GTDHR First S • High effiency heat recovery units

Heat recovery unit with high efficiency 90%

Brand

  • R-COVERY by ZEHNDER CALADAIR

Application

  • Ventilation for non-residential and industrial applications

Certification

  • Heat exchanger is Eurovent certified
  • Efficiency of the heat exchanger of more than 90% EN308), in accordance with RT2012 and the directive ErP 2009/125/EC
  • Construction according to EN 1886
  • Classifications: L1 T3 TB2 D1
  • Filter leakage class: F9

Accessories

  • Airtight control valve AKH
  • MVX-RM
  • MVX-AGC
  • MTS

Order example

GTDHR 9023 F S -L

Explanation

GTDHR = Type heat recovery unit

9023 = Size 6

F = First

S = Season

L = Configuration (configuration P only available on demand)

Articles

Article selection assistant
Diameter [mm]
Article number Type [mm] Diameter [mm] Length [m] E-shop
C020403082000 Sonoflex 25 82 82 10
C020403102000 Sonoflex 25 102 102 10
C020403112000 Sonoflex 25 112 112 10
C020403127000 Sonoflex 25 127 127 10
C020403133000 Sonoflex 25 133 133 10
C020403140000 Sonoflex 25 140 140 10
C020403152000 Sonoflex 25 152 152 10
C020403165000 Sonoflex 25 165 165 10
C020403185000 Sonoflex 25 185 185 10
C020403203000 Sonoflex 25 203 203 10
C020403229000 Sonoflex 25 229 229 10
C020403254000 Sonoflex 25 254 254 10
C020403280000 Sonoflex 25 280 280 10
C020403305000 Sonoflex 25 305 305 10
C020403315000 Sonoflex 25 315 315 10
C020403356000 Sonoflex 25 356 356 10
C020403406000 Sonoflex 25 406 406 10
C020403457000 Sonoflex 25 457 457 10
C020403508000 Sonoflex 25 508 508 10
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
=> Article with a volume discount
Price per box (10 m)

Selection curves

Selection curves

Selection curves

Selection curves

Selection curves

  • Pab [W] * = Absorbed power per fan
  • Lpa @ 4m = Sound pressure level in free field with inlets and outlets connected

Technical data

 Qmax [m³/h]Psmax @ Qmax [Pa]U [V]P [W]Imax [A]tm [°C]to [°C]IP
GTDHR 9008
800*250*1 x 2302 x 2203.460-20IP44
GTDHR 9010
980*500*1 x 2302 x 4804.360-20IP54
GTDHR 9016
1550*400*1 x 2302 x 4804.360-20IP54
GTDHR 9023
2300*350*1 x 2302 x 700640-20IP54
GTDHR 9035
3500*700*3 x 4002 x 25007.740-20IP54

* Fan curve is adjustable by means of potentiometers
  • tm = Maximum air temperature
  • to = Minimum operating temperature

Horizontal configurations - side by side flow - top view

Blue arrow: Fresh air

Purple arrow: Return air


Configuration P is only available on demand

Product drawing horizontal configuration

Dimensions


Ø [mm]A [mm]B [mm]C [mm]D [mm]E [mm]F [mm]F1 [mm]F2 [mm][kg]
GTDHR First S 9008
315
20109155052554051097362517210
GTDHR First S 9010
315
20109155052554051097362517215
GTDHR First S 9016
400223011156053055051261362607295
GTDHR First S 9023
450234513157053556051376362607390
GTDHR First S 9035
500262515158054057051520450655545

Attention

  • The GTDHR 9048 and 9070 only exist in vertical configuration