Fire dampers SC90+ offer a solution for small diameters. Two half round blades are held together by a fusible link. When the temperature rises above 72°C the fusible link will break. Thereby the two half blades are released and the fire damper is shut, preventing smoke or flames from passing through
Explanation
SC90+ = Round butterfly fire damper Rf 90 minutes
125 = duct diameter
Quick selection
|
100 | Qv | 85 | 113 | 141 | 170 | 198 | 226 | veff | 8 | 11 | 14 | 16 | 19 | 22 | Ps | 12 | 22 | 35 | 50 | 68 | 88 | Lw | 42 | 47 | 49 | 52 | 54 | 57 | 125 | Qv | 133 | 177 | 221 | 265 | 309 | 353 | veff | 6 | 8 | 10 | 12 | 14 | 16 | Ps | 8 | 14 | 22 | 32 | 44 | 57 | Lw | 41 | 45 | 47 | 50 | 52 | 55 | 160 | Qv | 217 | 290 | 362 | 434 | 507 | 579 | veff | 5 | 7 | 8 | 10 | 12 | 14 | Ps | 6 | 10 | 16 | 22 | 31 | 40 | Lw | 38 | 43 | 46 | 49 | 51 | 53 | 200 | Qv | 339 | 452 | 565 | 679 | 792 | 905 | veff | 8 | 11 | 13 | 16 | 18 | 21 | Ps | 4 | 8 | 12 | 17 | 24 | 31 | Lw | 37 | 42 | 45 | 47 | 50 | 52 |
Symbols and specifications
- v = Air velocity in the duct in m/s
- Qv = Air volume in m³/h
- veff = Effective velocity through the damper in m/s
- Ps = Static pressure in Pa
- Lw = Acoustic power in dB(A)
Dimensions
|
100 | 100 | 98.5 | 18 | 125 | 125 | 123.5 | 31 | 160 | 160 | 158.5 | 49 | 200 | 200 | 198.5 | 69 |
|