Acoustically insulated (40 mm/88 kg/m³) centrifugal fan box
BFA 125 E2 K 01 + TSC-1-15
BFA = boxfan
R = mounted roof
125 = diameter
E = controlable via transformator speed controller
2 = number of poles
K 01 = version
TSC-1-15 = speed controller
Air performance data
|
|
BFA-R 125 E2 K 01 | 307 | 283 | 243 | 211 | 170 | 130 | - | - | BFA-R 160 E2 K 01 | 356 | 310 | 269 | 226 | 173 | 123 | - | - | BFA-R 200 E2 K 01 | 675 | 614 | 550 | 485 | 422 | 361 | 229 | - | BFA-R 250 E2 K 01 | 1044 | 991 | 918 | 830 | 765 | 709 | 585 | 385 | BFA-R 355 E4 K 01 | 1982 | 1786 | 1640 | 1422 | 1253 | 1017 | 491 | - | BFA-R 400 E4 K 01 | 2208 | 1977 | 1750 | 1532 | 1323 | 1046 | 462 | - | BFA-R 450 E4 K 01 | 3403 | 3197 | 2978 | 2709 | 2413 | 2164 | 1443 | 800 | BFA-R 500 E4 K 01 | 3639 | 3375 | 3126 | 2830 | 2552 | 2275 | 1497 | 481 |
Technical data
|
|
BFA-R 125 E2 K 01 | 230 | 50 | 0.3 | TSC-1-15 | ESC-15 | 24.6 | 70 | 70 | -25 | 2386 | 55 | 68 | 54 | BFA-R 160 E2 K 01 | 230 | 49 | 0.3 | TSC-1-15 | ESC-15 | 25.5 | 70 | 70 | -25 | 2420 | 57 | 71 | 54 | BFA-R 200 E2 K 01 | 230 | 100 | 0.5 | TSC-1-15 | ESC-15 | 29.1 | 80 | 80 | -25 | 2480 | 64 | 76 | 59 | BFA-R 250 E2 K 01 | 230 | 171 | 0.8 | TSC-1-15 | ESC-15 | 39 | 60 | 55 | -25 | 2680 | 66 | 74 | 59 | BFA-R 355 E4 K 01 | 230 | 237 | 1.3 | TSC-1-15 | ESC-15 | 38.5 | 45 | 45 | -25 | 1368 | 66 | 75 | 61 | BFA-R 400 E4 K 01 | 230 | 242 | 1.3 | TSC-1-15 | ESC-15 | 39.5 | 40 | 40 | -25 | 1370 | 67 | 76 | 62 | BFA-R 450 E4 K 01 | 230 | 451 | 2.6 | TSCTK-1-40 | ESCTK-5 | 41.3 | 65 | 65 | -25 | 1374 | 73 | 82 | 67 | BFA-R 500 E4 K 01 | 230 | 466 | 2.7 | TSCTK-1-40 | ESCTK-5 | 41.2 | 65 | 65 | -25 | 1382 | 73 | 82 | 67 |
- SCT = Transformer speed controller
- SCE = Electronic speed controller
- ** Caution: an electronic controller can produce a magnetic noise
- ŋt = Maximum total efficiency
- Tm = Maximum air temperature
- Tu = Maximum ambient temperature
- To = Minimum operating temperature
- Lwa 2 = Casing sound power level
- Lwa 5 = Sound power level @inlet
- Lwa 6 = Sound power level @outlet
- The sound power levels are measured according to DIN 45635 part 2 & 38
Dimensions
|
BFA-R 125 E2 K 01 | 124 | 378 | 380 | 232 | 119 | 136 | 426 | 384 | 11.6 | BFA-R 160 E2 K 01 | 159 | 378 | 380 | 232 | 137 | 133 | 426 | 384 | 11.8 | BFA-R 200 E2 K 01 | 199 | 460 | 480 | 287 | 165 | 168 | 508 | 466 | 17.7 | BFA-R 250 E2 K 01 | 249 | 460 | 480 | 287 | 190 | 148 | 508 | 466 | 18.9 | BFA-R 355 E4 K 01 | 354 | 650 | 680 | 492 | 234 | 273 | 698 | 656 | 41.8 | BFA-R 400 E4 K 01 | 399 | 650 | 680 | 492 | 256 | 263 | 698 | 656 | 41.0 | BFA-R 450 E4 K 01 | 449 | 800 | 780 | 547 | 276 | 283 | 847 | 805 | 67.5 | BFA-R 500 E4 K 01 | 499 | 800 | 780 | 587 | 302 | 293 | 847 | 805 | 69.5 |
|