This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
High efficiency heat recovery units with low energy consumption. The Flair units are available in different sizes and versions, applicable for air flow rates up to ≤ 600 m³/h. The units are supplied as standard with an integrated touch screen with a position switch, ball-siphon, ModBus communication and energetic modulating préheater. A large range of wireless or wired conrtrollers, sensors and other accessories is also available as an option.
Brand
Brink
Application
Ventilation with heat recovery for residential and non-residential applications where high efficiency is acquired
Applicable for air flows up to 600 m³/h
Available in different configurations
For inside installation
Specifications
Modulating electric preheater
‘Bypass boost’ function
Tension: 230 Vac
ModBus communication
Filterwizard for end user
Possibilty to upgrade to Plus version by installing an additional pcb
Composition
Constant flow EC motors (EBM) with integrated anemometer
TFT touch screen with integrated 4 positions switch and wizard for servicing
Siphon with 32 mm connection
Automatic bypass (100%) with actuator
Casing of epoxy steel
Round connection with diameter 160/180/200 mm
2 x ISO Coarse 60% filters
Certification
All Flair units are tested according NBN EN 308 and PassivHaus certified
Accessories
Wireless controllers and room sensors, type FLR-RF
Wired touch-controller with weekly program, type TC E-BUS
Digital controller with weekly program, type DCREN AC
Four position switch with filter indication, type CVREN 4
Wireles 4 position switch, type RFREN 4
Humidity sensor (in-duct), type HRT REN
CO2-sensors (max. 4 pieces) via eBus connection, type CO2 REN E-BUS
2-Zone demand controlled ventilation based on time CO2, type DCV
Replacement filter, type FS FLR
Optional pcb for upgrade to Plus-version, type PCB PLUS FLAIR
Mounting chair, type MC FLAIR
Additional external pre- or post-heating battery, type CVR-VNF
Order example
FLAIR 325 R 4/0
Explanation
FLAIR = type of heat recovery unit
325 = max. air volume in m³/h
R = right version, L = left version
4/0 = 4 connections on top
Artikelen
Article selection assistant
Type
Air flow [m³/h]
Article number
Type
Air flow [m³/h]
E-shop
Spare parts
I100114225011
FLAIR 225 4/0 L BE
225
I100114225211
FLAIR 225 4/0 R BE
225
I100114325011
FLAIR 325 4/0 L BE
325
I100114325021
FLAIR 325 2/2 L BE
325
I100114325211
FLAIR 325 4/0 R BE
325
I100114325221
FLAIR 325 2/2 R BE
325
I100114400011
FLAIR 400 4/0 L BE
400
I100114400021
FLAIR 400 2/2 L BE
400
I100114400211
FLAIR 400 4/0 R BE
400
I100114400221
FLAIR 400 2/2 R BE
400
I100114450011
FLAIR 450 4/0 L EU
450
I100114450211
FLAIR 450 4/0 R EU
450
I100114600011
FLAIR 600 4/0 L EU
600
I100114600211
FLAIR 600 4/0 R EU
600
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
Technical data
FLAIR 225
Q [m³/h]
40
50
100
150
225
Ps [Pa]
3
6
5
10
20
40
44
89
100
200
P [W]
7,9
8,2
8
8,5
13,2
15,9
26,2
34
61,5
82
[A]
0,1
0,11
0,1
0,1
0,13
0,15
0,22
0,29
0,48
0,63
FLAIR 325
[m³/h]
50
100
150
250
325
[Pa]
2
5
9
19
21
43
59
118
100
200
[W]
6,1
6,4
8,2
9,7
15,4
19,4
46,9
61,4
87,2
116,5
[A]
0,08
0,08
0,09
0,11
0,16
0,19
0,42
0,53
0,73
0,94
FLAIR 400
[m³/h]
50
100
200
300
400
[Pa]
2
3
6
13
25
50
56
113
100
200
[W]
4,4
4,6
5,3
6,4
22,7
28,5
62,6
78,9
126,6
160,8
[A]
0,06
0,06
0,07
0,08
0,25
0,31
0,58
0,71
1,01
1,26
FLAIR 450
[m³/h]
75
100
200
300
450
[Pa]
3
6
5
10
20
40
44
89
100
200
[W]
10,4
10,8
12,4
13,2
17,6
23,8
51,9
69,3
149,5
198,8
[A]
0,17
0,17
0,19
0,19
0,2
0,27
0,53
0,69
1,32
1,68
FLAIR 600
[m³/h]
100
150
300
500
600
[Pa]
3
6
6
13
25
50
69
139
100
188
[W]
12,1
12,5
17,2
18,3
44,5
54,2
166,6
203,1
250
288
[A]
0,18
0,19
0,23
0,24
0,46
0,55
1,45
1,71
2,11
2,3
Sound data
FLAIR 225
Q [m³/h]
50
100
100
150
150
225
225
Ps [Pa]
25
25
50
50
100
100
150
Lwa 2 [dB(A)]
28
31
33,5
38,5
40,5
45,5
47
Lwa 5 [dB(A)]
<30
<34,5
<36,5
44
43
47,5
48,5
Lwa 6 [dB(A)]
43,5
48,5
50,5
55
57,5
62,5
64,5
FLAIR 325
Q [m³/h]
100
150
150
200
200
250
250
325
Ps [Pa]
25
25
50
50
100
100
150
150
Lwa 2 [dB(A)]
27
34
35
40
41
46
46
51
Lwa 5 [dB(A)]
32
40
38
46
44
49
49
55
Lwa 6 [dB(A)]
44
49
51
55
57
61
62
69
FLAIR 400
Q [m³/h]
150
250
350
400
Ps [Pa]
25
50
100
100
Lwa 2 [dB(A)]
37
43,5
52
55
Lwa 5 [dB(A)]
43,5
46,5
51
61
Lwa 6 [dB(A)]
50
58
69,5
71
FLAIR 450
Q [m³/h]
100
200
200
300
300
450
450
Ps [Pa]
25
25
50
50
100
100
150
Lwa 2 [dB(A)]
<38,1
36.5
42
45.5
42.5
49
49.5
Lwa 5 [dB(A)]
<36,3
38.5
40
45
42.5
49
49.5
Lwa 6 [dB(A)]
<38,5
43.5
47.5
53
53.5
58.6
59
FLAIR 600
Q [m³/h]
150
300
300
500
500
600
600
Ps [Pa]
25
50
100
100
150
100
150
Lwa 2 [dB(A)]
37.5
45.5
46
56
54.5
56.5
56.5
Lwa 5 [dB(A)]
35
45
42.5
51
52
53.5
56.5
Lwa 6 [dB(A)]
43.5
53
53.5
60.5
61.5
62
66.6
Lwa 2 = Sound power casing Lwa 5 = Sound power inlet Lwa 6 =Sound power outlet