BCS-ECP • Duct fans with EC-motor + integrated potentiometer

Centrifugal duct fan with an EC motor with integrated potentiometer

Application

  • BCS-EC fans are designed to be built-in in circular ducts
  • They are used for ventilation in many applications such as offices, restaurants, technical rooms or other

Composition

  • Backward curved impeller made of plastic (EBM Papst)
  • EC-motor (EBM Papst) 230 V ca 1ph, speed controllable by means of a 10k Ohm potentiometer or a external signal 0-10V Vdc, protection class IP54, insulation class B
  • Integrated automatic thermal contact with automatic restart, locked-rotor protection, softstart
  • Maintenance-free, long-life ball bearings
  • Sheet steel housing powder coated RAL 7035
  • Junction box IP54 with cable gland
  • Mounting bracket included
  • With integrated potentiometer for an unique adjustment

Accessories

  • Potentiometer, type ESCP010
  • Clamping strip, type BMK
  • Safety grille, type BSV-S

Text for tender

Copy
  • The fans shall be of the centrifugal in-line duct type with backward curved impeller and with external 230V rotor motor with thermal protection. IP54, class F, junction box IP54. Sheet steel housing powder coated RAL 7035. The maximum working temperature shall be 55°C to 80°C, depending on the model.
    A potentiometer is integrated in the connection box for one-off measurement of the flow. If you want to adjust the flow from a distance, you must also provide the MPT010 potentiometer option, the cabling of which must be done on the construction side.
  • ATC type BCA.

    Order example

    BCS-ECP250 + ESCP010

    • BCS-EC = type of fan
    • 250 = diameter
    • ESCP010 = potentio-meter

    Air performance data

     Q [m³/h]
    50Pa100Pa150Pa200Pa250Pa300Pa400Pa500Pa600Pa700Pa
    BCS-ECP 125

    415

    375

    340

    305

    270

    235

    175

    115

    -

    -

    BCS-ECP 160

    470

    430

    390

    345

    305

    260

    175

    90

    55

    -

    BCS-ECP 200

    1050

    985

    910

    840

    780

    710

    570

    430

    295

    180

    BCS-ECP 250

    1100

    1045

    975

    910

    840

    755

    600

    455

    320

    200

    BCS-ECP 315

    1270

    1200

    1125

    1035

    955

    860

    650

    400

    145

    -

    Selection curves

    Technical data

     U [V]P [W]I [A]SCPŋt [%]Tm [°C]Tu [°C]To [°C]n [rpm]Lwa [dB(A)]
     Lwa 5Lwa 6Lwa 2
    BCS-ECP 125230850.87ESCP010-6060-253200696955
    BCS-ECP 160230830.88ESCP010-6060-253200727259
    BCS-ECP 2002301701.59ESCP010-4545-253210757559
    BCS-ECP 2502301701.32ESCP010-4545-253210777760
    BCS-ECP 3152301661.56ESCP010-6060-252550787862

    • SCP = Potentiometer 0-10V
    • ŋt = Maximum total efficiency
    • Tm = Maximum air temperature
    • Tu = Maximum ambient temperature
    • To = Minimum operating temperature
    • Lwa 2 = Casing sound power level
    • Lwa 5 = Sound power level @inlet
    • Lwa 6 = Sound power level @outlet
    • The sound power levels are measured according to DIN 45635

    Dimensions

     ØA [mm]B [mm]ØC [mm]D [mm][kg]
    BCS-ECP 125

    125

    207 ±2

    245

    290

    2.36

    BCS-ECP 160

    160

    200 ±2

    245

    290

    2.66

    BCS-ECP 200

    200

    240 ±2

    345

    390

    4.33

    BCS-ECP 250

    250

    245 ±2

    345

    390

    4.33

    BCS-ECP 315

    315

    250 ±2

    400

    445

    5.61

    Wiring diagram

    PE = green/yellow

    BU = blue

    BK = black

    RD = red

    YE = yellow

    WH = white

    HELPCopyrightSales conditionsCookie policyfujitsu-airco.be