VAV-CS air flow regulator can be used both for variable and constant flow and, if appropriate, for forced shut-off for both air supply and air exhaust
Explanation:
VAV-CS = Circular Airflow regulator type
100 = Diameter of the damper
SAR 100 = Sound attenuator type
Air flow Characteristics
|
| 100 | Qv | 28 | 57 | 113 | 170 | 226 | 283 | | DpT min | 4 | 8 | 24 | 47 | 77 | 114 | | DpT=50Pa | Lw | 40 | 47 | 45 | 46 | 47 | 48 | | NR | 34 | 48 | 38 | 40 | 42 | 44 | | DpT=100Pa | Lw | 44 | 51 | 52 | 52 | 53 | 53 | | NR | 40 | 48 | 48 | 46 | 48 | 50 | | DpT=200Pa | Lw | 49 | 56 | 62 | 59 | 59 | 60 | | NR | 48 | 50 | 62 | 54 | 53 | 55 | | DpT=500Pa | Lw | 58 | 61 | 67 | 72 | 69 | 69 | | NR | 58 | 59 | 62 | 72 | 67 | 63 | | 125 | Qv | 44 | 88 | 177 | 265 | 353 | 442 | | DpT min | 4 | 8 | 23 | 44 | 72 | 107 | | DpT=50Pa | Lw | 41 | 48 | 46 | 47 | 48 | 49 | | NR | 35 | 49 | 39 | 41 | 43 | 45 | | DpT=100Pa | Lw | 45 | 52 | 53 | 53 | 54 | 54 | | NR | 41 | 49 | 49 | 47 | 49 | 51 | | DpT=200Pa | Lw | 50 | 57 | 63 | 60 | 60 | 61 | | NR | 49 | 51 | 63 | 55 | 55 | 56 | | DpT=500Pa | Lw | 59 | 52 | 68 | 73 | 70 | 70 | | NR | 59 | 60 | 63 | 73 | 68 | 64 | | 160 | Qv | 72 | 145 | 290 | 434 | 579 | 724 | | DpT min | 4 | 8 | 22 | 41 | 68 | 101 | | DpT=50Pa | Lw | 42 | 49 | 47 | 48 | 49 | 50 | | NR | 36 | 49 | 40 | 43 | 45 | 46 | | DpT=100Pa | Lw | 46 | 53 | 54 | 54 | 55 | 55 | | NR | 42 | 50 | 50 | 48 | 51 | 52 | | DpT=200Pa | Lw | 51 | 58 | 64 | 61 | 61 | 62 | | NR | 50 | 52 | 64 | 56 | 56 | 57 | | DpT=500Pa | Lw | 60 | 63 | 69 | 74 | 71 | 71 | | NR | 60 | 61 | 64 | 74 | 69 | 65 | | 200 | Qv | 113 | 226 | 452 | 679 | 905 | 1131 | | DpT min | 4 | 8 | 20 | 38 | 63 | 94 | | DpT=50Pa | Lw | 43 | 50 | 48 | 49 | 50 | 51 | | NR | 37 | 50 | 41 | 44 | 46 | 47 | | DpT=100Pa | Lw | 47 | 54 | 55 | 55 | 56 | 56 | | NR | 43 | 51 | 51 | 49 | 52 | 53 | | DpT=200Pa | Lw | 52 | 59 | 65 | 62 | 62 | 63 | | NR | 51 | 53 | 65 | 57 | 57 | 58 | | DpT=500Pa | Lw | 61 | 64 | 70 | 75 | 72 | 72 | | NR | 61 | 62 | 65 | 75 | 70 | 66 | | 250 | Qv | 177 | 353 | 707 | 1060 | 1414 | 1767 | | DpT min | 3 | 7 | 19 | 36 | 59 | 88 | | DpT=50Pa | Lw | 44 | 51 | 49 | 50 | 51 | 52 | | NR | 38 | 51 | 42 | 45 | 47 | 48 | | DpT=100Pa | Lw | 48 | 55 | 56 | 56 | 57 | 57 | | NR | 44 | 52 | 52 | 50 | 53 | 54 | | DpT=200Pa | Lw | 53 | 60 | 66 | 63 | 63 | 64 | | NR | 52 | 54 | 66 | 58 | 58 | 59 | | DpT=500Pa | Lw | 62 | 65 | 71 | 76 | 73 | 73 | | NR | 62 | 63 | 66 | 76 | 71 | 67 | | 315 | Qv | 281 | 561 | 1122 | 1683 | 2244 | 2806 | | DpT min | 3 | 6 | 18 | 34 | 56 | 84 | | DpT=50Pa | Lw | 45 | 52 | 50 | 51 | 52 | 53 | | NR | 39 | 52 | 43 | 46 | 48 | 50 | | DpT=100Pa | Lw | 49 | 56 | 57 | 57 | 58 | 58 | | NR | 45 | 53 | 53 | 51 | 54 | 56 | | DpT=200Pa | Lw | 54 | 61 | 67 | 64 | 64 | 65 | | NR | 53 | 55 | 67 | 59 | 59 | 60 | | DpT=500Pa | Lw | 63 | 66 | 72 | 77 | 74 | 74 | | NR | 63 | 64 | 67 | 77 | 72 | 68 | | 355 | Qv | 356 | 713 | 1425 | 2138 | 2851 | 3563 | | DpT min | 3 | 6 | 18 | 33 | 54 | 80 | | DpT=50Pa | Lw | 45 | 52 | 50 | 51 | 52 | 53 | | NR | 40 | 53 | 44 | 47 | 49 | 50 | | DpT=100Pa | Lw | 49 | 56 | 57 | 58 | 58 | 59 | | NR | 46 | 53 | 53 | 52 | 55 | 56 | | DpT=200Pa | Lw | 55 | 61 | 67 | 65 | 65 | 65 | | NR | 54 | 56 | 68 | 59 | 59 | 61 | | DpT=500Pa | Lw | 63 | 66 | 73 | 77 | 75 | 74 | | NR | 63 | 65 | 68 | 77 | 73 | 68 | | 400 | Qv | 452 | 905 | 1810 | 2714 | 3619 | 4524 | | DpT min | 3 | 6 | 17 | 32 | 53 | 78 | | DpT=50Pa | Lw | 45 | 40 | 46 | 50 | 53 | 55 | | NR | 43 | 37 | 41 | 47 | 51 | 54 | | DpT=100Pa | Lw | 39 | 46 | 52 | 56 | 58 | 60 | | NR | 37 | 43 | 48 | 52 | 55 | 59 | | DpT=200Pa | Lw | 48 | 53 | 58 | 61 | 64 | 65 | | NR | 47 | 50 | 55 | 56 | 60 | 63 | | DpT=500Pa | Lw | 58 | 63 | 66 | 69 | 71 | 72 | | NR | 57 | 60 | 63 | 65 | 66 | 68 | | 500 | Qv | 707 | 1414 | 2827 | 4241 | 5655 | 7069 | | DpT min | 3 | 6 | 16 | 30 | 49 | 73 | | DpT=50Pa | Lw | 34 | 41 | 47 | 51 | 54 | 56 | | NR | 31 | 38 | 42 | 48 | 52 | 55 | | DpT=100Pa | Lw | 41 | 47 | 53 | 57 | 59 | 61 | | NR | 39 | 44 | 49 | 53 | 57 | 60 | | DpT=200Pa | Lw | 49 | 54 | 59 | 62 | 65 | 66 | | NR | 48 | 51 | 56 | 57 | 61 | 64 | | DpT=500Pa | Lw | 59 | 64 | 67 | 70 | 72 | 73 | | NR | 58 | 61 | 64 | 66 | 67 | 70 | | 630 | Qv | 1122 | 2244 | 4489 | 6733 | 8978 | 11222 | | DpT min | 2 | 5 | 14 | 28 | 47 | 69 | | DpT=50Pa | Lw | 35 | 42 | 48 | 52 | 55 | 57 | | NR | 32 | 38 | 43 | 49 | 53 | 56 | | DpT=100Pa | Lw | 42 | 48 | 54 | 58 | 60 | 62 | | NR | 40 | 45 | 50 | 54 | 58 | 61 | | DpT=200Pa | Lw | 50 | 55 | 60 | 63 | 66 | 67 | | NR | 49 | 52 | 57 | 58 | 62 | 65 | | DpT=500Pa | Lw | 60 | 65 | 68 | 71 | 73 | 74 | | NR | 59 | 62 | 65 | 67 | 68 | 71 |
Symbols and specifications
- VAV-CS 100, 125, ..., 630 = Variable or constant volume damper with duct connection Ø100, Ø125, ..., Ø630
- v = In-duct average velocity in m/s
- Qv = In-duct average air volume rate in m³/h
- DpT min = minimal total pressure drop when valve is 100% opened in Pa
- Lw, DpT at 50Pa, 100Pa, 200Pa or 500Pa = A-weighted sound power emitted to the connected duct without silencer at total Pressure drop of 50, 100, 200 or 500Pa given in dB(A)
- NR, DpT at 50Pa, 100Pa, 200Pa or 500Pa = Noise rate for sound power emitted to connected duct without silencer at total Pressure drop of 50, 100, 200 or 500Pa
Dimensions
|
VAV-CS 100 | 98 | 305 | 40 | VAV-CS 125 | 123 | 330 | 40 | VAV-CS 160 | 158 | 400 | 40 | VAV-CS 200 | 198 | 470 | 40 | VAV-CS 250 | 248 | 555 | 40 | VAV-CS 315 | 313 | 680 | 40 | VAV-CS 355 | 353 | 750 | 40 | VAV-CS 400 | 398 | 825 | 40 | VAV-CS 500 | 498 | 990 | 40 | VAV-CS 630 | 628 | 1220 | 40 |
|