PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

DI/P30 • Glass wool insulation plates

  • Glasswool
  • Internal acoustic insulation
  • Standard
  • 25 or 50 mm

Glass wool duct insulation plates with black fiberglass foil

Application

  • For internal thermal and acoustic insulation of HVAC ductwork applications, acoustic splitters or acoustic housings

Material

  • Glass wool plate with glasswoolfibers, glued on a black fiberglass screen

Colour

  • Yellow mineral glasswoll with black fiberglass screen

Composition

  • Mineral glass wool matress with horizontally orientated glasswool fibers
  • Black fiberglass screen

Characteristics

  • Heat conductivity of 0.032 W/mK at 10°C and volume mass max 32 kg/m³
  • Application temperatures up to 125°C
  • Non hygroscopical and non capillary material
  • Fire resistance class A2-s1,d0
  • Size 2.4 x 1.2 m (2.88 m²) per plate with a thickness of 25 mm or 50 mm
  • Wrapped with 40 pieces (thickness 25 mm) or 20 pieces (thickness 50 mm) in polyethylene shrinkfoil
  • Maximum air velocity 12 m/s
  • CE certificate 64721
  • Store in dry area
  • Wear protective clothing when installing

Mounting

  • To be glued on inside ducts
  • To be pinned on surfaces by means of insulation pins with washers

Accessories

  • Contact glue, type POWER SPRAY
  • Insulation self-adhesive pins with washers, type CD 32 or CD 63

Text for tender

Copy
  • The thermal and acoustic internal insulation will be done by means of glass wool insulation plates of 25 mm or 50 mm. The matresses consist of mineral glass wool fibers glued on a black fiberglass screen.
  • CAIROX Type DI/ P30-25 or DI/ P30-50

Order example

  • DI/P30-25

Explanation

DI/P30-25 = Glass fiber acoustic insulation plate of 25mm thickness

Attenuation table

acoustic properties

DI/P
Hz
125250500100020004000
30-25

 

αs

0.07

0.220.510.710.851.03
30-50

 

αs
0.190.560.940.981.021.13

Symbols and specifications

αs = absorption coefficient in sabine

Hz = frequenty band in Hertz

DI/P30-25 = insulation plate thickness 25 mm

DI/P30-50 = insulation plate thickness 50 mm

Attenuation example

example:
Duct of 0.50 x 0.40 m
Frequency: 2000 Hz
Reduction per channel:
type 602 25mm: 9 dB
These graphs are the translation of the formula:
∆N=1,05αs1,4 p/s dB/lm
with ΔN = noise reduction in dB /lm.
αs = sound absorption coefficient according sabine.
p = inner circumference of the channel in lm: 2 (a + b)
s = inner surface of the channel in m2: (a x b)
Sound absorption coefficient
αs (according sabine)
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be