PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

LIGHT-600x600 • Cassette units 600 x 600 mm AC motors

EUROVENT certified fan coil; cassette unit for ceiling mounting 600 x 600 mm, for cooling and/or heating of water

Brand

  • Ventilclima

Application

  • For cooling and/or heating by water of hotels, hospitals, shops, offices,...

Composition

  • Galvanised steel, with thermo-acoustic isolation
  • Hooks in corners for easy mounting in ceiling
  • Condensate pump (Prevalence is 650 mm)
  • One phase electrical motor with overload cutout, 3 speeds
  • Air filter is attached on the inside of the louvre
  • The exchagers are made of copper tubes with female fittings
  • Also available ECM model with EC motor

Options

Louvre/valves/controller have to be ordered seperately
  • 2-pipe (LIGHT 6x) or 4-pipe (LIGHT 8x)
  • With infrared controller or wall mounted controller
  • Premounted internal valves
  • Electrical resistance (E)
  • Input of fresh air
  • ON/OFF or modulating motor 230 or 24V on the valves
  • Eurovent certificated hygiene units available on demand
  • Also available ECM model with EC motor

Accessories

  • Decoration panel, type LIGHT-PANEL-600x600: to be ordered separately!
    • In metal (MET) or plastic (ABS)
    • Manual (M), motorized (A) or fixed (F) louvers
    • Thermostat (NC) or infrared controller (RC)
    • Thermostat, type I-10 / I-20/ I-50 / I-60 / I-70 (to be ordered separately)
  • Infrared controller, type LIGHT-IR
  • Auxiliary drain pan always supplied included (not installed)

  • The decorative panel must be ordered separately

Order example

LIGHT-ECM-63-RC-E

Explication

LIGHT-ECM = Cassette with EC motor

63 = Size

RC = With infrared controller

NC = Wall thermostat

E = Electric resistance

(83C and 84C have more cooling capacity than 83 and 84 due to more efficient battery)

Articles

Article selection assistant
Type
Integrated auxiliary switch
Article number Type Integrated auxiliary switch E-shop
J120514001000 SFA No
J120514001020 SFA-S2 Yes
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales

Specifications

LIGHT-600 x 600 - 2 pipes (LIGHT 6x)
   6162636465
Cooling capacity 7/12°C *[W]max22232667424749755381
[W]med18352433304736484655
[W]min15561944214426973967
Water flow[l/h]max390465739867939
[l/h]med321424530635812
[l/h]min271338372468691
Water pressure drop[kPa]max2016242430
[kPa]med1414181824
[kPa]min1110111618
Heating capacity 45/40°C *[W]max23402620408049105420
[W]med19202370293034404930
[W]min15901910209025804090
Water pressure drop[kPa]max20.915.518.522.829.6
[kPa]med14.212.516.21825.7
[kPa]min10.58.99.715.319.2
Heating capacity 50°C *[W]max28003150491059006500
[W]med23002850352241505900
[W]min19002300251031004900
Water pressure drop[kPa]max19161923,129
[kPa]med13131719,823
[kPa]min1091016,518
Sound power level[dB(A)]max4644526062
[dB(A)]med3941444959
[dB(A)]min3334343956
Sound pressure level[dB(A)]max3735435153
[dB(A)]med3032354050
[dB(A)]min2425253047
Air flow[m³/h]max367398550660760
[m³/h]med295355398468660
[m³/h]min225269269328550
Net weight[kg]net2021232324
Asynchronous motor
Motor fan absorbed power[W]max4843637589
Motor fan absorbed current[A]max0,220,190,280,330,39
EC-motor (LIGHT-ECM)
Motor fan absorbed power[W]max1211,225,54058
Motor fan absorbed current[A]max0,110,110,220,330,47
Electrical heating (LIGHT-E)
Heating power output[W] 15001500250025002500
Heating power input[V] 230230230230230
* The cooling capacity/ heating capaity are realised under the following EUROVENT conditions
(Cooling) Temp. Int.: 27°C D.B./19°C W.B. – Water: 7°Cin /12°C out
(Heating) Temp. Int: 20°C D.B. – Water : 45°C in /40°C out
(Heating) Temp. Int: 20°C D.B. – Water : 50°C in
The sound power level test has been performed according to EN 16583:2015 standard (n.a. = Non available)

Specifications

LIGHT-600 x 600 - 4 pipes (LIGHT 8x)
   81828383C8484C
Cooling capacity*[W]max230327073337382738254395
[W]med190523732507295730483408
[W]min160618641884197423672627
Water flow[l/h]max403472584668669767
[l/h]med333414438515532594
[l/h]min280324328343412456
Water pressure drop[kPa]max18141732.32128
[kPa]med151214281722
[kPa]min101010221217
Heating capacity*[W]max269030703900289043803250
[W]med230026803070234035102610
[W]min178021502150168027602100
Water pressure drop[kPa]max122043184121
[kPa]med111635153519
[kPa]min91221112213
Sound power level[dB(A)]max464752525858
[dB(A)]med394144444951
[dB(A)]min333734373944
Sound pressure level[dB(A)]max373843434949
[dB(A)]med303235354042
[dB(A)]min242825283035
Air flow[m³/h]max367398550550660660
[m³/h]med295355398398468468
[m³/h]min224269269269328328
Net weight[kg]net232424242424
Asynchronous motor
Motor fan absorbed power[W]max474363637575
Motor fan absorbed current[A]max0,220,190.280.280.330.33
EC-motor (LIGHT-ECM)
Motor fan absorbed power[W]max121225293844
Motor fan absorbed current[A]max0.160.160.280.310.360.42
Moteur EC (LIGHT-ECM)
Heating power output[W] n.a.n.a.n.a.n.a.n.a.n.a.
Heating power input[V] n.a.n.a.n.a.n.a.n.a.n.a.
* The cooling capacity/ heating capaity are realised under the following EUROVENT conditions 
(Cooling) Temp. Int.: 27°C D.B./19°C W.B. – Water: 7°Cin /12°C out 
(Heating) Temp. Int: 20°C D.B. – Water : 65°C in /55°C out 
The sound power level test has been performed according to EN 16583:2015 standard (n.a. = Non available) 