MICROBLUE RESERVOIR FSA NEW • Compact condensate pumps up to 3,5 kW (with reservoir)

Silent condensate pump with reservoir and elongated design that can be mounted in any direction up to 2m from the indoor unit.

Equipped with a fail safe alarm: a voltage free relay designed to switch off the air conditioning while keeping the pump running continuously when the condensation water reaches a certain level in the reservoir.

Thanks to the intelligent sensor technology, the pump automatically adjusts to the water level in the reservoir to operate as quietly and as efficiently as possible.

Built-in intelligence provides installers with rapid system analysis by means of a display on the pump.

Brand

  • BlueDiamond

Application

  • Heat pumps with a capacity up to 3,5 kW

Specifications

  • Max. flow rate: 5 l/h
  • Max. delivery height: 5 m
  • Max. suction height: 2 m
  • Sound pressure at 1 m= 17 dB(A)
  • Fail safe alarm: volt free relay
  • Patented rotary diaphragm pump principle
  • No maintenance

Mounting

  • To be mounted in any orientation up to 2 m away from the indoor unit
  • To be mounted in a mounting duct or in a false wall
  • To be mounted under the indoor unit (Fascia kit)
  • Connection diameter: 6 mm

Articles

Article selection assistant
Type
# pipes
AC or EC engine
Horizontal or vertical
Hydraulic connection
Article number Type # pipes AC or EC engine Horizontal or vertical Hydraulic connection E-shop
J035520030010 FRESH-H-1/L/2P 2 AC Horizontal Left
J035520030012 FRESH-V-1/L/2P 2 AC Vertical Left
J035520030020 FRESH-H-2/L/2P 2 AC Horizontal Left
J035520030022 FRESH-V-2/L/2P 2 AC Vertical Left
J035520030030 FRESH-H-3/L/2P 2 AC Horizontal Left
J035520030032 FRESH-V-3/L/2P 2 AC Vertical Left
J035520030040 FRESH-H-4/L/2P 2 AC Horizontal Left
J035520030042 FRESH-V-4/L/2P 2 AC Vertical Left
J035520030050 FRESH-H-5/L/2P 2 AC Horizontal Left
J035520030052 FRESH-V-5/L/2P 2 AC Vertical Left
J035520030060 FRESH-H-6/L/2P 2 AC Horizontal Left
J035520030062 FRESH-V-6/L/2P 2 AC Vertical Left
J035520030070 FRESH-H-7/L/2P 2 AC Horizontal Left
J035520030072 FRESH-V-7/L/2P 2 AC Vertical Left
J035520031010 FRESH-H-1/R/2P 2 AC Horizontal Right
J035520031012 FRESH-V-1/R/2P 2 AC Vertical Right
J035520031020 FRESH-H-2/R/2P 2 AC Horizontal Right
J035520031022 FRESH-V-2/R/2P 2 AC Vertical Right
J035520031030 FRESH-H-3/R/2P 2 AC Horizontal Right
J035520031032 FRESH-V-3/R/2P 2 AC Vertical Right
J035520031040 FRESH-H-4/R/2P 2 AC Horizontal Right
J035520031042 FRESH-V-4/R/2P 2 AC Vertical Right
J035520031050 FRESH-H-5/R/2P 2 AC Horizontal Right
J035520031052 FRESH-V-5/R/2P 2 AC Vertical Right
J035520031060 FRESH-H-6/R/2P 2 AC Horizontal Right
J035520031062 FRESH-V-6/R/2P 2 AC Vertical Right
J035520031070 FRESH-H-7/R/2P 2 AC Horizontal Right
J035520031072 FRESH-V-7/R/2P 2 AC Vertical Right
J035520032010 FRESH-H-1/L/4P 4 AC Horizontal Left
J035520032012 FRESH-V-1/L/4P 4 AC Vertical Left
J035520032020 FRESH-H-2/L/4P 4 AC Horizontal Left
J035520032022 FRESH-V-2/L/4P 4 AC Vertical Left
J035520032030 FRESH-H-3/L/4P 4 AC Horizontal Left
J035520032032 FRESH-V-3/L/4P 4 AC Vertical Left
J035520032040 FRESH-H-4/L/4P 4 AC Horizontal Left
J035520032042 FRESH-V-4/L/4P 4 AC Vertical Left
J035520032050 FRESH-H-5/L/4P 4 AC Horizontal Left
J035520032052 FRESH-V-5/L/4P 4 AC Vertical Left
J035520032060 FRESH-H-6/L/4P 4 AC Horizontal Left
J035520032062 FRESH-V-6/L/4P 4 AC Vertical Left
J035520032070 FRESH-H-7/L/4P 4 AC Horizontal Left
J035520032072 FRESH-V-7/L/4P 4 AC Vertical Left
J035520033010 FRESH-H-1/R/4P 4 AC Horizontal Right
J035520033012 FRESH-V-1/R/4P 4 AC Vertical Right
J035520033020 FRESH-H-2/R/4P 4 AC Horizontal Right
J035520033022 FRESH-V-2/R/4P 4 AC Vertical Right
J035520033030 FRESH-H-3/R/4P 4 AC Horizontal Right
J035520033032 FRESH-V-3/R/4P 4 AC Vertical Right
J035520033040 FRESH-H-4/R/4P 4 AC Horizontal Right
J035520033042 FRESH-V-4/R/4P 4 AC Vertical Right
J035520033050 FRESH-H-5/R/4P 4 AC Horizontal Right
J035520033052 FRESH-V-5/R/4P 4 AC Vertical Right
J035520033060 FRESH-H-6/R/4P 4 AC Horizontal Right
J035520033062 FRESH-V-6/R/4P 4 AC Vertical Right
J035520033070 FRESH-H-7/R/4P 4 AC Horizontal Right
J035520033072 FRESH-V-7/R/4P 4 AC Vertical Right

Dimensions

  • Pump (L x W x D): 147 x 37 x 40 mm

Discharge pipe run

V (Vertical)H (Horizontal)
5 m0 m
4 m3 m
3 m6 m
2 m9 m
1 m12 m
The MICROBLUE® can be mounted in any orientation up to 2m away from the airco unit.

Accessoires

  • Cover under AC unit to hide Microblue and reservoir, type MIB fascia kit
  • Adapting piece for condensate drain, type MIB stepped adaptor (Blue)

Technical data

  • Voltage: 240 V AC
  • Current draw: 0,04 A
  • Electric power: 2,6 W

Technical drawing