HRC70 080 ZéPAC HEAT COOL • Cascade high temperature air/water heat pumps 70°C HEATING/COOLING

The HRC70 80 ZéPAC are two air/water heat pumps in cascade that are suitable for heating and cooling. The water can be heated at high temperatures. The monoblock units are filled with the natural refrigerant propane (R290) and easily reach water temperatures up to 70°C. The devices guarentee proper operation at outside temperatures down to -20°C.
The HRC70 40 ZéPAC is a heating/cooling unit that uses 2 scroll compressors of the same capacity and with a soft starter as standard. This ensures 4 power stages and low power consumption for the whole cascade. Due to the specific construction, the device will switch to defrost mode less often and the defrost cycle will be completed as efficiently as possible.The unit maintains its high COP values even at negative outside temperatures.

Brand

  • Auer - Intuis

Application

  • Production of domestic hot water
  • Floor heating or cooling
  • Fan coils heating or cooling
  • Radiators only heating
  • Also available as a reversible HRC70 40 on 1 Pilote ZéPAC

Composition

Outdoor: Two monoblock reversible heat pumps HRC70 40 kW with :

  • Flexible pipes (Durite) of 5 m long and rigid insulated pipe to indoor module (diameter according to distance between the two, see table at the bottom of this page).
  • Filter 1"1/4 already installed in the return connection of this heatpump.
  • Primary pump already installed in this heatpump.
  • 2.5 bar pressure relief valve mounted in the HRC70.


Indoor module ZéPAC Uni-module 2x Pilote:
  • Two Buffertanks/hydraulic separators of each 63L with air vent and release valve
  • 50 m long bus cable for communication between the HRC70 and the ZéPAC (do not place in parallel with power cable).
  • Pressure sensor
  • 6 bar safety valve
  • Flow meter
  • Electronic CAREL regulation
  • USB stick (comes with manual)
  • 4 x Shut-off valve on the left-side
  • Sludge valve

Installation

  • The addition of an anti-corrosion agent or a glycol/anti-corrosion mixture is mandatory.

Accessories

  • Wireless Room Thermostat TH NCR/2 radio
  • Sensor DHW DHW S HRC70
  • Extra secondary pump HRC PK ZéPAC
  • Startup (MANDATORY), type XSTARTUPJ

Applicable boiler

  • Warm water tank 300 liters, type SANI+ 300 R-AQUA
  • Warm water tank 500 liters, type SANI+ 500 R-AQUA

Notes

1. Buffer tank 2 x 63L
2. Electronic regulation
3. Drain valve

Technical data

Technical specifications HRC70 80 ZéPAC HEAT COOL
Maximum water temperature°C70
Maximum heating capacitykW82
Heating capacity +7°C/+35°CkW66
COP +7°C/+35°C 4,20
Heating capacity +7°C/+45°CkW62
Heating capacity +7°C/+55°CkW61
Heating capacity -7°C/+35°CkW50
Heating capacity -7°C/+45°CkW48
Heating capacity -7°C/+65°CkW44
Cooling capacity 35°C Ext. 7/12°C WaterkW49,16
Energy class 35C°/55C° A+
Annual energy consumptionkWh/year32186
Operating range°C-20°C ~ +40°C
Outdoor unit dimensions HxWxD (2x)mm1545 x 1630 x 1200
Weight (2x)kg425
Air flow rate (2x)m³/h6000 to 12000
Rated water flow rate per HRC 40m³/h4,7
Condensate drain connection per HRC 40G F1"
Hydraulic connection diameter per HRC 40Victualic/Rainuré40/49 male
Sound level @ 1m 1 / 2 Compressors (per HRC 40)dB(A)52/61
Refrigerant (GWP) R290 (3)
Amount of refrigerant R290 (per HRC 40)kg3,6 (0,702)
Power supply 3 x 400V + N
Fuse 2xA32 (D)
Cable section 2xmm²5G6
Maximum absorbed power 2xA26,3
Maximum starting current 2xA54
Power position OFF (POFF) 2xkW0,0077
Power thermostat OFF (PTO) 2xkW0,0117
Power standby (PSB) 2xkW0,0077
Power carter heating (PCK) 2xkW0,0117

Technical data

Indoor module PILOTE ZéPAC Uni-module 2x Pilote
Power supply 230V/1 ph
Minimum power cable widthmm²3G 2,5
Circuit breakerA20
Multifunctional tankL2 x 63
Dimensions ZéPAC Uni-module (WxHxD)mm590 x 2491 x 542
Weight Pilote ZéPAC without waterkg2 x 52
Hydraulic connections 12 x

Dimensions

Minimum required piping diameter between HRC70 40 and ZéPACIn function of the used tube
2 Heatpumps on 1 pilote ZéPAC 2XSteelCopperPER-tube
If distance between heat pump and indoor module >10 m and <20 m44,2 mm33,9 mm33,9 mm
If distance between heat pump and indoor module >20 m and <35 m52,1 mm40,2 mm40,2 mm
If distance between heat pump and indoor module >35 m and <50 m59 mm45,9 mm45,9 mm
If distance between heat pump and indoor module >50 m and <75 m63,5 mm49,5 mm49,5 mm
If distance between heat pump and indoor module >75 m and <100 m67 mm52,5 mm52,5 mm
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be