CAB • Cleaners

  • Cleaning products
  • Hydraulic systems
  • Cleaning products

The cleaner (C3 Cleaner 570911) dislodges sludge, scale deposits and dirt particles from hydraulic installations, after which the filter or dirt separator collects the dirt so that it can be eliminated. The cleaner can be applied to new and existing heating and cooling systems at high or low temperature. The cleaner is non-aggressive and therefore suitable for all materials used in hydraulic systems. In addition, the cleaner can be used with all types of propylene glycol.

Brand

Caleffi

Application

To remove sludge, scale, dirt particles and deposits from existing installations. For new installations, the cleaner enables commissioning to the required standards.

Specifications

  • Bottle content: 500 ml liquid
  • Colour: light brown
  • Odour: light
  • pH: 7-8
  • Relative density: 1,15
  • Solubility (in water): soluble in hot and cold water

Artikelen

Artikelselectie-assistent
Type batterij
Type
Grootte
Artikelnummer Type batterij Type Referentie Grootte E-shop
I100210070200 Water HRS-FW 700 RIS 700 PWR EKO 3.0 700
I100210070300 Elektrisch HRS-FE 700 1.2 RIS 700 PE 1.2 EKO 3.0 700
I100210120200 Water HRS-FW 1200 RIS 1200 PW EKO 3.0 1200
I100210120300 Elektrisch HRS-FE 1200 3.0 RIS 1200 PE 3.0 EKO 3.0 1200
I100210190200 Water HRS-FW 1900 RIS 1900 PW EKO 3.0 1900
I100210190300 Elektrisch HRS-FE 1900 3.0 RIS 1900 PE 3.0 EKO 3.0 1900
I100210250200 Water HRS-FW 2500 RIS 2500 PW EKO 3.0 2500
I100210250300 Elektrisch HRS-FE 2500 4.5 RIS 2500 PE 4.5 EKO 3.0 2500
=> Voorraadproduct centraal magazijn behoudens verkoop

Notes


Flushing an existing or new installation:

  1. Turn off the circulation pump.

  2. Add the appropriate amount of cleaner to the installation, this can be done through the dirt separator. Overdosage poses no problems.
    Dosage: 500 ml per 150 l of water.

  3. Turn the circulation pump on and let the water circulate during:
    min. 1 hour for high temperature water (T > 50°C)
    min. 4 hours for low temperature water (30°C < T < 40°C)
    up to 1 week for cold water

  4. Turn off the circulation pump.

  5. Drain the water and flush thoroughly, at least twice, until the water runs clear. Dispose of drain water according to applicable regulations. Repeat the above steps for heavily contaminated systems.

  6. Add the appropriate amount of protection additive to the system.
    Dosage: 500 ml per 150 l of water.

  7. Turn the circulation pump on.

The complete instructions can be found in the manual under “Downloads”.