This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
HRC70 40 and HRC70 80 air/water heat pumps in cascade are suitable for high water temperatures. The monoblock unit is filled with the natural refrigerant propane (R290) and easily reaches water temperatures up to 70°C. The devices guarantee proper operation at outside tempartures down to -20°C.
The HRC70 40 and HRC70 80 are a heating only unit that use 2 scroll compressors of the same capacity and with a soft starter as standard. This ensures 2 power stages and low power consumption. Due to the specific construction, the device will switch to defrost mode less and the defrost cycle will be completed as efficiently as possible.
The unit maintains its high COP values even at negative outside temperatures. Possibility to cascade 3 HRC70 40units with a total power of 120kW or 2 HRC70 80 units with a total power of 160kW.
Brand
Auer - Intuis
Application
Production of domestic hot water
Floor heating
Fan coils
Radiators
Appropriate for:
Production of domestic hot water for showers in fitness centers, factories, sporting facilities,...
Heating of halls and large rooms
Retail, public buildings, offices,...
Composition
Outdoor: Two or three monoblock heat pumps HRC70 40 or HRC70 80 for cascade installation.
Included with each outdoor unit:
10 m long bus cable for communication between the HRC70 and the Pilote Z2 (3 core and already connected to each HRC70) (do not place in parallel with power
cable).
Flexible pipes (Durite) of 5 m long and rigid insulated pipe to
indoor module (diameter according to distance between the two, see table at the
bottom of this page).
Filter 1"1/4 for placement on the hydraulic return duct.
Primary pumps are installed in the heat pumps.
2,5 bar pressure relief valve mounted in the heat pumps.
Indoor module Pilote Z2:
Buffertank/hydraulic decoupling bottle 200L with air vent, release valve and safety valve
4 x 2"1/2 flanges and 4 x 1"1/2" sleeves
Flow and return collector to put the heat pumps in cascade
Pressure sensor
Flow meter
Separate box with electronic regulation
USB stick (comes with manual)
Shut-off valve 1 "1/4
Filter tap 1 "1/4
Outdoor sensor for weather dependent control
Installation
The addition of an anti-corrosion agent or a glycol/anti-corrosion mixture is mandatory.
Accessories
Room thermostat RAM 812
Room sensor with display TH HRC70
Domestic hot water sensor DHW S HRC70
HRC70 Communication 20
HRC70 Communication 50
Secondary pump HRC PK CASCADE 6P10
Startup is chargeable (MANDATORY), type XSTARTUPJ, quotation available on request
Applicable boiler
Domestic hot water
tank 300 liters, type SANI+ 300 R-AQUA
Domestic hot water
tank 500 liters, type SANI+ 500 R-AQUA
Artikelen
Article selection assistant
Dia [mm]
Color
Q Intake (2,5 m/s in the duct) [m³/h]
Q Outtake (3,5 m/s in the valve) [m³/h]
Article number
Type
Dia [mm]
Color
Q Intake (2,5 m/s in the duct) [m³/h]
Q Outtake (3,5 m/s in the valve) [m³/h]
E-shop
A090101125000
CT125R
125
Red
105
147
A090101150000
CT150R
150
Red
153
214
A090101160000
CT160R
160
Red
153
214
A090101200000
CT200R
200
Red
275
384
A090101250000
CT250R
250
Red
431
604
A090101315000
CT315R
315
Red
689
964
A090101355000
CT355R
355
Red
876
1226
A090101400000
CT400R
400
Red
1114
1560
A090101450000
CT450R
450
Red
1412
1977
A090101500000
CT500R
500
Red
1746
2444
A090101630000
CT630R
630
Red
2779
3891
A090102125000
CT125B
125
Gray
105
147
A090102150000
CT150B
150
Gray
153
214
A090102160000
CT160B
160
Gray
153
214
A090102200000
CT200B
200
Gray
275
384
A090102250000
CT250B
250
Gray
431
604
A090102315000
CT315B
315
Gray
689
964
A090102355000
CT355B
355
Gray
876
1226
A090102400000
CT400B
400
Gray
1114
1560
A090102450000
CT450B
450
Gray
1412
1977
A090102500000
CT500B
500
Gray
1746
2444
A090102630000
CT630B
630
Gray
2779
3891
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
=> Article with a volume discount
Notes
1. Painted welded tank 200 L
2. Hydraulic pressure sensor
3. Automatic purge
4. 6 bar safety valve
5. 2"1/2 valve
6. Thermowell
7. Support foot
8. Drain valve 1"1/4
9. Upper flange
10. Lower flange
11. Insulated finishing cover
Technical data
Technical specifications
HRC 080 Z2 cascade
HRC 120 Z2 cascade
HRC 160 Z2 cascade
Number of outdoor units
2 x HRC70 40
3 x HRC70 40
2 x HRC70 80
Maximum water temperature
°C
70
70
70
Maximum heating capacity
kW
82
123
166
Rated heating capacity +7°C/+35°C
kW
66
99.2
152
COP +7°C/+35°C
4,2
4,2
4,2
Rated heating capacity +7°C/+45°C
kW
62
93
149
Rated heating capacity +7°C/+55°C
kW
61
91.5
146
Rated heating capacity -7°C/+35°C
kW
50
75
108
Rated heating capacity -7°C/+45°C
kW
48
72
106
Rated heating capacity -7°C/+65°C
kW
44
66
102
Energy class 35C°/55C°
A+
A+
A++
Annual energy consumption
kWh/year
32186
48279
56.178
Operating range
°C
-20°C ~ +40°C
Outdoor unit dimensions HxLxW
mm
1545 x 1630 x 1200
1545 x 1630 x 1200
1580 x 2700 x 1200
Total weight outdoor units
kg
2 x 425
3 x 425
2 x 645
Air flow rate per outdoor unit
m³/h
6000 to 12000
6000 to 12000
12000 to 24000
Rated water flow rate per unit
m³/h
4,7
4,7
11
Condensate drain connection
G F
1"
Hydraulic diameter connection
mm
40/49 male
Sound level @ 1m 1 / 2 Compressors
dB(A)
52/61
52/61
39,5 (5m)
Refrigerant (GWP)
R290 (3)
Total amount of refrigerant R290
kg
3,6 (0,702)
3,6 (0,702)
4,5 (0,877)
Power supply per outdoor unit
3 x 400V + N
Fuse per outdoor unit
A
32 (D)
32 (D)
63 (D)
Cable section outdoor per unit
mm²
5G6
5G6
5G16
Maximum absorbed power per unit
A
26,3
26,3
62,2
Maximum starting current per unit
A
54
54
115
Power position OFF (POFF) per unit
kW
0,0077
0,0077
0,008
Power thermostat OFF (PTO) per unit
kW
0,0117
0,0117
0,008
Power standby (PSB) per unit
kW
0,0077
0,0077
0,008
Power carter heating (PCK) per unit
kW
0,0117
0,0117
0,013
Technical data
Indoor module PILOTE
Z2
Minimum power cable width
mm²
3G1,5
Circuit breaker
A
10
Power supply Pilote Z2
230V mono
Multifunctional tank
L
200
Dimensions (LxHxD) Pilote Z2 without the pumps
mm
775 x 1422 x 610
Dimensions (LxHxD) Regulation
mm
455 x 629 x 171
Weight Pilote Z2 without water
kg
81
Weight Pilote Z2 without water
kg
9
Hydraulic connections
inch
Flange 2"1/2 Sleeves 1"1/2
Maximum pressure
bar
6
Dimensions
Minimum required piping diameter between HRC70 40 or 80 and Z2
Depending on the tube used
2 Heatpumps HRC70 40 on 1 pilote Z2
Steel
Copper
PER-tube
If distance between heat pump and indoor module >10 m and <20 m
57,3 mm
44,6 mm
44,6 mm
If distance between heat pump and indoor module >20 m and <35 m
65 mm
50,9 mm
50,9 mm
If distance between heat pump and indoor module >35 m and <50 m
65 mm
50,9 mm
50,9 mm
If distance between heat pump and indoor module >50 m and <75 m
70 mm
55,1 mm
55,1 mm
If distance between heat pump and indoor module >75 m and <100 m
73,9 mm
58,3 mm
58,3 mm
3 Heatpumps HRC70 40 on 1 pilote Z2
Steel
Copper
PER-tube
If distance between heat pump and indoor module >10 m and <20 m
67,2 mm
52,6 mm
52,6 mm
If distance between heat pump and indoor module >20 m and <35 m
76,2 mm
60 mm
60 mm
If distance between heat pump and indoor module >35 m and <50 m
76,2 mm
60 mm
60 mm
If distance between heat pump and indoor module >50 m and <75 m
82,2 mm
64,91 mm
64,91 mm
If distance between heat pump and indoor module >75 m and <100 m
86,7 mm
68,7 mm
68,7 mm
2 Heatpumps HRC70 80 on 1 pilote Z2
Steel
Copper
PER-tube
If distance between heat pump and indoor module >10 m and <20 m
86,4 mm
68 mm
68 mm
If distance between heat pump and indoor module >20 m and <35 m
98,4 mm
77,8 mm
77,8 mm
If distance between heat pump and indoor module >35 m and <50 m
98,4 mm
77,8 mm
77,8 mm
If distance between heat pump and indoor module >50 m and <75 m
106,3 mm
84,5 mm
84,5 mm
If distance between heat pump and indoor module >75 m and <100 m