Multinozzle ceiling diffusers with high induction rate, consisting of a square plate with individual adjustable nozzles arranged in a square pattern and to be equipped with a plenum box.
The nozzles are designed to create a high Coanda effect at both low and high flow rates.
PS/SNS-XL = diffuser SNS-XL in plate 596 X 596
- SNS-XL, 600-64 + PPS-P 600 + PPS-APD 250 + PPS-MB
Explanation
SNS-XL= Diffuser type
600 = Diffuser size
64 = Number of nozzles
Accessories
PPS-P 600 = Plenum box
PPS-APD 250 = Plenum box connection diameter
PPS-MB = mounting bar for PPS-P plenum
Dimensions
|
SNS-XL 300-16 | 298x298 | 16 | SNS-XL 400-24 | 398x398 | 24 | SNS-XL 500-36 | 498x498 | 36 | SNS-XL 500-48 | 498x498 | 48 | PS/SNS-XL 300/596-16 | 596x596 | 16 | PS/SNS-XL 400/596-24 | 596x596 | 24 | PS/SNS-XL 500/596-36 | 596x596 | 36 | PS/SNS-XL 500/596-48 | 596x596 | 48 | SNS-XL 600-64 | 596x596 | 64 | SNS-XL 600-80 | 596x596 | 80 |
Quick selection
|
| Ak | 0.019 | 0.0285 | 0.0427 | 0.0569 | 0.0759 | 0.0949 | 0.0949 | |
|
100 | | H= | 2.7 | 0.16 | 0.12 | 0.09 | | | | | | | | | | | | | | | | | | | Vz | H= | 3.2 | 0.12 | 0.09 | 0.08 | | | | | | | | | | | | | | | | | | | | H= | 3.8 | 0.09 | 0.08 | 0.06 | | | | | | | | | | | | | | | | | | | Vk | 1.5 | | | | | | | X(0,25) | 1 | | | | | | | Pt | 10 | | | | | | | Lw(A) | <20 | | | | | | | 150 | | H= | 2.7 | 0.24 | 0.17 | 0.13 | 0.19 | 0.13 | 0.1 | | | | | | | | | | | | | | | | Vz | H= | 3.2 | 0.18 | 0.14 | 0.11 | 0.14 | 0.11 | 0.09 | | | | | | | | | | | | | | | | | H= | 3.8 | 0.14 | 0.11 | 0.1 | 0.11 | 0.09 | 0.07 | | | | | | | | | | | | | | | | Vk | 2.2 | 1.5 | | | | | | X(0,25) | 1.5 | 1.1 | | | | | | Pt | 23 | 10 | | | | | | Lw(A) | 28 | <20 | | | | | | 200 | | H= | 2.7 | 0.32 | 0.23 | 0.18 | 0.25 | 0.18 | 0.14 | | | | | | | | | | | | | | | | Vz | H= | 3.2 | 0.24 | 0.19 | 0.15 | 0.19 | 0.14 | 0.12 | | | | | | | | | | | | | | | | | H= | 3.8 | 0.19 | 0.15 | 0.13 | 0.14 | 0.12 | 0.1 | | | | | | | | | | | | | | | | Vk | 2.9 | 1.9 | | | | | | X(0,25) | 1.9 | 1.5 | | | | | | Pt | 41 | 18 | | | | | | Lw(A) | 37 | 26 | | | | | | 300 | | H= | 2.7 | 0.48 | 0.35 | 0.27 | 0.37 | 0.27 | 0.21 | 0.31 | 0.22 | 0.17 | 0.31 | 0.22 | 0.17 | | | | | | | | | | Vz | H= | 3.2 | 0.36 | 0.28 | 0.23 | 0.28 | 0.21 | 0.17 | 0.23 | 0.18 | 0.14 | 0.24 | 0.18 | 0.15 | | | | | | | | | | | H= | 3.8 | 0.28 | 0.23 | 0.19 | 0.21 | 0.17 | 0.15 | 0.18 | 0.14 | 0.12 | 0.18 | 0.15 | 0.12 | | | | | | | | | | Vk | 4.4 | 2.9 | 2 | 1.5 | | | | X(0,25) | 2.9 | 2.2 | 1.9 | 1.9 | | | | Pt | 91 | 39 | 15 | 7 | | | | Lw(A) | 49 | 38 | 25 | <20 | | | | 400 | | H= | 2.7 | | | | 0.5 | 0.35 | 0.28 | 0.41 | 0.29 | 0.23 | 0.42 | 0.3 | 0.23 | 0.38 | 0.27 | 0.21 | | | | | | | Vz | H= | 3.2 | | | | 0.37 | 0.29 | 0.23 | 0.31 | 0.24 | 0.19 | 0.31 | 0.24 | 0.2 | 0.28 | 0.22 | 0.18 | | | | | | | | H= | 3.8 | | | | 0.29 | 0.23 | 0.2 | 0.24 | 0.19 | 0.16 | 0.24 | 0.2 | 0.17 | 0.22 | 0.18 | 0.15 | | | | | | | Vk | | 3.9 | 2.6 | 2 | 1.5 | | | X(0,25) | | 3 | 2.5 | 2.5 | 2.3 | | | Pt | | 68 | 27 | 13 | 9 | | | Lw(A) | | 46 | 34 | 24 | <20 | | | 500 | | H= | 2.7 | | | | 0.62 | 0.44 | 0.34 | 0.52 | 0.37 | 0.29 | 0.52 | 0.37 | 0.29 | 0.47 | 0.34 | 0.26 | 0.45 | 0.32 | 0.25 | 0.45 | 0.32 | 0.25 | Vz | H= | 3.2 | | | | 0.46 | 0.36 | 0.29 | 0.39 | 0.3 | 0.24 | 0.39 | 0.3 | 0.25 | 0.35 | 0.27 | 0.22 | 0.34 | 0.26 | 0.21 | 0.34 | 0.26 | 0.21 | | H= | 3.8 | | | | 0.36 | 0.29 | 0.24 | 0.3 | 0.24 | 0.2 | 0.3 | 0.25 | 0.21 | 0.27 | 0.22 | 0.19 | 0.26 | 0.21 | 0.18 | 0.26 | 0.21 | 0.18 | Vk | | 4.9 | 3.3 | 2.4 | 1.8 | 1.5 | 1.5 | X(0,25) | | 3.7 | 3.1 | 3.1 | 2.8 | 2.7 | 2.7 | Pt | | 105 | 41 | 20 | 14 | 10 | 6 | Lw(A) | | 53 | 41 | 31 | 27 | 23 | <20 | 600 | | H= | 2.7 | | | | | | | 0.62 | 0.44 | 0.34 | 0.63 | 0.45 | 0.35 | 0.56 | 0.4 | 0.31 | 0.54 | 0.39 | 0.3 | 0.54 | 0.39 | 0.3 | Vz | H= | 3.2 | | | | | | | 0.46 | 0.36 | 0.29 | 0.47 | 0.36 | 0.29 | 0.42 | 0.33 | 0.26 | 0.41 | 0.31 | 0.25 | 0.41 | 0.31 | 0.25 | | H= | 3.8 | | | | | | | 0.36 | 0.29 | 0.24 | 0.36 | 0.29 | 0.25 | 0.33 | 0.26 | 0.22 | 0.31 | 0.25 | 0.21 | 0.31 | 0.25 | 0.21 | Vk | | | 3.9 | 2.9 | 2.2 | 1.8 | 1.8 | X(0,25) | | | 3.7 | 3.8 | 3.4 | 3.2 | 3.2 | Pt | | | 58 | 29 | 20 | 14 | 9 | Lw(A) | | | 46 | 36 | 32 | 29 | 21 | 700 | | H= | 2.7 | | | | | | | 0.72 | 0.52 | 0.4 | 0.73 | 0.52 | 0.41 | 0.66 | 0.47 | 0.37 | 0.63 | 0.45 | 0.35 | 0.63 | 0.45 | 0.35 | Vz | H= | 3.2 | | | | | | | 0.54 | 0.42 | 0.34 | 0.55 | 0.42 | 0.34 | 0.49 | 0.38 | 0.31 | 0.47 | 0.36 | 0.3 | 0.47 | 0.36 | 0.3 | | H= | 3.8 | | | | | | | 0.42 | 0.34 | 0.28 | 0.42 | 0.34 | 0.29 | 0.38 | 0.31 | 0.26 | 0.36 | 0.3 | 0.25 | 0.36 | 0.3 | 0.25 | Vk | | | 4.6 | 3.4 | 2.6 | 2 | 2 | X(0,25) | | | 4.3 | 4.4 | 4 | 3.8 | 3.8 | Pt | | | 79 | 40 | 27 | 20 | 12 | Lw(A) | | | 51 | 41 | 37 | 33 | 25 | 800 | | H= | 2.7 | | | | | | | | | | 0.84 | 0.6 | 0.47 | 0.75 | 0.54 | 0.42 | 0.72 | 0.52 | 0.4 | 0.72 | 0.52 | 0.4 | Vz | H= | 3.2 | | | | | | | | | | 0.63 | 0.48 | 0.39 | 0.56 | 0.43 | 0.35 | 0.54 | 0.42 | 0.34 | 0.54 | 0.42 | 0.34 | | H= | 3.8 | | | | | | | | | | 0.48 | 0.39 | 0.33 | 0.43 | 0.35 | 0.3 | 0.42 | 0.34 | 0.28 | 0.42 | 0.34 | 0.28 | Vk | | | | 3.9 | 2.9 | 2.3 | 2.3 | X(0,25) | | | | 5 | 4.5 | 4.3 | 4.3 | Pt | | | | 52 | 35 | 26 | 15 | Lw(A) | | | | 45 | 41 | 37 | 29 | 1000 | | H= | 2.7 | | | | | | | | | | 1.05 | 0.75 | 0.58 | 0.94 | 0.67 | 0.52 | 0.9 | 0.64 | 0.5 | 0.9 | 0.64 | 0.5 | Vz | H= | 3.2 | | | | | | | | | | 0.79 | 0.6 | 0.49 | 0.71 | 0.54 | 0.44 | 0.68 | 0.52 | 0.42 | 0.68 | 0.52 | 0.42 | | H= | 3.8 | | | | | | | | | | 0.6 | 0.49 | 0.41 | 0.54 | 0.44 | 0.37 | 0.52 | 0.42 | 0.36 | 0.52 | 0.42 | 0.36 | Vk | | | | 4.9 | 3.7 | 2.9 | 2.9 | X(0,25) | | | | 6.3 | 5.6 | 5.4 | 5.4 | Pt | | | | 82 | 55 | 40 | 24 | Lw(A) | | | | 52 | 48 | 44 | 36 |
Symbols and specifications
- Q = Air volume in m³/h
- Ak = Effective surface (free area) in m²
- B = Distance between the diffusers in m
- H = Installation height of the diffusers in m
- Vz = Maximum velocity at the occupied zone according to distance between the diffusers and installation height in m/s
- Vk = Average effective velocity through the diffuser in m/s
- X0.25 = Throw length in m at an end velocity Vt of 0,25m/s
- Pt = Total pressure loss over difuuser and plenum given in Pa
- Lw(A) = Acoustic power in dB(A)
- The throw X0.25 is given at an end velocity of 0.25m/s for a smooth ceiling without any obstacles.
- The values are given for isothermal supply air. Throw distances for cooling conditions at -11K can be calculated by dividing the X0.25 values with factor 1.1. For heating purposes at Dt of +11K a multiplier of 1.1 should be applied to the given X0.25 value.
- In order to achieve a high comfort level, selections can be made according to the maximal velocity at the occupied zone Vz. These values are given at distances between diffusers B and installation heights H. Velocities Vz lower than, or equal to 0,25m/s at the occupied zone are advised.
- The pressure losses Ps are given for diffusers without damper of with fully opened damper.
- The acoustic power values Lw(A) are given for diffusers without damper of with fully opened damper without room attenuation. Acoustic powers below 20dB(A) are mentioned as "<20" in the tables.
- For all special requirements, please contact our engineering office.
Placement instruction
|