MB blowers are used for applications where slightly dusty air has to be removed.
The fan is suitable for handling air up to 80°C.
A protection hood is required for outside use.
Composition
The casing is made of spot welded sheet steel and painted in epoxy RAL 7031 with a total thickness of 80µ. The strong base frame support the motor
The impeller with forward curved blades is dynamically and statically balanced grade G6.3 according to ISO 1940/1. The many concave blades (30 or more) gives a great air volume at low speed which is benefit to a low noise level.
Totally closed squirrel-cage asynchronous motor
Protection IP55 – Insulation F
Supply: 230Vac 1ph 50Hz (Steinmetz type) - 230/400Vac 3ph 50Hz and 400/690Vac from 5.5kW motors
Accessories
Inlet flange, type RNFLA
Outlet guard, type RDP
Square/round piece on outlet, type RC
5-steps transformer speed controller 230V, type TSCTK-1
5-steps transformer speed controller 3x400v, type TSCTK-4
Frequency converter 1x230V, type FIS(-C)-11-B
Frequency converter 3x400V, type FIS(-C)-44-B
Options
ATEX II 2G T3 version
High temperature 180°C version
2-speed motors
Stainless steel version
Belt driven version
Order example
MB253/400V
MB253 = fan
400V = supply 3ph
BTRN = speed controller
RNFL = inlet flange
RDP = outlet guard
Square/round piece
Artikelen
Article selection assistant
Type
Article number
Type
E-shop
J017105099170
HRC PK CASCADE - 6P10
Air performance data
Q [m³/h]
200Pa
300Pa
400Pa
500Pa
600Pa
750Pa
MB 201
1200
-
-
-
-
-
MB 253
3000
2600
1500
-
-
-
MB 302
-
5300
4800
4200
3000
-
MB 353
9000
8500
8000
7500
6800
5000
MB 403
-
-
-
12500
12000
11000
MB 404
8000
7000
5700
1800
-
-
MB 455
12000
11250
10000
8200
3800
-
MB 503
-
18000
17500
17000
16000
14000
Attention
The MB fan may never be used with free inlet. There should be a minimal counter-pressure as shown in the table above. Please measure the current at first startup.
The motorspeed is not adjustable by means of an electronic controller.
Selection curves
Technical data
U [V]
P [kW]
I [A]
SC
n [rpm]
Lpa @ 1,5 m [dB(A)]
MB 201
1 x 230
0.25
2.32
TSCTK 1-30 / FIS-1120E-0.37-B
1380
63
MB 253
1 x 230
0.55
4.03
TSCTK 1-50 / FIS-1120E-0.75-B
1380
70
MB 302
1 x 230
1.10
7.27
TSCTK 1-110 / FIS-1120E-1.1-B
1380
74
MB 201
3 x 400
0.25
0.77
TSCTK 4-20 / FIS-4420E-0.75-B
1380
63
MB 253
3 x 400
0.55
1.44
TSCTK 4-20 / FIS-4420E-0.75-B
1380
70
MB 302
3 x 400
1.10
2.55
TSCTK 4-30 / FIS-4420E-1.5-B
1380
74
MB 353
3 x 400
3
6.40
TSCTK-4-70 / FIS-4420E-4.0-B
1410
79
MB 403
3 x 400
5.50
11.40
TSCTK-4-140 / FIS-4420E-5.5-B
1410
82
MB 404
3 x 400
1.50
3.90
TSCTK-4-40 / FIS-4420E-1.5-B
920
75
MB 455
3 x 400
3
7.20
TSCTK-4-110 / FIS-4420E-4.0-B
940
79
MB 503
3 x 400
7.50
17
FIS-4420E-7.5-B
950
83
SC = Speed controller
Lpa = Sound pressure level
Sound pressure Lpa measured according to UNI EN10531
Attention
In the orientation drawing, the motor is directed towards you. The desired orientation has to be specified upon order
A protection hood is
required for outdoor mounting