The cleaner (C3 Cleaner 570911) dislodges sludge, scale deposits and dirt particles from hydraulic installations, after which the filter or dirt separator collects the dirt so that it can be eliminated. The cleaner can be applied to new and existing heating and cooling systems at high or low temperature. The cleaner is non-aggressive and therefore suitable for all materials used in hydraulic systems. In addition, the cleaner can be used with all types of propylene glycol.

Brand

Caleffi

Application

To remove sludge, scale, dirt particles and deposits from existing installations. For new installations, the cleaner enables commissioning to the required standards.

Specifications

  • Bottle content: 500 ml liquid
  • Colour: light brown
  • Odour: light
  • pH: 7-8
  • Relative density: 1,15
  • Solubility (in water): soluble in hot and cold water

Articles

Article selection assistant
Type
Code supplier
Article number Type Code supplier E-shop
J083501042200 VAPACYL 422 D1-2L222 / PCM1-2L-2WO
J083501052200 VAPACYL 522/922 D1-2N235 / PCD1-2N-2WA
J083501053400 VAPACYL 534/934 D1-2H335
J083501183400 VAPACYL 1834 D3N335 / PCM3N-3WA
J083501303400 VAPACYL 3034 D4N355 / PCD4N-3WB
J083501456400 VAPACYL 4564 D4N655 / PCD4N-6WB
=> Stock product central warehouse, except sales

Notes


Flushing an existing or new installation:

  1. Turn off the circulation pump.

  2. Add the appropriate amount of cleaner to the installation, this can be done through the dirt separator. Overdosage poses no problems.
    Dosage: 500 ml per 150 l of water.

  3. Turn the circulation pump on and let the water circulate during:
    min. 1 hour for high temperature water (T > 50°C)
    min. 4 hours for low temperature water (30°C < T < 40°C)
    up to 1 week for cold water

  4. Turn off the circulation pump.

  5. Drain the water and flush thoroughly, at least twice, until the water runs clear. Dispose of drain water according to applicable regulations. Repeat the above steps for heavily contaminated systems.

  6. Add the appropriate amount of protection additive to the system.
    Dosage: 500 ml per 150 l of water.

  7. Turn the circulation pump on.

The complete instructions can be found in the manual under “Downloads”.