EUROVENT certified fan coil; cassette unit for ceiling mounting 600 x 600 mm, for cooling and/or heating of water
LIGHT-ECM-63-RC-E
Explication
LIGHT-ECM = Cassette with EC motor
63 = Size
RC = With infrared controller
NC = Wall thermostat
E = Electric resistance
(
83C and
84C have more cooling capacity than
83 and
84 due to more efficient battery)
Specifications
|
|
Cooling capacity 7/12°C * | [W] | max | 2223 | 2667 | 4247 | 4975 | 5381 | [W] | med | 1835 | 2433 | 3047 | 3648 | 4655 | [W] | min | 1556 | 1944 | 2144 | 2697 | 3967 | Water flow | [l/h] | max | 390 | 465 | 739 | 867 | 939 | [l/h] | med | 321 | 424 | 530 | 635 | 812 | [l/h] | min | 271 | 338 | 372 | 468 | 691 | Water pressure drop | [kPa] | max | 20 | 16 | 24 | 24 | 30 | [kPa] | med | 14 | 14 | 18 | 18 | 24 | [kPa] | min | 11 | 10 | 11 | 16 | 18 | Heating capacity 45/40°C * | [W] | max | 2340 | 2620 | 4080 | 4910 | 5420 | [W] | med | 1920 | 2370 | 2930 | 3440 | 4930 | [W] | min | 1590 | 1910 | 2090 | 2580 | 4090 | Water pressure drop | [kPa] | max | 20.9 | 15.5 | 18.5 | 22.8 | 29.6 | [kPa] | med | 14.2 | 12.5 | 16.2 | 18 | 25.7 | [kPa] | min | 10.5 | 8.9 | 9.7 | 15.3 | 19.2 | Heating capacity 50°C * | [W] | max | 2800 | 3150 | 4910 | 5900 | 6500 | [W] | med | 2300 | 2850 | 3522 | 4150 | 5900 | [W] | min | 1900 | 2300 | 2510 | 3100 | 4900 | Water pressure drop | [kPa] | max | 19 | 16 | 19 | 23,1 | 29 | [kPa] | med | 13 | 13 | 17 | 19,8 | 23 | [kPa] | min | 10 | 9 | 10 | 16,5 | 18 | Sound power level | [dB(A)] | max | 46 | 44 | 52 | 60 | 62 | [dB(A)] | med | 39 | 41 | 44 | 49 | 59 | [dB(A)] | min | 33 | 34 | 34 | 39 | 56 | Sound pressure level | [dB(A)] | max | 37 | 35 | 43 | 51 | 53 | [dB(A)] | med | 30 | 32 | 35 | 40 | 50 | [dB(A)] | min | 24 | 25 | 25 | 30 | 47 | Air flow | [m³/h] | max | 367 | 398 | 550 | 660 | 760 | [m³/h] | med | 295 | 355 | 398 | 468 | 660 | [m³/h] | min | 225 | 269 | 269 | 328 | 550 | Net weight | [kg] | net | 20 | 21 | 23 | 23 | 24 | |
Motor fan absorbed power | [W] | max | 48 | 43 | 63 | 75 | 89 | Motor fan absorbed current | [A] | max | 0,22 | 0,19 | 0,28 | 0,33 | 0,39 | |
Motor fan absorbed power | [W] | max | 12 | 11,2 | 25,5 | 40 | 58 | Motor fan absorbed current | [A] | max | 0,11 | 0,11 | 0,22 | 0,33 | 0,47 | |
Heating power output | [W] | | 1500 | 1500 | 2500 | 2500 | 2500 | Heating power input | [V] | | 230 | 230 | 230 | 230 | 230 | * The cooling capacity/ heating capaity are realised under the following EUROVENT conditions | (Cooling) Temp. Int.: 27°C D.B./19°C W.B. – Water: 7°Cin /12°C out | (Heating) Temp. Int: 20°C D.B. – Water : 45°C in /40°C out | (Heating) Temp. Int: 20°C D.B. – Water : 50°C in | The sound power level test has been performed according to EN 16583:2015 standard (n.a. = Non available) |
Specifications
|
|
Cooling capacity* | [W] | max | 2303 | 2707 | 3337 | 3827 | 3825 | 4395 | [W] | med | 1905 | 2373 | 2507 | 2957 | 3048 | 3408 | [W] | min | 1606 | 1864 | 1884 | 1974 | 2367 | 2627 | Water flow | [l/h] | max | 403 | 472 | 584 | 668 | 669 | 767 | [l/h] | med | 333 | 414 | 438 | 515 | 532 | 594 | [l/h] | min | 280 | 324 | 328 | 343 | 412 | 456 | Water pressure drop | [kPa] | max | 18 | 14 | 17 | 32.3 | 21 | 28 | [kPa] | med | 15 | 12 | 14 | 28 | 17 | 22 | [kPa] | min | 10 | 10 | 10 | 22 | 12 | 17 | Heating capacity* | [W] | max | 2690 | 3070 | 3900 | 2890 | 4380 | 3250 | [W] | med | 2300 | 2680 | 3070 | 2340 | 3510 | 2610 | [W] | min | 1780 | 2150 | 2150 | 1680 | 2760 | 2100 | Water pressure drop | [kPa] | max | 12 | 20 | 43 | 18 | 41 | 21 | [kPa] | med | 11 | 16 | 35 | 15 | 35 | 19 | [kPa] | min | 9 | 12 | 21 | 11 | 22 | 13 | Sound power level | [dB(A)] | max | 46 | 47 | 52 | 52 | 58 | 58 | [dB(A)] | med | 39 | 41 | 44 | 44 | 49 | 51 | [dB(A)] | min | 33 | 37 | 34 | 37 | 39 | 44 | Sound pressure level | [dB(A)] | max | 37 | 38 | 43 | 43 | 49 | 49 | [dB(A)] | med | 30 | 32 | 35 | 35 | 40 | 42 | [dB(A)] | min | 24 | 28 | 25 | 28 | 30 | 35 | Air flow | [m³/h] | max | 367 | 398 | 550 | 550 | 660 | 660 | [m³/h] | med | 295 | 355 | 398 | 398 | 468 | 468 | [m³/h] | min | 224 | 269 | 269 | 269 | 328 | 328 | Net weight | [kg] | net | 23 | 24 | 24 | 24 | 24 | 24 | |
Motor fan absorbed power | [W] | max | 47 | 43 | 63 | 63 | 75 | 75 | Motor fan absorbed current | [A] | max | 0,22 | 0,19 | 0.28 | 0.28 | 0.33 | 0.33 | |
Motor fan absorbed power | [W] | max | 12 | 12 | 25 | 29 | 38 | 44 | Motor fan absorbed current | [A] | max | 0.16 | 0.16 | 0.28 | 0.31 | 0.36 | 0.42 | |
Heating power output | [W] | | n.a. | n.a. | n.a. | n.a. | n.a. | n.a. | Heating power input | [V] | | n.a. | n.a. | n.a. | n.a. | n.a. | n.a. | * The cooling capacity/ heating capaity are realised under the following EUROVENT conditions | | (Cooling) Temp. Int.: 27°C D.B./19°C W.B. – Water: 7°Cin /12°C out | | (Heating) Temp. Int: 20°C D.B. – Water : 65°C in /55°C out | | The sound power level test has been performed according to EN 16583:2015 standard (n.a. = Non available) | |
|