Sound insulated duct fan (40 mm insulation), centrifugal fan with EC motor
Application
BFA-R EC fans are used for ventilation in many applications where low noise levels have to be respected, such as offices, restaurants, technical rooms or other
The BFA-R EC can be controlled by an external analogue signal (0-10 V): ideal for realising a control in function of CO2, temperature, constant pressure or humidity
Can be used for air supply or extraction
Indoor and outdoor installation possible without additional accessories
Composition
Casing procured from galvanised steel
Removable panel with mounted roof, fixed with screws for easy inspection of motor
Isolation: high performance wool (88 kg/m³) with fireclass A1 according to DIN EN13501-1
Fan with backwards curved blades
Only suction fan, completely synthetic
Isolation class motor B for diameter 355 and 400, class F for all other diameters
Protection classes:
BFA-R 125 - 200 EC K 01 et BFA-R 355 - 500 EC K 01: IP54 for the motor protection class and the whole fan
BFA-R 250 - 315 EC K 01: motor protection class IP33, IP54 for the whole fan
BFA-R 450 - 500 EC K 01: motor protection class IP55, IP54 for the whole fan
Terminal box IP66 with cable glands
Accessories
Potentiometer, type ESCP010
Flexible connection, type BMK
Text for tender
The centrifugal fan box shall be acoustically insulated with 40 mm rock wool fibrewith a density of minimum 88 kg/m³. The closed motor shall be of the direct driven type, IP44, insulation class B, with thermal protection, voltage controllable with auto transformer
Cairox Type BFA-R EC
The centrifugal fan box shall be acoustically insulated with 40 mm rock wool fibrewith a density of minimum 88 kg/m³. The closed motor shall be of the direct driven type, IP44, insulation class B, with thermal protection, voltage controllable with auto transformer
Cairox Type BFA-R EC
Order example
BFA-R 125 EC K 01 + ESCP010
Explination:
BFA = type of fan
R = mounted roof
125 = diameter
EC = type of motor
K 01 = versie
ESCP010= potentiometer
Articles
Article selection assistant
Type
Volume [L]
Article number
Type
Volume [L]
E-shop
J019006000200
VKG-HC 200
200
J019006000300
VKG-HC 300
300
J019006000500
VKG-HC 500
500
J019006000750
VKG-HC 750
750
J019006001000
VKG-HC 1000
1000
J019006001500
VKG-HC 1500
1500
J019006002000
VKG-HC 2000
2000
J019006002500
VKG-HC 2500
2500
J019006003000
VKG-HC 3000
3000
J019006004000
VKG-HC 4000
4000
J019006005000
VKG-HC 5000
5000
=> Stock product central warehouse, except sales
Air performance data
Q [m³/h]
100 Pa
150 Pa
200 Pa
250 Pa
300 Pa
400 Pa
500 Pa
600Pa
BFA-R 125 EC K 01
435
410
390
375
350
300
250
200
BFA-R 160 EC K 01
510
475
450
430
400
335
265
190
BFA-R 200 EC K 01
745
691
630
580
535
410
250
-
BFA-R 250 EC K 01
1138
1078
1016
948
874
745
623
500
BFA-R 315 EC K 01
1650
1573
1465
1395
1300
1125
900
750
BFA-R 355 EC K 01
1680
1497
1300
1142
900
600
-
-
BFA-R 400 EC K 01
1855
1612
1399
1185
925
590
-
-
BFA-R 450 EC K 01
3735
3495
3168
2913
2646
2254
1709
1263
BFA-R 500 EC K 01
3960
3658
3374
3114
2850
2232
1655
1219
Technical data
U [V]
P [W]
I [A]
ŋt [%]
Tm [°C]
Tu [°C]
To [°C]
n [rpm]
Lwa [dB (A)]
Lwa 5
Lwa 6
Lwa 2
BFA-R 125 EC K 01
1x230
106
0.89
33.0
60
60
-30
3440
63
78
64
BFA-R 160 EC K 01
1x230
104
0.88
35.0
60
60
-30
3466
66
81
62
BFA-R 200 EC K 01
1x230
118
1.02
38.7
60
60
-30
2878
64
79
61
BFA-R 250 EC K 01
1x230
204
1.8
41.6
70
70
-30
2870
77
89
73
BFA-R 315 EC K 01
1x230
274
1.91
44.8
55
55
-30
2620
76
90
73
BFA-R 355 EC K 01
1x230
165
1.39
47.2
60
60
-25
1295
64
73
60
BFA-R 400 EC K 01
1x230
165
1.40
48.7
60
60
-25
1298
66
75
61
BFA-R 450 EC K 01
1x230
507
2.30
49.1
50
50
-25
1585
77
85
70
BFA-R 500 EC K 01
1x230
506
2.33
48.8
50
50
-25
1593
77
86
69
ŋt = Maximum total return
Tm = Maximum airtemperature
Tu = Maximum casing temperature
To = Minimum working temperature
Lwa 2 = Casing sound power level
Lwa 5 = Sound power level @inlet
Lwa 6 = Sound power level @outlet
The sound power levels are measured according to DIN 45635 part 2 & 38