The fan is of the mixed flow type. Motors can be controlled by means of an integrated EC controller. The fan is equipped with a 230V 1ph speed controllable motor or a 400V 3ph speed controllable motor, depending on the type. The fans can be fitted in any position. Air flow up to 20.000 m³/h. Housing supplied with mounting brackets. Housing made out of galvanized steel (size 250mm-355mm) or seawater resistant aluminium (size 400mm-710mm). Motor equipped with thermal protection.
CAIROX, type ETALINE EC
The fan is of the mixed flow type. Motors can be controlled by means of an integrated EC controller. The fan is equipped with a 230V 1ph speed controllable motor or a 400V 3ph speed controllable motor, depending on the type. The fans can be fitted in any position. Air flow up to 20.000 m³/h. Housing supplied with mounting brackets. Housing made out of galvanized steel (size 250mm-355mm) or seawater resistant aluminium (size 400mm-710mm). Motor equipped with thermal protection.
CAIROX, type ETALINE EC
ETALINE 400 EC K 01 + ESCP010
ETALINE = type of fan
400 = diameter
EC = EC motor
K 01 = tversion
ESCP010 = potentiometer
Air performance data
|
|
ETALINE 400 EC K 01 | 7214 | 7111 | 7000 | 6876 | 6741 | 6595 | 6270 | 5889 | 5468 | 5112 | ETALINE 450 EC K 01 | 7390 | 7275 | 7125 | 6945 | 6725 | 6475 | 5940 | 5400 | 1400 | 947 | ETALINE 500 EC K 01 | 10100 | 9875 | 9500 | 9350 | 9000 | 8750 | 8200 | 7425 | 6375 | 2000 | ETALINE 560 EC K 01 | 11300 | 11000 | 10725 | 10400 | 10050 | 9675 | 8650 | 6900 | 2520 | 1800 | ETALINE 630 EC K 01 | 14850 | 14500 | 14150 | 13850 | 13500 | 13100 | 12275 | 11350 | 3025 | 2325 | ETALINE 710 EC K 01 | 20325 | 19925 | 19500 | 19000 | 18650 | 18250 | 17290 | 16475 | 15350 | 5275 |
Selection curves
Selection curves
Technical data
|
|
ETALINE 400 EC K 01 | 1 x 230 | 1637 | 11.8 | 63.6 | 40 | 40 | -20 | 3000 | 93 | 97 | 88 | ETALINE 450 EC K 01 | 1 x 230 | 1144 | 8.2 | 69.2 | 60 | 60 | -20 | 2100 | 88 | 93 | 85 | ETALINE 500 EC K 01 | 3 x 400 | 2085 | 3.18 | 69.3 | 40 | 40 | -20 | 2100 | 91 | 96 | 86 | ETALINE 560 EC K 01 | 3 x 400 | 1642 | 2.43 | 64.1 | 60 | 60 | -20 | 1750 | 90 | 94 | 83 | ETALINE 630 EC K 01 | 3 x 400 | 2414 | 3.7 | 71.3 | 60 | 60 | -20 | 1500 | 88 | 92 | 83 | ETALINE 710 EC K 01 | 3 x 400 | 3950 | 6 | 69.5 | 60 | 60 | -20 | 1500 | 92 | 97 | 85 |
- ŋt = Maximum total efficiency
- Tm = Maximum air temperature
- Tu = Maximum ambient temperature
- To = Minimum operating temperature
- Lwa 2 = Casing sound power level
- Lwa 5 = Sound power level @inlet
- Lwa 6 = Sound power level @outlet
- The sound power levels are measured according to DIN 45635 part 2 & 38
Dimensions
|
ETALINE 400 EC K 01 | 427 | 403 | 416 | 432 | 16.5 | ETALINE 450 EC K 01 | 478 | 453 | 467 | 467 | 18.2 | ETALINE 500 EC K 01 | 523 | 504 | 515 | 512 | 24.8 | ETALINE 560 EC K 01 | 539 | 564 | 582 | 573 | 28.6 | ETALINE 630 EC K 01 | 659 | 634 | 654 | 643 | 45.2 | ETALINE 710 EC K 01 | 738 | 714 | 732 | 723 | 51.5 |
|