PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

ISW-4P • 4-pole Isolator Switches

  • Outdoor units
  • 4-pole Isolator switches

Isolator switch.
Insulated 4-pole CE marked isolator switch. Suitable for disconnecting the power supply to outdoor heat pump units and air handling units. Available in small (ISW-4P-20A and ISW-4P-32A) and standard (ISW-4P-40A and ISW-4P-63A) sizes with cable gland.

Composition

  • Protection class: IP65
  • M20/25 inputs up to 63A
  • Handle lockable in off position
  • Interlocked cover - removable in off position only
  • Earth and neutral terminals included
  • Standard: IEC 60947-3

Articles

Article selection assistant
Type
# pipes
Mounted
Article number Type # pipes Mounted E-shop
J035509007113 LIGHT-71-M-1x3WVOO230V 2 Yes
J035509009423 LIGHT-94-M-2x3WVOO230V 4 Yes
J035509616213 LIGHT-61-M-1x3WVOO230V 2 Yes
J035509616215 LIGHT-62-M-1x3WVOO230V 2 Yes
J035509636513 LIGHT-63-64-M-1x3WVOO230V 2 Yes
j035509636515 LIGHT-65-M-1x3WVOO230V 2 Yes
J035509727313 LIGHT-72-73-M-1x3WVOO230V 2 Yes
J035509818423 LIGHT-81-M-2x3WVOO230V 4 Yes
j035509818425 LIGHT-82-83-84-M-2x3WVOO230V 4 Yes
j035509818427 LIGHT-83C-84C-M-2x3WVOO230V 4 Yes
J035509919323 LIGHT-91-93-M-2x3WVOO230V 4 Yes
j035509919325 LIGHT-92-93-M-2x3WVOO230V 4 Yes
J03550A007113 LIGHT-71-NM-1x3WVOO230V 2 No
J03550A009423 LIGHT-94-NM-2x3WVOO230V 4 No
J03550A616213 LIGHT-61-62-NM-1x3WVOO230V 2 No
J03550A636513 LIGHT-63-64-65-NM-1x3WVOO230V 2 No
J03550A727313 LIGHT-72-73-NM-1x3WVOO230V 2 No
J03550A818423 LIGHT-81-84-NM-2x3WVOO230V 4 No
J03550A919323 LIGHT-91-93-NM-2x3WVOO230V 4 No
M = mounted; NM = not mounted

Technical data

TYPEAmpère (A) - AC21Capacity (kW) - AC23 A
240VA
Capacity (kW) - AC23 A
400VA
Cable capacity
Solid (mm²)Stranded (mm²)
ISW-4P-20A205.53.71-160,75-10
ISW-4P-32A32117.51-160,75-10
ISW-4P-40A4015111-160,75-10
ISW-4P-63A632218.51-160,75-10
Utilization category according to IEC 60947-3-1:
- AC-21: Switching of resistive loads, including moderate overloads
- AC-23: Switching of motor loads or other highly inductive loads

Dimensions

TYPEWidth (mm)Depth (mm)Height (mm)
ISW-4P-20A100120125
ISW-4P-32A100120125
ISW-4P-40A114135175
ISW-4P-63A114135175
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be

Requesting information. Please wait a moment...