PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

ETALINE 3N • Duct fans

3 speed mixed flow duct fan with high efficiency

Application

  • Thanks to the fact that the motor is integrated in the stator’s hub, out of the air stream, the ETALINE 3N fans can be used for slightly polluted air.
  • The ETALINE 3N fans are used for ventilation in offices, schools and small spaces, etc.

Composition

  • Compact fan housing with mounting bracket included.
  • The fan housing is made out of polyamid. The impeller balanced according to the quality of G6.3 according to DIN ISO 1940 on two Levels.
  • The motor is equipped with maintenance-free, long-life ball bearings.
  • Supply: 230Vac 1ph
  • Insulation class F – protection class IP44
  • Motor with overheat protection

Accessories

  • 3-speed switch, type SC4
  • Fitting clamp, type BMK
  • Protection grille, type BSV-S

Text for tender

Copy

Fans are of the mixed flow type and are equipped with a 3-speed motor 230Vac 1ph. Can be fitted in any position. Air volume up to 1500 m3/h. Including mounting brackets. Housing from polyamid. 3-speed motor with integrated thermal switch.

Order example

ETALINE 160L 3N 01 + SC4

ETALINE = Type of fan

160L = diameter (large housing)

3N = 3-speed motor

01 = version

SC4 = 3-speed operation switch

Air performance data

 Q [m³/h]
50Pa100Pa150Pa200Pa250Pa300Pa
ETALINE 125 3N 0133029525018010-
ETALINE 160 3N 0140036032027050-
ETALINE 160L 3N 01770710660600540440
ETALINE 200 3N 01860790680500140-
ETALINE 200L 3N 01850800740680610530
ETALINE 250 3N 0116401560148013801260570

Selection curves

Selection curves

Technical data

 U [V]P [W]I [A]ŋt [%]Tm [°C]Tu [°C]To [°C]n [rpm]Lwa [dB(A)]
Lwa 5Lwa 6Lwa 2
ETALINE 125 3N 011 x 230520.2422,38080-252740676655
ETALINE 160 3N 011 x 230530.3032.98080-252779687058
ETALINE 160L 3N 011 x 2301300.6033,15050-252614717264
ETALINE 200 3N 011 x 2301090.5032.76060-252724737763
ETALINE 200L 3N 011 x 2301300.5935,65050-252703757769
ETALINE 250 3N 011 x 2301800.82535050-252885787965

  • ŋt = Maximum total efficiency
  • Tm = Maximum air temperature
  • Tu = Maximum ambient temperature
  • To = Minimum operating temperature
  • Lwa 2 = Casing sound power level
  • Lwa 5 = Sound power level @inlet
  • Lwa 6 = Sound power level @outlet
  • The sound power levels are measured according to DIN 45635 part 2 & 38

Dimensions

 B [mm]D [mm]d [mm]E [mm]F [mm]L [mm]H [mm][kg]
ETALINE 125 3N 0119019112422242151972.4
ETALINE 160 3N 0119019115922232151972.2
ETALINE 160L 3N 0123523815922232602433.4
ETALINE 200 3N 01199201---2252053.2
ETALINE 200L 3N 0124323819922232452433.3
ETALINE 250 3N 01245250---2782597.1