PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

BFA-R EC • Fan casing - 40 mm insulation with EC motor

  • Insulated fan boxes
  • 40 mm insulation
  • Direct driven
  • EC motor

Sound insulated duct fan (40 mm insulation), centrifugal fan with EC motor

Application

  • BFA-R EC fans are used for ventilation in many applications where low noise levels have to be respected, such as offices, restaurants, technical rooms or other
  • The BFA-R EC can be controlled by an external analogue signal (0-10 V): ideal for realising a control in function of CO2, temperature, constant pressure or humidity
  • Can be used for air supply or extraction
  • Indoor and outdoor installation possible without additional accessories

Composition

  • Casing procured from galvanised steel
  • Removable panel with mounted roof, fixed with screws for easy inspection of motor
  • Isolation: high performance wool (88 kg/m³) with fireclass A1 according to DIN EN13501-1
  • Fan with backwards curved blades
  • Only suction fan, completely synthetic
  • Isolation class motor B for diameter 355 and 400, class F for all other diameters
  • Protection classes:
    • BFA-R 125 - 200 EC K 01 et BFA-R 355 - 500 EC K 01: IP54 for the motor protection class and the whole fan
    • BFA-R 250 - 315 EC K 01: motor protection class IP33, IP54 for the whole fan
    • BFA-R 450 - 500 EC K 01: motor protection class IP55, IP54 for the whole fan
  • Terminal box IP66 with cable glands

Accessories

  • Potentiometer, type ESCP010
  • Flexible connection, type BMK

Text for tender

Copy
  • The centrifugal fan box shall be acoustically insulated with 40 mm rock wool fibrewith a density of minimum 88 kg/m³. The closed motor shall be of the direct driven type, IP44, insulation class B, with thermal protection, voltage controllable with auto transformer
  • Cairox Type BFA-R EC

Order example

BFA-R 125 EC K 01 + ESCP010


Explination:

BFA = type of fan

R = mounted roof

125 = diameter

EC = type of motor

K 01 = versie

ESCP010 = potentiometer

Air performance data

 Q [m³/h]
100 Pa150 Pa200 Pa250 Pa300 Pa400 Pa500 Pa600Pa
BFA-R 125 EC K 01435410390375350300250200
BFA-R 160 EC K 01510475450430400335265190
BFA-R 200 EC K 01745691630580535410250-
BFA-R 250 EC K 01113810781016948874745623500
BFA-R 315 EC K 01165015731465139513001125900750
BFA-R 355 EC K 011680149713001142900600--
BFA-R 400 EC K 011855161213991185925590--
BFA-R 450 EC K 0137353495316829132646225417091263
BFA-R 500 EC K 0139603658337431142850223216551219

Technical data

 U [V]P [W]I [A]ŋt [%]Tm [°C]Tu [°C]To [°C]n [rpm]Lwa [dB (A)]
Lwa 5Lwa 6Lwa 2
BFA-R 125 EC K 011x2301060.8933.06060-303440637864
BFA-R 160 EC K 011x2301040.8835.06060-303466668162
BFA-R 200 EC K 011x2301181.0238.76060-302878647961
BFA-R 250 EC K 011x2302041.841.67070-302870778973
BFA-R 315 EC K 011x2302741.9144.85555-302620769073
BFA-R 355 EC K 011x2301651.3947.26060-251295647360
BFA-R 400 EC K 011x2301651.4048.76060-251298667561
BFA-R 450 EC K 011x2305072.3049.15050-251585778570
BFA-R 500 EC K 011x2305062.3348.85050-251593778669

  • ŋt = Maximum total return
  • Tm = Maximum airtemperature
  • Tu = Maximum casing temperature
  • To = Minimum working temperature
  • Lwa 2 = Casing sound power level
  • Lwa 5 = Sound power level @inlet
  • Lwa 6 = Sound power level @outlet
  • The sound power levels are measured according to DIN 45635 part 2 & 38

Dimensions

 Ø N [mm]A [mm]B [mm]C [mm]D [mm]E [mm]F [mm]G [mm][kg]
BFA-R 125 EC K 0112437838023211913646038411.80
BFA-R 160 EC K 0115937838023213613346038411.90
BFA-R 200 EC K 0119946048028716516854246618.70
BFA-R 250 EC K 0124946048028719014857146618.60
BFA-R 315 EC K 0131451054038721620861751625.00
BFA-R 355 EC K 0135465068049223427375765640.40
BFA-R 400 EC K 0139965068049225626379765640.00
BFA-R 450 EC K 0144980078054727628394680565.30
BFA-R 500 EC K 0149980078058730229394680567.3
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be

Requesting information. Please wait a moment...