The cleaner (C3 Cleaner 570911) dislodges sludge, scale deposits and dirt particles from hydraulic installations, after which the filter or dirt separator collects the dirt so that it can be eliminated. The cleaner can be applied to new and existing heating and cooling systems at high or low temperature. The cleaner is non-aggressive and therefore suitable for all materials used in hydraulic systems. In addition, the cleaner can be used with all types of propylene glycol.

Brand

Caleffi

Application

To remove sludge, scale, dirt particles and deposits from existing installations. For new installations, the cleaner enables commissioning to the required standards.

Specifications

  • Bottle content: 500 ml liquid
  • Colour: light brown
  • Odour: light
  • pH: 7-8
  • Relative density: 1,15
  • Solubility (in water): soluble in hot and cold water

Articles

Artikelselectie-assistent
Type
Specificatie
Artikelnummer Type Specificatie E-shop
I100100600010 FS FLAIR 325/400 C60 (2PCS) Filterset Coarse 60% (G4)
I100100600020 FS FLAIR 325/400 EPM1 50 (1PCE) Filter ePM1 50% (F7)
I100100600030 FS FLAIR 325/400 EPM1+C60 (2PCS) Filterset ePM1 50% + Coarse 60% (F7+G4)
I100100600040 FS FLAIR 325/400 C60-LL (G4) (1PCE) Filter Long Life Coarse 60% (G4)
I100100600050 FS FLAIR 325/400 CAR EPM2.5 (1PCE) Carbonfilter ePM2,5 (M5)
I100100600110 FS FLAIR 225 C60 (2PCS) Filterset Coarse 60% (G4)
I100100600120 FS FLAIR 225 EPM1 (1PCE) Filter ePM1 50% (F7)
I100100600130 FS FLAIR 225 EPM1+C60 (2PCS) Filterset ePM1 + Coarse 60% (F7+G4)
I100100600150 FS FLAIR 225 CAR EPM2.5 (1PCE) Carbonfilter ePM2,5 (M5)
I100100600210 FS FLAIR 450/600 C60 (2PCS) Filterset Coarse 60% (G4)
I100100600220 FS FLAIR 450/600 EPM1 (1PCE) Filter ePM1 50% (F7)
I100100600230 FS FLAIR 450/600 EPM1+C60 (2PCS) Filterset ePM1 + Coarse 60% (F7+G4)
I100100600250 FS FLAIR 450/600 CAR EPM2.5 (1PCE) Carbonfilter M5
=> Voorraadproduct centraal magazijn behoudens verkoop
=> Voorraadproduct regionale filialen behoudens verkoop

Notes


Flushing an existing or new installation:

  1. Turn off the circulation pump.

  2. Add the appropriate amount of cleaner to the installation, this can be done through the dirt separator. Overdosage poses no problems.
    Dosage: 500 ml per 150 l of water.

  3. Turn the circulation pump on and let the water circulate during:
    min. 1 hour for high temperature water (T > 50°C)
    min. 4 hours for low temperature water (30°C < T < 40°C)
    up to 1 week for cold water

  4. Turn off the circulation pump.

  5. Drain the water and flush thoroughly, at least twice, until the water runs clear. Dispose of drain water according to applicable regulations. Repeat the above steps for heavily contaminated systems.

  6. Add the appropriate amount of protection additive to the system.
    Dosage: 500 ml per 150 l of water.

  7. Turn the circulation pump on.

The complete instructions can be found in the manual under “Downloads”.