Notes
1. Painted welded tank 200 L 2. Hydraulic pressure sensor 3. Automatic purge 4. 6 bar safety valve 5. 2"1/2 valve 6. Thermowell 7. Support foot 8. Drain valve 1"1/4 9. Upper flange 10. Lower flange 11. Insulated finishing cover
Technical data
|
Number of outdoor units | | 2 x HRC70 40 | 3 x HRC70 40 | 2 x HRC70 80 | Maximum water temperature | °C | 70 | 70 | 70 | Maximum heating capacity | kW | 82 | 123 | 166 | Rated heating capacity +7°C/+35°C | kW | 66 | 99.2 | 152 | COP +7°C/+35°C | | 4,2 | 4,2 | 4,2 | Rated heating capacity +7°C/+45°C | kW | 62 | 93 | 149 | Rated heating capacity +7°C/+55°C | kW | 61 | 91.5 | 146 | Rated heating capacity -7°C/+35°C | kW | 50 | 75 | 108 | Rated heating capacity -7°C/+45°C | kW | 48 | 72 | 106 | Rated heating capacity -7°C/+65°C | kW | 44 | 66 | 102 | Energy class 35C°/55C° | | A+ | A+ | A++ | Annual energy consumption | kWh/year | 32186 | 48279 | 56.178 | Operating range | °C | -20°C ~ +40°C | Outdoor unit dimensions HxLxW | mm | 1545 x 1630 x 1200 | 1545 x 1630 x 1200 | 1580 x 2700 x 1200 | Total weight outdoor units | kg | 2 x 425 | 3 x 425 | 2 x 645 | Air flow rate per outdoor unit | m³/h | 6000 to 12000 | 6000 to 12000 | 12000 to 24000 | Rated water flow rate per unit | m³/h | 4,7 | 4,7 | 11 | Condensate drain connection | G F | 1" | Hydraulic diameter connection | mm | 40/49 male | Sound level @ 1m 1 / 2 Compressors | dB(A) | 52/61 | 52/61 | 39,5 (5m) | Refrigerant (GWP) | | R290 (3) | Total amount of refrigerant R290 | kg | 3,6 (0,702) | 3,6 (0,702) | 4,5 (0,877) | Power supply per outdoor unit | | 3 x 400V + N | Fuse per outdoor unit | A | 32 (D) | 32 (D) | 63 (D) | Cable section outdoor per unit | mm² | 5G6 | 5G6 | 5G16 | Maximum absorbed power per unit | A | 26,3 | 26,3 | 62,2 | Maximum starting current per unit | A | 54 | 54 | 115 | Power position OFF (POFF) per unit | kW | 0,0077 | 0,0077 | 0,008 | Power thermostat OFF (PTO) per unit | kW | 0,0117 | 0,0117 | 0,008 | Power standby (PSB) per unit | kW | 0,0077 | 0,0077 | 0,008 | Power carter heating (PCK) per unit | kW | 0,0117 | 0,0117 | 0,013 |
Technical data
|
Minimum power cable width | mm² | 3G1,5 | Circuit breaker | A | 10 | Power supply Pilote Z2 | | 230V mono | Multifunctional tank | L | 200 | Dimensions (LxHxD) Pilote Z2 without the pumps | mm | 775 x 1422 x 610 | Dimensions (LxHxD) Regulation | mm | 455 x 629 x 171 | Weight Pilote Z2 without water | kg | 81 | Weight Pilote Z2 without water | kg | 9 | Hydraulic connections | inch | Flange 2"1/2 Sleeves 1"1/2 | Maximum pressure | bar | 6 |
Dimensions
|
2 Heatpumps HRC70 40 on 1 pilote Z2 | Steel | Copper | PER-tube | If distance between heat pump and indoor module >10 m and <20 m | 57,3 mm | 44,6 mm | 44,6 mm | If distance between heat pump and indoor module >20 m and <35 m | 65 mm | 50,9 mm | 50,9 mm | If distance between heat pump and indoor module >35 m and <50 m | 65 mm | 50,9 mm | 50,9 mm | If distance between heat pump and indoor module >50 m and <75 m | 70 mm | 55,1 mm | 55,1 mm | If distance between heat pump and indoor module >75 m and <100 m | 73,9 mm | 58,3 mm | 58,3 mm | 3 Heatpumps HRC70 40 on 1 pilote Z2 | Steel | Copper | PER-tube | If distance between heat pump and indoor module >10 m and <20 m | 67,2 mm | 52,6 mm | 52,6 mm | If distance between heat pump and indoor module >20 m and <35 m | 76,2 mm | 60 mm | 60 mm | If distance between heat pump and indoor module >35 m and <50 m | 76,2 mm | 60 mm | 60 mm | If distance between heat pump and indoor module >50 m and <75 m | 82,2 mm | 64,91 mm | 64,91 mm | If distance between heat pump and indoor module >75 m and <100 m | 86,7 mm | 68,7 mm | 68,7 mm | 2 Heatpumps HRC70 80 on 1 pilote Z2 | Steel | Copper | PER-tube | If distance between heat pump and indoor module >10 m and <20 m | 86,4 mm | 68 mm | 68 mm | If distance between heat pump and indoor module >20 m and <35 m | 98,4 mm | 77,8 mm | 77,8 mm | If distance between heat pump and indoor module >35 m and <50 m | 98,4 mm | 77,8 mm | 77,8 mm | If distance between heat pump and indoor module >50 m and <75 m | 106,3 mm | 84,5 mm | 84,5 mm | If distance between heat pump and indoor module >75 m and <100 m | 112,2 mm | 89,6 mm | 89,6 mm |
|