CGW-M SG • Air/water heat pumps R32 Monobloc

Air/water DC inverter-controlled monoblock heat pump with R32 refrigerant.

All hydraulic components such as a water pump, expansion vessel, pressure relief valve, back-up heater, etc., as well as the heat pump are combined in this monoblock. Thanks to the advanced heat pump technology, the energy from the outside air is absorbed and transferred to the water for home heating and cooling and domestic hot water. The intelligent regulation of the compressor and the expansion valve ensures precise and fast water temperature control, thus reducing energy consumption.

Brand

  • R-AQUA

Application

  • Heating of new or existing houses
  • Heating by means of radiators, convectors or floor, wall or ceiling heating
  • Cooling by means of convectors, floor, wall or ceiling cooling
  • Production of domestic hot water, provided a hot water heater is installed

Composition

  • High efficiency plate heat exchanger
  • Energy-efficient circulation pump
  • Colour touch screen controller (wired)

  • Expansion vessel (2 or 3 liters)
  • Safety valve (3 bar)
  • Electrical backup heater
  • Water pressure sensor
  • Integrated outside temperature sensor

  • DC inverter-controlled two-stage compressor with gas injection
  • DC fan motor
  • Gold Fin condenser

Refrigerant

  • R32

Specifications

  • Monobloc system
  • 1 device for heating, cooling and domestic hot water
    • Heating assured at outside temperatures down to -25°C
    • Water temperature up to 55°C at outside temperatures down to -15°C
  • A+++ at 35°C water temperature
  • Bivalent setup
    • The heat pump will send a signal to an external heat source (eg gas boiler) depending on the outside temperature. This causes the heat pump stoped, and the second source present will provide the heating.

  • Smart Grid ready
  • Visual indication of energy consumption
  • Standard equipped with WiFi
  • Standard equipped with Modbus interface
  • Easy installation
  • EUROVENT EN 14511 and EN 14825 certification
  • Keymark certification

Accessories

  • Room Thermostat, type TS-CLOUD, TS-CLOUD RF (only suitable for heating)
  • Cascade module, type CASCADE
  • Buffer tank, type BTE 60, BTE 100
  • Anti-vibration mounting blocks, type MPRH
  • 3-way zone valve, type TWV
  • Antifreeze valve, type AFP
  • Deaerator, type AAS

  • Magnetic dirt separator, type ADS

  • Differential pressure regulator, type DPC

  • Filling set, type WFS

  • Expansion vessel for heating, type HEV

  • Expansion vessel console, type EVC

  • Protector, type PAB

  • Coding plug for permanently disabling the cooling function, type COD-M-H

  • Start-up is strongly recommended, type XSTARTUPJ

Water filter, safety group, anti-freeze protection and expansion vessel MUST be provided on site.

Applicable boiler

  • Domestic hot water heater 200 liters, type SANI-EM 200
  • Domestic hot water heater 300 liters, type SANI-EM 300, SANI+ 300
  • Domestic hot water heater 500 liters, type SANI-EM 500, SANI+ 500

Startup

  • Start-up by CAIROX BELGIUM is strongly recommended

Notes

The 3-way valve is not supplied with the CGW-M unit.

Technical data

Monobloc unitCGW-M SG 06 A1-1phCGW-M SG 08 A1-1phCGW-M SG 10 A1-1phCGW-M SG 12 A1-1phCGW-M SG 16 A1-1phCGW-M SG 16 M1-3ph
Heating capacity A7/W35kW6,008,2010,2012,0015,7015,70
COP A7/W35 5,405,325,054,944,554,40
Heating capacity A7/W45kW6,808,3010,2013,0016,2016,20
COP A7/W45 4,104,364,083,773,613,61
Heating capacity A2/W35kW4,808,168,8011,0412,6412,64
COP A2/W35 3,993,803,763,653,573,34
Heating capacity A2/W45kW4,808,168,8011,0412,6412,64
COP A2/W45 3,193,043,012,922,862,86
Heating capacity A-7/W35kW3,967,267,799,1110,4310,43
COP A-7/W35 3,152,972,942,882,822,64
Heating capacity A-7/W45kW3,967,267,799,1110,4310,43
COP A-7/W45 2,523,382,352,302,262,11
Heating capacity A-10/W35kW3,606,607,088,289,489,48
Heating capacity A-10/W45kW3,606,607,088,289,489,48
Cooling capacity A35/W7kW5,707,409,0011,1013,8013,80
EER A35/W7 3,253,703,403,102,712,71
Cooling capacity A35/W18kW6,508,3010,2012,0015,5015,40
EER A35/W18 5,105,325,104,904,313,80
SEER A35 4,965,025,064,934,814,68
SCOP W35/W55 5,04/3,504,51/3,704,48/3,884,78/3,804,69/3,764,56/3,83
Seasonal efficiency heat pump ηs W35/W55 199/137177/145176/152188/149184/147179/150
Annual energy consumption heat pump W35/W55kWh2386/28823827/52064163/54865194/63876072/76755927/7404
Energy class W35/W55 A+++/A++A+++/A++A+++/A+++A+++/A++A+++/A++A+++/A+++
Refrigerant (GWP) R32 (675)
Refrigerant chargegr (CO2eq-T)950 (0,64)1600 (1,08)1600 (1,08)2200 (1,49)2200 (1,49)2200 (1,49)
Power supplyV / Ph / Hz230/1/50400/3/50
Rated powerkW2.455,205.756.856,908.66
Air flow ratem³/h320058005800580050155015
Hydraulic connections (supply-return)inch1"
Outgoing water temperature (min.-max.)Heating°C20 ~ 60
Cooling°C7 ~ 25
DHW°C40 ~ 80
ComponentsCompressorType-DC Rotary
Absorbed powerW123023752375368036803680
PumpType-High-efficiency pump
Regulation-Electronic - continuous control
Capacity (min.-max.)W3 ~ 87
Flow rate (min.)l/h720
Expansion vesselVolume*l23
Pre-pressurebar1,50
Electrical heatingType-Wet
Material-Incoloy825
Regulation-Automatic
Number of steps-2
CapacitykW36
CombinationkW1,50 + 1,503 + 3
Heat exchangerType-Plate heat exchanger
Number-1
Sound power level**dB586868686868
Sound pressure level @ 1m**dB(A)535454565959
Sound pressure level @ 5m***dB(A)364646464646
Power cable section heat pumpmm²3G2,53G43G43G63G65G2,5
Automatic fuse (slow) heat pumpA163232404016
Power cable section electrical heatingmm²3G2,53G63G63G63G65G2,5
Automatic fuse (slow) electrical heatingA163232323216
DimensionsUnit (LxDxH)mm735x1150x365878x1206x445
Weightkg95127127142142148
Specifications and design can be modified for further improvement without prior notice
Capacities measured according to EN14511
* The size of the expansion vessel should be determined in accordance with the total water volume of the system
** Measured according to EN12102
*** Lp measured at 5m in free field (Q=2)
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be