Dehumidifier for wallmounting for indoor pools mounted through the wall. The
SBA-P increases comfort and prevents mould growth and moisture damage to furniture or the building structure. The units have an epoxy coating to resist chlorine vapours. Optionally, this dehumidifier can be equipped with a heating coil for a more pleasant indoor climate.
The dehumidifier does not have a built-in humidity probe. Choose from the accessories listed below for a built-in humidity probe RGDD or a remote humidistat HYGR for mounting in the pool area.
The "SBA (P) 50 1PH RGDD" and "SBA (A) 75 1 PH RGDD"
are stock product central warehouse unless sold and have the following options
fitted as standard:
- KGBH Grille set Air grilles with a double row of adjustable brushed aluminium fins
- PMBH Exhaust and return plenum 90°
- RGDD Humidity and temperature
sensor Built-in
Technical data
|
Moisture removal at 30°C - 80% | l/24h | 49 | 73 | 95 | 155 | 190 | Moisture removal at 30°C - 60% | l/24h | 40.1 | 56.6 | 77.3 | 113.1 | 143.5 | Moisture removal at 27°C - 60% | l/24h | 35.6 | 50.7 | 68.9 | 96.6 | 131.7 | Moisture removal at 20°C - 60% | l/24h | 25.8 | 35.6 | 51.3 | 71.5 | 96.6 | Nominal input power(1)(2) | kW | 0.7 | 1.2 | 1.6 | 1.9 | 2.5 | Maximum input power(2) | kW | 1.2 | 1.8 | 2 | 2.7 | 3.4 | Electrical post-heater (option) | kW | 3 | 3 | 3 | 6 | 6 | Maximum input current(2) | A | 4 | 6.8 | 7.8 | 12.1 | 15.7 | Peak current | A | 19 | 25 | 38 | 45 | 64 | Hot water coil(3) | kW | 3.5 | 7 | 7 | 11.5 | 11.8 | Air flow rate | m3/h | 500 | 800 | 1000 | 1400 | 1650 | Refrigerant (GWP) | | R410A (2088) | Refrigerant charge | g (CO2eq-T) | 470 (0.981) | 600 (1.253) | 700 (1.462) | 1200 (2.506) | Sound power(4) | dB(A) | 54 | 57 | 57 | 59 | 61 | Sound pressure level(5) | dB(A) | 47 | 50 | 50 | 52 | 54 | Power supply | V/Ph/Hz | 230/1/50 |
Performances are calculated with low fan speed and are referred to the following conditions: - (1) Temperature 30°C, humidity 80%
- (2) Without electrric heater
- (3) Room temperature 30°C, water temperature 80/70°C, compressor OFF
- (4) Sound power level calculated according to ISO 9614
- (5) Sound pressure level measured at 1 meter from the unit in free field conditions according to ISO 9614
Dimensions
|
|
SBA 50 P | 680 | 250 | 706 | 41 | SBA 75 P | 680 | 250 | 1006 | 51 | SBA 100 P | 680 | 250 | 1006 | 61 | SBA 150 P | 770 | 300 | 1255 | 82 | SBA 200 P | 770 | 300 | 1255 | 87 |
Accessories
|
Low noise version LS00 | Standard | Hot water coil (LPHW) | HOWA.49 | HOWA.75 | HOWA.76 | Electrical reheating 3 kW (230/1/50) | HOEL.29 | - | - | - | - | Electrical reheating 3 kW (230/1/50) | - | HOEL.30 | - | - | Electrical reheating 6 kW (230/1/50) | - | - | - | HOEL.62 | Built-in electronic temperature/humidity sensor | RGDD.05 | Mechanical humidistat | HYGR.20 | Remote Control Panel | PCRL.10 | Serial card RS485-MODBUS | INSE.10 | Built-in 3-way valve | KIVM.75 | KIVM.76 | Exhaust and return plenums in bend 90° 2 pieces | PMBH.09 | PMBH.10 | PMBH.20 | Pulsation and extraction grilles with subframe | KGBH.50 | KGBH.75 | KGBH.15 | Mounting feet | N/A |
|