BUPE • Fan box

Direct driven centrifugal fan box with acoustic insulation. The range consists of 6 sizes and 9 types and covers an air flow range from 900 up to 9600 m³/h.

Application

  • BUPE fans are used for air supply or exhaust of offices, restaurants or shops

Composition

  • BUPE fan casings are manufactured from fabricated galvanized sheet steel and internally lined with high grade acoustic insulation material
  • The BUPE casing design enables the fan to be accessed from both side panels.
  • A wiring entry grommet is provided on the duct outlet panel to facilitate wiring and installation

Fan

  • Low pressure centrifugal fan with forward curved impeller manufactured from pressed and formed galvanised sheet steel
  • All impellers are factory fitted to the motors and dynamically balanced to minimise vibration

Motor

  • Closed motor

  • Protection class IP44, insulation class F
  • Supply: 230Vac 1ph or 400Vac 3ph
  • All models include a Safety Thermal Overload protection device.

NOTE: BUPE fans must never be used in free inlet configuration. Measure current at start-up and respect minimal pressure values as indicated in the table.

Options

  • Fan without casing: type DA

Accessories

  • Auto transformer type BTRN or BTRNTK
  • Clamping strip type BMK
  • Filter box type FLK-B (G4 filter) or FLF-B (F7 filter)
  • Silencer type SAR
  • Duct battery type CVA, CWA, CWK

Order example

BUPE 9-9-24 + BTRN 1-3

BUPE 9-9-24 = fan

BTRN 1-3 = speed controller

Air performance data

Qv [m³/h]

50 Pa

100 Pa

150 Pa

200 Pa

250 Pa

300 Pa

400 Pa

BUPE 7-7-14

143013501200900300--

BUPE 9-9-24

250020501800----

BUPE 9-9-37

---280026002300800

BUPE 10-10-24

3200300025001200---

BUPE 10-10-55

-----37002750

BUPE 12-9-55

--3800360030002000-

BUPE 12-12-73

--

5650

540042503600-

BUPE 12-12-11

-71006600590050003800-

Selection curves

Selection curves

Note

The BUPE fan may never be used with free inlet. There should be a minimal counter-pressure as indicated above. Please measure the current at first starting.

Technical data

U [V]P [W]I [A]

SCT

n [rpm]Lpa @ 1m [dB(A)]

BUPE 7-7-14

1 x 2301471.70BTRN-1-2143056

BUPE 9-9-24

1 x 2302452.50BTRN-1-398055

BUPE 9-9-37

1 x 2303734.10BTRN-1-5143060

BUPE 10-10-24

1 x 2302453.20BTRN-1-598055

BUPE 10-10-55

1 x 2305504.60BTRN-1-7147064

BUPE 12-9-55

1 x 2305504.50BTRN-1-798060

BUPE 12-12-73

1 x 2307368BTRN-1-1098064

BUPE 12-12-11

3 x 230 / 38011008 / 4,6

BTRN-3-10 / BTRNTK-4-60 *

98067

SCT = Transformer speed controller

Lpa = Sound pressure level

Dimensions

 

ØDI [mm]

ØDO [mm]

A [mm]

B [mm]

C [mm]

F [mm]

I [mm]

K [mm]

Kg

BUPE 7/7

250250455445455753551532

BUPE 9/9

355355555515535953558543

BUPE 10/10

400400595565590903563555

BUPE 12/9

450450675620640553569072

BUPE 12/12

450450675620640553569075