | | | | | | 42 |
Symbols and specifications
- Q = Air volume in m³/h
- Ak = Effective surface (free area) in m²
- B = Distance between the diffusers in m
- H = Installation height of the diffusers in m
- Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
- Vk = Average effective velocity through the diffuser in m/s
- X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
- Ps = Static pressure loss given in Pa
- Lw(A) = Acoustic power in dB(A)
- The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
- In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
- The pressure losses Ps are given for diffusers without damper of with fully opened damper.
- The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For all special requirements, please contact our engineering office.
Placement instruction
|