UTP-CX/DX • Accessories VRF VII/VRII - Outdoor unit branche kit

  • Fujitsu
  • VRF Airstage
  • Accessories
  • Installation equipment VRF Airstage
  • Outdoor unit Branche Kit

Brand

  • Fujitsu

Product

  • Outdoor unit branche kit

Application

  • Connecting the Master outdoor with SLAVE outdoor unit from VRF VII/VRII serie to the same refrigerant circuit

Features

  • Maximum distance between outdoor unit and outdoor unit branche kit is 3m.
  • If the pipe length between outdoor unit branche kit and outdoor unit branche kit (or slave unit) is longer than 2m, or a lower pipe line exists between outdoor units, traps for gas pipe should be arranged to eliminate oil from entering into and remaining at pipes and the stopped outdoor unit.
  • Max.10° as installation angle in horizontal mounting position.
  • Vertikal mounting position of the branche kit is not allowed.
  • T-tubes are forbidden to use as outdoor unit branche kit.
  • The outdoor unit branche kit contains a liquid pipe & gas pipe separation tube and also a oil joint pipe.
  • Heat insulation is included for liquid - and gas pipe separation tube of the branche kit
  • No mistakes in developing and installation of the refrigerant flow circuit are possible because one type of branche kit is selectable for the VRF V-serie.
  • When using single outdoor unit, outdoor units branch kit is not necessary.
  • One outdoor unit branche kit connect two outdoor units and two outdoor unit branche kits can connect three outdoor units maximum.
  • Welding under dry nytrogen is required, if not used, it will be caused to damage for compressor and clog the strainer and electronic expansion valve.
  • Please consult installer for more information if required