This universal three-phase outdoor unit on R32 is inverter controlled and suitable for connecting different types of R32 indoor units such as cassettes. The DC rotary compressor guarantees an economical and quiet operation and a long service life.
Brand
R-4LIVING
Product
Outdoor unit 3x400V+N (cassette type)
Function
Air-air heat pump, inverter
Refrigerant
R32
Applicable indoor units
Type CGCI 45/60 A1
Features
Robust and compact
High-quality blue fin coating
Colour: Grey white (RAL 9002)
Valve protection
DC rotary compressors
Power supply: 400V/3/50Hz
Operating range in cooling at outdoor temperatures from -20°C to +48°C
Operating range in heating at outdoor temperatures from -20°C to +24°C
Accessories
Metal wall supports. Type WBA
Rubber mounting blocks (15 cm). Type MPRH 1200
Rubber mounting blocks. Type MPR 1000
Insulated copper tubes on rol. Type P-COIL
Articles
Artikelselectie-assistent
Type
Koelvermogen* [kW]
Verwarmingsvermogen* [kW]
# pijps
AC of EC motor
Artikelnummer
Type
Koelvermogen* [kW]
Verwarmingsvermogen* [kW]
# pijps
AC of EC motor
E-shop
J035509071001
LIGHT-71-NC
6.10
7.60
2
AC
J035509072002
LIGHT-72-NC
9.40
10.40
2
AC
J035509073003
LIGHT-73-NC
10.80
13.50
2
AC
J035509091001
LIGHT-91-NC
6.10
9
4
AC
J035509092002
LIGHT-92-NC
7.10
10.50
4
AC
J035509093003
LIGHT-93-NC
8.60
12.50
4
AC
J035509094003
LIGHT-94-NC
9.90
9.60
4
AC
J035509171001
LIGHT-71-RC
6.10
7.60
2
AC
J035509172002
LIGHT-72-RC
9.40
10.40
2
AC
J035509173003
LIGHT-73-RC
10.80
13.50
2
AC
J035509191001
LIGHT-91-RC
6.10
9
4
AC
J035509192002
LIGHT-92-RC
7.10
10.50
4
AC
J035509193003
LIGHT-93-RC
8.60
12.50
4
AC
J035509194003
LIGHT-94-RC
9.90
9.60
4
AC
Prijzen zijn exclusief decoratiepaneel
* Volgens EUROVENT bij hoogste snelheid
AC-ventilatoren zijn beschikbaar via de website en e-shop
Specifications
Technical specifications
CGOU 45 A3
CGOU 60 A3
Refrigerant (GWP)
R32 (675)
R32 (675)
Maximum air flow rate (C/H)
m³/h
5900/5900
6600/6600
Power supply
V
400/3
400/3
Compressor type
DC Rotary
DC Rotary
Sound pressure (C/H) @ 1m
dB(A)
56/55
57/56
Sound power (C/H) @ 1m
dB(A)
71/71
72/72
Dimensions (H x W x D)
mm
820x940x460
1345x900x340
Weight
kg
95
112
Cooling pipes
inch
3/8 - 5/8
3/8 - 5/8
Amount of prefilled refrigerant
g (CO2eq-T)
2650 (1,79)
3600 (2,43)
Extra amount of refrigerant per meter
g/m
40
40
Number of prefilled meters
m
5
5
Maximum length/height of cooling pipes
m/m
75/30
75/30
Minimum length of cooling pipes
m
5
5
Operating temperature in cooling
°C
-20~48
-20~48
Operating temperature in heating
°C
-20~24
-20~24
Power supply cable section
mm²
5G2,5
5G2,5
Automatic fuse (slow)
A
16
16