UTP-LX • Accessories VRF - Separation tubes DX-kit

  • Fujitsu - Airstage
  • VRF Airstage
  • Accessories
  • Installation equipment VRF Airstage
  • Separation tubes

Brand

  • Fujitsu - Airstage

Product

  • Installation equipment, separation tubes

Application

  • Deviding the variable refrigerant flow to two expansion valve kits UTP-VX90A
  • UTP-LX = VRF DX-kit

Features

  • The separation tube obtain an liquid and gas separation tube.
  • Supplied with insulation and required to use the insulation after brazing the pipes.
  • Three different kinds of separation tubes are avaible for the development of the refrigerant circuit.
  • Vertikal mounting position of the separation kit is allowed.
  • Max.15° as installation angle in horizontal mounting position.
  • T-tubes are forbidden because it causes a uneven refrigerant flow
  • Minimum distance between two separation tubes or bend of 90° is 500mm in straight part. To prevent the outdoor unit mulfunction and generation of refrigerant noise.
  • Please consult installer for more information if required
  • Welding under dry nytrogen is required, if not used, it will be caused to damage for compressor and clog the strainer and electronic expansion valve.

Artikelen

Artikelselectie-assistent
Type
Lengte [mm]
Spleten
Aansluitmaat
Artikelnummer Type Lengte [mm] Spleten Aansluitmaat E-shop
A04641T118625 GYP-LINE 18 - 1 - L= 625 MM - A 625 1 A
A04641T118A00 GYP-LINE 18 - 1 - L=1000 MM - A 1000 1 A
A04641T118C50 GYP-LINE 18 - 1 - L=1250 MM - A 1250 1 A
A04641T218625 GYP-LINE 18 - 2 - L= 625 MM - A 625 2 A
A04641T218A00 GYP-LINE 18 - 2 - L=1000 MM - A 1000 2 A
A04641T218C50 GYP-LINE 18 - 2 - L=1250 MM - A 1250 2 A
A04641T318625 GYP-LINE 18 - 3 - L= 625 MM - B 625 3 B
A04641T318A00 GYP-LINE 18 - 3 - L=1000 MM - B 1000 3 B
A04641T318C50 GYP-LINE 18 - 3 - L=1250 MM - B 1250 3 B