PRODUCTEN
EShop-nummer
Wachtwoord
Welcome to CAIROX BELGIUM

HRC70 080/120/160 Z2 CASCADE • Cascade high temperature air/water heat pumps 70°C

HRC70 40 and HRC70 80 air/water heat pumps in cascade are suitable for high water temperatures. The monoblock unit is filled with the natural refrigerant propane (R290) and easily reaches water temperatures up to 70°C. The devices guarantee proper operation at outside tempartures down to -20°C.
The HRC70 40 and HRC70 80 are a heating only unit that use 2 scroll compressors of the same capacity and with a soft starter as standard. This ensures 2 power stages and low power consumption. Due to the specific construction, the device will switch to defrost mode less and the defrost cycle will be completed as efficiently as possible.

The unit maintains its high COP values even at negative outside temperatures. Possibility to cascade 3 HRC70 40 units with a total power of 120kW or 2 HRC70 80 units with a total power of 160kW.

Brand

  • Auer - Intuis

Application

  • Production of domestic hot water
  • Floor heating
  • Fan coils
  • Radiators

Appropriate for:
  • Production of domestic hot water for showers in fitness centers, factories, sporting facilities,...
  • Heating of halls and large rooms
  • Retail, public buildings, offices,...

Composition

Outdoor: Two or three monoblock heat pumps HRC70 40 or HRC70 80 for cascade installation.
Included with each outdoor unit:

  • 10 m long bus cable for communication between the HRC70 and the Pilote Z2 (3 core and already connected to each HRC70) (do not place in parallel with power cable).
  • Flexible pipes (Durite) of 5 m long and rigid insulated pipe to indoor module (diameter according to distance between the two, see table at the bottom of this page).
  • Filter 1"1/4 for placement on the hydraulic return duct.
  • Primary pumps are installed in the heat pumps.
  • 2,5 bar pressure relief valve mounted in the heat pumps.


Indoor module Pilote Z2:
  • Buffertank/hydraulic decoupling bottle 200L with air vent, release valve and safety valve
  • 4 x 2"1/2 flanges and 4 x 1"1/2" sleeves
  • Flow and return collector to put the heat pumps in cascade
  • Pressure sensor
  • Flow meter
  • Separate box with electronic regulation
  • USB stick (comes with manual)
  • Shut-off valve 1 "1/4
  • Filter tap 1 "1/4
  • Outdoor sensor for weather dependent control

Installation

  • The addition of an anti-corrosion agent or a glycol/anti-corrosion mixture is mandatory.

Accessories

  • Room thermostat RAM 812
  • Room sensor with display TH HRC70
  • Domestic hot water sensor DHW S HRC70
  • HRC70 Communication 20
  • HRC70 Communication 50
  • Secondary pump HRC PK CASCADE 6P10
  • Startup is chargeable (MANDATORY), type XSTARTUPJ, quotation available on request

Applicable boiler

  • Domestic hot water tank 300 liters, type SANI+ 300 R-AQUA
  • Domestic hot water tank 500 liters, type SANI+ 500 R-AQUA

Notes

1. Painted welded tank 200 L
2. Hydraulic pressure sensor
3. Automatic purge
4. 6 bar safety valve
5. 2"1/2 valve
6. Thermowell
7. Support foot
8. Drain valve 1"1/4
9. Upper flange
10. Lower flange
11. Insulated finishing cover

Technical data

Technical specifications HRC 080 Z2 cascadeHRC 120 Z2 cascadeHRC 160 Z2 cascade
Number of outdoor units 2 x HRC70 403 x HRC70 402 x HRC70 80
Maximum water temperature°C707070
Maximum heating capacitykW82123166
Rated heating capacity +7°C/+35°CkW6699.2152
COP +7°C/+35°C 4,24,24,2
Rated heating capacity +7°C/+45°CkW6293149
Rated heating capacity +7°C/+55°CkW6191.5146
Rated heating capacity -7°C/+35°CkW5075108
Rated heating capacity -7°C/+45°CkW4872106
Rated heating capacity -7°C/+65°CkW4466102
Energy class 35C°/55C° A+A+A++
Annual energy consumptionkWh/year321864827956.178
Operating range°C-20°C ~ +40°C
Outdoor unit dimensions HxLxWmm1545 x 1630 x 12001545 x 1630 x 12001580 x 2700 x 1200
Total weight outdoor unitskg2 x 4253 x 4252 x 645
Air flow rate per outdoor unitm³/h6000 to 120006000 to 1200012000 to 24000
Rated water flow rate per unitm³/h4,74,711
Condensate drain connectionG F1"
Hydraulic diameter connectionmm40/49 male
Sound level @ 1m 1 / 2 CompressorsdB(A)52/6152/6139,5 (5m)
Refrigerant (GWP) R290 (3)
Total amount of refrigerant R290kg3,6 (0,702)3,6 (0,702)4,5 (0,877)
Power supply per outdoor unit 3 x 400V + N
Fuse per outdoor unitA32 (D)32 (D)63 (D)
Cable section outdoor per unitmm²5G65G65G16
Maximum absorbed power per unitA26,326,362,2
Maximum starting current per unitA5454115
Power position OFF (POFF) per unitkW0,00770,00770,008
Power thermostat OFF (PTO) per unitkW0,01170,01170,008
Power standby (PSB) per unitkW0,00770,00770,008
Power carter heating (PCK) per unitkW0,01170,01170,013

Technical data

Indoor module PILOTE Z2
Minimum power cable widthmm²3G1,5
Circuit breakerA10
Power supply Pilote Z2 230V mono
Multifunctional tankL200
Dimensions (LxHxD) Pilote Z2 without the pumpsmm775 x 1422 x 610
Dimensions (LxHxD) Regulationmm455 x 629 x 171
Weight Pilote Z2 without waterkg81
Weight Pilote Z2 without waterkg9
Hydraulic connectionsinchFlange 2"1/2 Sleeves 1"1/2
Maximum pressurebar6

Dimensions

Minimum required piping diameter between HRC70 40 or 80 and Z2Depending on the tube used
2 Heatpumps HRC70 40 on 1 pilote Z2SteelCopperPER-tube
If distance between heat pump and indoor module >10 m and <20 m57,3 mm44,6 mm44,6 mm
If distance between heat pump and indoor module >20 m and <35 m65 mm50,9 mm50,9 mm
If distance between heat pump and indoor module >35 m and <50 m65 mm50,9 mm50,9 mm
If distance between heat pump and indoor module >50 m and <75 m70 mm55,1 mm55,1 mm
If distance between heat pump and indoor module >75 m and <100 m73,9 mm58,3 mm58,3 mm
3 Heatpumps HRC70 40 on 1 pilote Z2SteelCopperPER-tube
If distance between heat pump and indoor module >10 m and <20 m67,2 mm52,6 mm52,6 mm
If distance between heat pump and indoor module >20 m and <35 m76,2 mm60 mm60 mm
If distance between heat pump and indoor module >35 m and <50 m76,2 mm60 mm60 mm
If distance between heat pump and indoor module >50 m and <75 m82,2 mm64,91 mm64,91 mm
If distance between heat pump and indoor module >75 m and <100 m86,7 mm68,7 mm68,7 mm
2 Heatpumps HRC70 80 on 1 pilote Z2SteelCopperPER-tube
If distance between heat pump and indoor module >10 m and <20 m86,4 mm68 mm68 mm
If distance between heat pump and indoor module >20 m and <35 m98,4 mm77,8 mm77,8 mm
If distance between heat pump and indoor module >35 m and <50 m98,4 mm77,8 mm77,8 mm
If distance between heat pump and indoor module >50 m and <75 m106,3 mm84,5 mm84,5 mm
If distance between heat pump and indoor module >75 m and <100 m112,2 mm89,6 mm89,6 mm
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be