PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

MVX-F9 • Replacement filters for MVB, GTDHR, GTDI and EVENTYS

High efficiency filter class F9 - ePM1 80% ISO 16890
for mounting in filter box type MVX-PF-F7

Composition

  • High efficienty filter F9
  • ISO 16890 ePM1 80%
  • Filter width depending on to the serial number :
    • Serial number up to 192254 : Filter width 98 mm
    • Serial number from 192255 : Filter width 48 mm
  • 10 times more filtration surface than gravimetric filter
  • Supplied as a separate component, unmounted; factory mounted upon request
  • Recommended final pressure lossp up to 450Pa
  • Recommended final ecological pressure loss maximum 250 Pa
  • Filter replacement recommended at 300Pa
  • The MVX-PF-F7 box can also be equipped with a F7 remplacement filter. This filter can be replaced by a finer filter class F9 after startup of the installation.

Artikelen

Article selection assistant
Type
Cooling capacity [kW]
Heating Capacity* [kW]
# pipes
AC or EC engine
Horizontal or vertical
Hydraulic connection
Article number Type Cooling capacity [kW] Heating Capacity* [kW] # pipes AC or EC engine Horizontal or vertical Hydraulic connection E-shop
J035530012010 UTV-10/L/2P 3.83 5.02 2 AC Vertical Left
J035530012020 UTV-20/L/2P 7.05 8.61 2 AC Vertical Left
J035530012030 UTV-30/L/2P 9.2 11.3 2 AC Vertical Left
J035530012040 UTV-40/L/2P 10.6 12.94 2 AC Vertical Left
J035530012050 UTV-50/L/2P 13.1 16.99 2 AC Vertical Left
J035530013010 UTV-10/R/2P 3.83 5.02 2 AC Vertical Right
J035530013020 UTV-20/R/2P 7.05 8.61 2 AC Vertical Right
J035530013030 UTV-30/R/2P 9.2 11.3 2 AC Vertical Right
J035530013040 UTV-40/R/2P 10.6 12.94 2 AC Vertical Right
J035530013050 UTV-50/R/2P 13.1 16.99 2 AC Vertical Right
J035530014110 UTV-10/L/4P 3.6 4.18 4 AC Vertical Left
J035530014120 UTV-20/L/4P 7.00 7.01 4 AC Vertical Left
J035530014130 UTV-30/L/4P 9.01 9.16 4 AC Vertical Left
J035530014140 UTV-40/L/4P 9.57 10.60 4 AC Vertical Left
J035530014150 UTV-50/L/4P 13.63 12.65 4 AC Vertical Left
J035530015010 UTV-10/R/4P 3.6 4.18 4 AC Vertical Right
J035530015020 UTV-20/R/4P 7.00 7.01 4 AC Vertical Right
J035530015030 UTV-30/R/4P 9.01 9.16 4 AC Vertical Right
J035530015040 UTV-40/R/4P 9.57 10.60 4 AC Vertical Right
J035530015050 UTV-50/R/4P 13.63 12.65 4 AC Vertical Right
J035530022010 UTC-10/L/2P 3.83 5.02 2 AC Horizontal Left
J035530022020 UTC-20/L/2P 7.05 8.61 2 AC Horizontal Left
J035530022030 UTC-30/L/2P 9.20 11.33 2 AC Horizontal Left
J035530022040 UTC-40/L/2P 10.60 12.94 2 AC Horizontal Left
J035530022050 UTC-50/L/2P 13.10 16.99 2 AC Horizontal Left
J035530023010 UTC-10/R/2P 3.83 5.02 2 AC Horizontal Right
J035530023020 UTC-20/R/2P 7.05 8.61 2 AC Horizontal Right
J035530023030 UTC-30/R/2P 9.20 11.33 2 AC Horizontal Right
J035530023040 UTC-40/R/2P 10.60 12.94 2 AC Horizontal Right
J035530023050 UTC-50/R/2P 13.10 16.99 2 AC Horizontal Right
J035530032010 UTC-10/L/4P 3.60 4.18 4 AC Horizontal Left
J035530032020 UTC-20/L/4P 7 7.01 4 AC Horizontal Left
J035530032030 UTC-30/L/4P 9.01 9.16 4 AC Horizontal Left
J035530032040 UTC-40/L/4P 9.57 10.60 4 AC Horizontal Left
J035530032050 UTC-50/L/4P 13.63 12.65 4 AC Horizontal Left
J035530033010 UTC-10/R/4P 3.60 4.18 4 AC Horizontal Right
J035530033020 UTC-20/R/4P 7 7.01 4 AC Horizontal Right
J035530033030 UTC-30/R/4P 9.01 9.16 4 AC Horizontal Right
J035530033040 UTC-40/R/4P 9.57 10.60 4 AC Horizontal Right
J035530033050 UTC-50/R/4P 13.63 12.65 4 AC Horizontal Right
*According to Eurovent at highest speed 0Pa

Pressure loss graph

Pressure loss graph

Dimensions

 L [mm]H [mm]
MVX4-F9390320
MVX5-F9490420
MVX6-F9590520
MVX7-F9690620
MVX8-F9

720

458
MVX9-F9

820

558
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be