The cleaner (C3 Cleaner 570911) dislodges sludge, scale deposits and dirt particles from hydraulic installations, after which the filter or dirt separator collects the dirt so that it can be eliminated. The cleaner can be applied to new and existing heating and cooling systems at high or low temperature. The cleaner is non-aggressive and therefore suitable for all materials used in hydraulic systems. In addition, the cleaner can be used with all types of propylene glycol.
Brand
Caleffi
Application
To remove sludge, scale, dirt particles and deposits from existing installations. For new installations, the cleaner enables commissioning to the required standards.
Specifications
Bottle content: 500 ml liquid
Colour: light brown
Odour: light
pH: 7-8
Relative density: 1,15
Solubility (in water): soluble in hot and cold water
Articles
Article selection assistant
Type
Volume [L]
Article number
Type
Volume [L]
E-shop
J019006000200
VKG-HC 200
200
J019006000300
VKG-HC 300
300
J019006000500
VKG-HC 500
500
J019006000750
VKG-HC 750
750
J019006001000
VKG-HC 1000
1000
J019006001500
VKG-HC 1500
1500
J019006002000
VKG-HC 2000
2000
J019006002500
VKG-HC 2500
2500
J019006003000
VKG-HC 3000
3000
J019006004000
VKG-HC 4000
4000
J019006005000
VKG-HC 5000
5000
=> Stock product central warehouse, except sales
Notes
Flushing an existing or new installation:
Turn off the circulation pump.
Add the appropriate amount of cleaner to the installation, this can be done through the dirt separator. Overdosage poses no problems. Dosage: 500 ml per 150 l of water.
Turn the circulation pump on and let the water circulate during: min. 1 hour for high temperature water (T > 50°C) min. 4 hours for low temperature water (30°C < T < 40°C) up to 1 week for cold water
Turn off the circulation pump.
Drain the water and flush thoroughly, at least twice, until the water runs clear. Dispose of drain water according to applicable regulations. Repeat the above steps for heavily contaminated systems.
Add the appropriate amount of protection additive to the system. Dosage: 500 ml per 150 l of water.
Turn the circulation pump on.
The
complete instructions can be found in the manual
under “Downloads”.