HF R • Anti-acid centrifugal fans

Anti-acid centrifugal fans

Brand

  • Hürner Luft- und Umwelttechnik

Application

  • These fans are suitable for extraction of aggressive gasses.
  • They are particularly applicable for the extraction in:
    • Laboratia
    • Chemical and petrochemical industry
    • Metal treatment industry
    • Food and beverage industry
    • Water treatment systems

Composition

  • The casing is made of fire resistant polyethylene (PEs/PE-FR,RAL7036)
  • The housing is fitted with a splinter guard and condensate drain at its deepest point
  • The impeller is made of fire-resistant polypropylene (PPs/PP-FR) and is of the backward-curved blade type, statically and dynamically balanced according to Q 6.3 (VDI 2056)
  • In the case of direct drive, the impeller is directly mounted on the motor shaft by a Taperlock bush
  • The impeller can be demounted without removing the housing
  • Squirel cage asynchronous motor
  • Motor with PTC for use with frequency inverter
  • Supply: 400Vac 3ph 50 Hz
  • Protection: IP55
  • Insulation class: F

Accessories

  • Flexible connections made of PVC, type PVC
  • Set anti-vibration mounth, type AVM
  • Safety switch, type SCHALTER
  • Motor protection cover, type KC
  • Frequency controller 3x400V, type FIS(-C)-44-B

Options

  • ATEX version in accordance with directive ATEX 94/9/CE:
    • ATEX 3G (ATEX zone 2 inside/outside)
    • ATEX 2G (ATEX zone 1 inside/outside) with PE-el housing and PP-el impeller for diameters: HF R 125, 160, 200, 250, 315, 400 en 500
  • Two speed motors
  • 230Vac (plug&play - not suitable for transformer and frequency control)

Other available products

These HF R fans are just a few of the very wide range of HF-fans. For a selection and price, perfectly tailored to your project, please send your request to engineering@cairox.be.

Order example

  • HF R 160-17D 400V 1500 rpm GR090

HF R = type of fan

160 = diameter

17 = type of impeller

D = direct driven / R = belt driven

400V = supply

1500 rpm = speed

GR090 = casing orientation

Air performance data

 

Q [m³/h]

75Pa

100Pa

150Pa

200Pa

250Pa

300Pa

400Pa

500Pa

600Pa

750Pa

1000Pa

HF R125 17D

375300150--------

HF R140 17D

550500400200-------

HF R160 17D

-800700600300------

HF R180 17D

--1050950700600-----

HF R200 17D

---145012601080600----

HF R250 17D

----31002880260021601440--

HF R280 17D

-----44004000360032402160-

HF R315 15D

------3960360032402160-

HF R355 15D

-------5760540045002520

HF R400 15D

--------720068405760

HF R450 15D

-----7200684057604800--

HF R500 15D

------10440972086406480-

Attention

The given pressure is the total pressure.

Selection curves

Selection curves

Technical data

 U [V]P [kW]I [A]SCFTm [°C]n [rpm]Lpa @ 1m [dB(A)]
Lpa 5 = Lpa 6Lpa 2
HF R125 17D3x4000.120.52FIS-4420E-0.75-B6014505341
HF R140 17D3x4000.120.52FIS-4420E-0.75-B6014505644
HF R160 17D3x4000.250.82FIS-4420E-0.75-B6014506048
HF R180 17D3x4000.250.82FIS-4420E-0.75-B6014506452
HF R200 17D3x4000.250.82FIS-4420E-0.75-B6014506755
HF R250 17D3x4000.551.60FIS-4420E-0.75-B6014507462
HF R280 17D3x4001.12.70FIS-4420E-1.5-B6014507766
HF R315 15D3x4001.12.70FIS-4420E-1.5-B6014507162
HF R355 15D3x4001.53.3FIS-4420E-1.5-B6014507566
HF R400 15D3x40036.33FIS-4420E-4.0-B6014507869
HF R450 15D3x4001.53.75FIS-4420E-1.5-B609506960
HF R500 15D3x4002.25.29FIS-4420E-2.2-B609507164

  • SCF = Speed controller
  • Tm = Maximum air temperature
  • Lpa 2 = Sound pressure level measured at 1 m distance with ducted inlet and outlet
  • Lpa 5 = Lpa 6 = Sound pressure level measured at 1 m distance in free field
  • Sound pressure level Lpa measured according to DIN 45635

Attention

At the orientation drawing, the motor is directed towards you.

Dimensions

 

A [mm]

B [mm]

C [mm]

E [mm]

F [mm]

G [mm]

H [mm]

ØD [mm]

J [mm]

K [mm]

L [mm]

M [mm]

N [mm]

R [mm]

X max. [mm]

[kg]

HF R125

366,5

435

422

248298

122

238

125

212

154

248

137

182

150

504

12

HF R140

409

462

428

248298

129

256140

226

172248149201167

518

13

HF R160

464

508

479

290

340139280160

245

196290170231188

550

22

HF R180

522

558

517

314364

151

310

180269

221

314190257211

629

27

HF R200

582

612

550

334

384

162

342

200292244334212287238

652

31

HF R250

732

728

635

400450184

415

250335

313

400266357294

736

49

HF R280

816

804

711

460

510

200455280367

350

460301401326

768

62

HF R315

920,5

939

731

424474252510315439

393

424335459370

840

65

HF R355

1030

1061

836

665

745

271595355476

436

376371509416

877

97

HF R400

1141

1154

888

723

803

290650400515

484

412415564457

916

87

HF R450

1297

1311

994

814894323730450580556478479637516

1100

116

HF R500

1469

1411

1052893973337810500609623530540718596

1284

123