PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

DXI.A • EMIBYTE DX close control unit inverter

  • Close control unit
  • Direct expansion
  • EMICON
  • 7 - 110 kW

Close control unit with direct expansion for vertical installation. Optional heating element, humidifier and dehumidifier are available for a precise temperature and humidity control. Particularly suitable for precision air conditioning in server rooms/ IT rooms and all technological applications. The inverter compressor allows modulation of the cooling capacity. This makes the unit particularly efficient at part loads, optimizing the power consumption and lowering the starting current. Electronic expansion valve and EC inverter fans are fitted as standard in this model. To be used with an RCE external air condenser.

Brand

  • EMICON

Application

  • Server rooms
  • Archives
  • Telecom

Composition

  • Galvanized steel frame
  • Touch screen display 4.3"
  • EC Centrifugal fan with backward curved blades
  • Inverter compressor
  • LAN connection
  • DX coil with bluefin coating
  • 3-way valve
  • Condensate tray
  • Long-life G4 filter
  • Microprocessor

Refrigerant

R410A

Models

  • D - Down flow air supply
  • U - Up flow air supply
  • F - Front flow air supply
  • B - Up flow air supply, rear flow air return

Accessories

  • Adjustable frame B
  • Dehumidification control DH
  • Humidifier H
  • Hot water coil BC
  • Three-phase network without neutral MN
  • Condensate pump PB
  • Condensate pump for humidifier PBH
  • Wired controller with touch screen
  • Electrical resistance RE or REM

Applicable outdoor units

  • Remote condensor RCE

Technical data

DXI.A 61111121151181201
Cooling capacity (24°C - 50% RH)kW7.210.111.216.118.220.5
Sensible cooling capacity (24°C - 50% RH)kW7.29.311.214.517.620.5
Absorbed nominal power (24°C - 50% RH)kW46691111
Absorbed nominal current (24°C - 50% RH)A141818162121
Electric power 400/3/50+N+PE
Dimensions L x W x Hmm550x750x1980550x750x1980550x750x1980550x750x1980750x980x1980750x980x1980
Air flow ratem³/h390039003900390057005700
Static pressurePa559560479412568539
Nominal steam capacity of humidifier (optional)kg/h333355
Electric resistance RE (optional)kW3334.54.56
Electric resistance REM (optional)kW666699
Water heating coil (optional)kW7.37.37.37.310.610.6
        
DXI.A 251321381392472491
Cooling capacity (24°C - 50% RH)kW25.633737.23947.450.7
Sensible cooling capacity (24°C - 50% RH)kW25.530.737.138.944.345.1
Absorbed nominal power (24°C - 50% RH)kW121516192123
Absorbed nominal current (24°C - 50% RH)A212426384034
Electric power 400/3/50+N+PE
Dimensions L x W x Hmm850x1160x1980850x1160x1980850x1505x1980850x1505x1980850x1505x1980850x1505x1980
Air flow ratem³/h8150815011500115001150011500
Static pressurePa451362428427402388
Nominal steam capacity of humidifier (optional)kg/h888888
Electric resistance RE (optional)kW666999
Electric resistance REM (optional)kW121212121212
Water heating coil (optional)kW16.716.724.524.524.524.5
        
DXI.A 531532631652691742
Cooling capacity (24°C - 50% RH)kW5452.864.868.470.174.9
Sensible cooling capacity (24°C - 50% RH)kW52.752.763.464.666.374.7
Absorbed nominal power (24°C - 50% RH)kW242328313033
Absorbed nominal current (24°C - 50% RH)A374247485051
Electric power 400/3/50+N+PE
Dimensions L x W x Hmm850x1860x1980850x1860x1980850x2210x1980850x2210x1980850x2210x1980580x2565x1980
Air flow ratem³/h145001450017600176001760020900
Static pressurePa417432417392432437
Nominal steam capacity of humidifier (optional)kg/h888888
Electric resistance RE (optional)kW151518181824
Electric resistance REM (optional)kW181824242427
Water heating coil (optional)kW31.131.137.437.437.448.9
        
DXI.A 76186193195210211142
Cooling capacity (24°C - 50% RH)kW78.285.894.796.5100.7109.8
Sensible cooling capacity (24°C - 50% RH)kW75.280.291.693.996.198.8
Absorbed nominal power (24°C - 50% RH)kW363845494756
Absorbed nominal current (24°C - 50% RH)A586176747993
Electric power 400/3/50+N+PE
Dimensions L x W x Hmm580x2565x1980580x2565x1980850x3100x1980850x3100x1980850x3100x1980850x3100x1980
Air flow ratem³/h209002090025700257002570025700
Static pressurePa436429446449442431
Nominal steam capacity of humidifier (optional)kg/h888888
Electric resistance RE (optional)kW242427272727
Electric resistance REM (optional)kW272736363636
Water heating coil (optional)kW48.948.960.86.860.86.8

Configuration

HELPCopyrightSales conditionsCookie policyfujitsu-airco.be