PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

FLAIR • Heat recovery units system D ≤ 600 m³/h

High efficiency heat recovery units with low energy consumption.
The Flair units are available in different sizes and versions, applicable for air flow rates up to ≤ 600 m³/h. The units are supplied as standard with an integrated touch screen with a position switch, ball-siphon, ModBus communication and energetic modulating préheater. A large range of wireless or wired conrtrollers, sensors and other accessories is also available as an option.

Brand

  • Brink

Application

  • Ventilation with heat recovery for residential and non-residential applications where high efficiency is acquired
  • Applicable for air flows up to 600 m³/h
  • Available in different configurations
  • For inside installation

Specifications

  • Modulating electric preheater
  • ‘Bypass boost’ function
  • Tension: 230 Vac
  • ModBus communication
  • Filterwizard for end user
  • Possibilty to upgrade to Plus version by installing an additional pcb

Composition

  • Constant flow EC motors (EBM) with integrated anemometer
  • TFT touch screen with integrated 4 positions switch and wizard for servicing
  • Siphon with 32 mm connection
  • Automatic bypass (100%) with actuator
  • Casing of epoxy steel
  • Round connection with diameter 160/180/200 mm
  • 2 x ISO Coarse 60% filters

Certification

  • All Flair units are tested according NBN EN 308 and PassivHaus certified

Accessories

  • Wireless controllers and room sensors, type FLR-RF
  • Wired touch-controller with weekly program, type TC E-BUS
  • Digital controller with weekly program, type DCREN AC
  • Four position switch with filter indication, type CVREN 4
  • Wireles 4 position switch, type RFREN 4
  • Humidity sensor (in-duct), type HRT REN
  • CO2-sensors (max. 4 pieces) via eBus connection, type CO2 REN E-BUS
  • 2-Zone demand controlled ventilation based on time CO2, type DCV
  • Replacement filter, type FS FLR
    • Optional pcb for upgrade to Plus-version, type PCB PLUS FLAIR
    • Mounting chair, type MC FLAIR
    • Additional external pre- or post-heating battery, type CVR-VNF

    Order example

    FLAIR 325 R 4/0
    Explanation
    FLAIR = type of heat recovery unit
    325 = max. air volume in m³/h
    R = right version, L = left version
    4/0 = 4 connections on top

    Technical data

    FLAIR 225
    Q [m³/h]4050100150225
    Ps [Pa]3651020404489100200
    P [W]7,98,288,513,215,926,23461,582
    [A]0,10,110,10,10,130,150,220,290,480,63
    FLAIR 325
    [m³/h]50100150250325
    [Pa]25919214359118100200
    [W]6,16,48,29,715,419,446,961,487,2116,5
    [A]0,080,080,090,110,160,190,420,530,730,94
    FLAIR 400
    [m³/h]50100200300400
    [Pa]23613255056113100200
    [W]4,44,65,36,422,728,562,678,9126,6160,8
    [A]0,060,060,070,080,250,310,580,711,011,26
    FLAIR 450
    [m³/h]75100200300450
    [Pa]3651020404489100200
    [W]10,410,812,413,217,623,851,969,3149,5198,8
    [A]0,170,170,190,190,20,270,530,691,321,68
    FLAIR 600
    [m³/h]100150300500600
    [Pa]36613255069139100188
    [W]12,112,517,218,344,554,2166,6203,1250288
    [A]0,180,190,230,240,460,551,451,712,112,3

    Sound data

    FLAIR 225
    Q [m³/h]50100100150150225225 
    Ps [Pa]25255050100100150 
    Lwa 2 [dB(A)]283133,538,540,545,547 
    Lwa 5 [dB(A)]<30<34,5<36,5444347,548,5 
    Lwa 6 [dB(A)]43,548,550,55557,562,564,5 
    FLAIR 325
    Q [m³/h]100150150200200250250325
    Ps [Pa]25255050100100150150
    Lwa 2 [dB(A)]2734354041464651
    Lwa 5 [dB(A)]3240384644494955
    Lwa 6 [dB(A)]4449515557616269
    FLAIR 400
    Q [m³/h]150250350400    
    Ps [Pa]2550100100    
    Lwa 2 [dB(A)]3743,55255    
    Lwa 5 [dB(A)]43,546,55161    
    Lwa 6 [dB(A)]505869,571    
    FLAIR 450
    Q [m³/h]100200200300300450450 
    Ps [Pa]25255050100100150 
    Lwa 2 [dB(A)]<38,136.54245.542.54949.5 
    Lwa 5 [dB(A)]<36,338.5404542.54949.5 
    Lwa 6 [dB(A)]<38,543.547.55353.558.659 
    FLAIR 600
    Q [m³/h]150300300500500600600 
    Ps [Pa]2550100100150100150 
    Lwa 2 [dB(A)]37.545.5465654.556.556.5 
    Lwa 5 [dB(A)]354542.5515253.556.5 
    Lwa 6 [dB(A)]43.55353.560.561.56266.6 

    Lwa 2 = Sound power casing
    Lwa 5 = Sound power inlet
    Lwa 6 =Sound power outlet

    1 = To dwelling
    2 = To outside
    3 = From dwelling
    4 = From outside
    5 = Electrical connections
    6 = Siphon connection
    7 = Exhaust air filter
    8 = Supply air filter

    HELPCopyrightSales conditionsCookie policyfujitsu-airco.be

    Requesting information. Please wait a moment...