PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

GTDHR First S • High effiency heat recovery units

Heat recovery unit with high efficiency 90%

Brand

  • R-COVERY by ZEHNDER CALADAIR

Application

  • Ventilation for non-residential and industrial applications

Certification

  • Heat exchanger is Eurovent certified
  • Efficiency of the heat exchanger of more than 90% EN308), in accordance with RT2012 and the directive ErP 2009/125/EC
  • Construction according to EN 1886
  • Classifications: L1 T3 TB2 D1
  • Filter leakage class: F9

Accessories

  • Airtight control valve AKH
  • MVX-RM
  • MVX-AGC
  • MTS

Order example

GTDHR 9023 F S -L

Explanation

GTDHR = Type heat recovery unit

9023 = Size 6

F = First

S = Season

L = Configuration (configuration P only available on demand)

Selection curves

Selection curves

Selection curves

Selection curves

Selection curves

  • Pab [W] * = Absorbed power per fan
  • Lpa @ 4m = Sound pressure level in free field with inlets and outlets connected

Technical data

 Qmax [m³/h]Psmax @ Qmax [Pa]U [V]P [W]Imax [A]tm [°C]to [°C]IP
GTDHR 9008
800*250*1 x 2302 x 2203.460-20IP44
GTDHR 9010
980*500*1 x 2302 x 4804.360-20IP54
GTDHR 9016
1550*400*1 x 2302 x 4804.360-20IP54
GTDHR 9023
2300*350*1 x 2302 x 700640-20IP54
GTDHR 9035
3500*700*3 x 4002 x 25007.740-20IP54

* Fan curve is adjustable by means of potentiometers
  • tm = Maximum air temperature
  • to = Minimum operating temperature

Horizontal configurations - side by side flow - top view

Blue arrow: Fresh air

Purple arrow: Return air


Configuration P is only available on demand

Product drawing horizontal configuration

Dimensions


Ø [mm]A [mm]B [mm]C [mm]D [mm]E [mm]F [mm]F1 [mm]F2 [mm][kg]
GTDHR First S 9008
315
20109155052554051097362517210
GTDHR First S 9010
315
20109155052554051097362517215
GTDHR First S 9016
400223011156053055051261362607295
GTDHR First S 9023
450234513157053556051376362607390
GTDHR First S 9035
500262515158054057051520450655545

Attention

  • The GTDHR 9048 and 9070 only exist in vertical configuration
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be