Ductable horizontal dehumidifier for indoor swimming pools. The SHA increases comfort and prevents mould growth and moisture damage to furniture or the building structure. The units have an epoxy coating to resist chlorine vapours. Optionally, this dehumidifier can be equipped with a heating coil for a more pleasant indoor climate. The dehumidifier does not have a built-in humidity probe. Choose from the accessories listed below for a built-in humidity probe RGDD or a remote humidistat HYGR for installation in the swimming pool area.

Brand

  • Emicon

Application

  • Dehumidification of indoor swimming pools
  • On request also available as an industrial dehumidifier (HHA version) operating up to 5°C instead of up to 20°C.

Capacity

  • 50 to 200 l/24h
  • 500 to 1650 m³/h

Accessoires

  • HYGR Remote mechanical hygrostat. To be installed on the wall, it is supplied with a regulation knob and working range from 30% to 100% with precision of 3%.(Not compatible with the RGDD option)
  • HOEL - Electric post-heating battery (Also take the RGDD.05 in this case).
  • HOWA - Hot water battery (on central heating water from the boiler or heat pump) to heat the air in the room after drying (also take the KIVM and RGDD.05 in this case)(not available for HHA version).
  • KIVM - modulating 3-way valve. In combination with the HOWA hot water battery. The 3-way valve is controlled directly from the microprocessor of the unit (not available for HHA version).
  • INSE - Serial Interface Card RS485. This interface card allows the regulator to communicate with other devices via the Modbus protocol.
  • LS00 - Low noise version (standard).
  • PCRL - Remote control. This panel can be mounted up to 50 m (maximum) from the device and displays all control functions. It is connected using a double cable with a section of 0.75 mm².
  • RGDD - Humidity and Temperature electronic sensor. Built-in Electronic temperature and humidity sensor.(Not compatible with the HYGR option)
  • RP01 - Partial heat recovery. The exchanger is designed to recover approximately 20% of the thermal capacity generated by the unit to the poolwater. (Watercondensor Cu-Ni)(not available for HHA version).
  • KGBH - Louver kit and case for ducted version(not available for HHA version).
  • V1CE - E.C. fan 200 Pa.(not available for HHA version)

Artikelen

Article selection assistant
Diameter D [mm]
Article number Type [mm] Diameter D [mm] E-shop
C010103080000 MDV 80 80
C010103100000 MDV 100 100
C010103125000 MDV 125 125
C010103150000 MDV 150 150
C010103160000 MDV 160 160
C010103180000 MDV 180 180
C010103200000 MDV 200 200
C010103250000 MDV 250 250
C010103280000 MDV 280 280
C010103300000 MDV 300 300
C010103315000 MDV 315 315
C010103355000 MDV 355 355
C010103400000 MDV 400 400
C010103450000 MDV 450 450
C010103500000 MDV 500 500
C010103560000 MDV 560 560
C010103630000 MDV 630 630
C010103710000 MDV 710 710
C010103800000 MDV 800 800
C010103900000 MDV 900 900
C010103A00000 MDV 1000 1000
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
Price per piece

Technical data

SHA5075100150200
Moisture removal at 30°C - 80%l/24h497395155190
Moisture removal at 30°C - 60%l/24h3956.777.4118.3146.7
Moisture removal at 27°C - 60%l/24h34.950.169.1104.4129.5
Moisture removal at 20°C - 60%l/24h25.635.450.775.792.5
Nominal input powerkW0.971.291.762.072.74
Maximum input powerkW1.21.522.33.1
Electrical post-heater (option)kW33366
Maximum input current (1)A3.95.68.410.513.2
Peak currentA19.120.138.444.763.7
Hot water coil (2)kW3.57.58.51314
Partial heat recovery(3)kW-1.11.72.33
Air flow ratem3/h500800100014001650
Available static pressurePa50÷150
Refrigerant (GWP) R410A (2088)
Refrigerant chargeg (CO2eq-T)360 (0.752)600 (1.253)900 (1.879)
Sound power (4)dB(A)57596166.568.5
Sound pressure level (5)dB(A)50525459.561.5
Power supplyV/Ph/Hz230/1/50

Performances are calculated with low fan speed and are referred to the following conditions:
  • (1)Temperature 30°C, Humidity 80%
  • (2)Room temperature 30°C, water temperature 80/70°C, compressor OFF
  • (3)Room temperature 30°C/80%, water temperature 27/32°C
  • (4)Sound power level calculated according to ISO 9614, fan with available static pressure 50 Pa
  • (5)Sound pressure level measured at 1 meter from the unit in free field conditions according to ISO 9614

Dimensions

 A [mm]B [mm]C [mm][kg]
SHA 5036070071063
SHA 7546098090095
SHA 100460980900122
SHA 15053011601050131
SHA 20053011601050140

Accessories

SHA5075100150200
Hot water coil (LPHW)HOWA.49HOWA.75HOWA.76
Electrical post-heating battery 3 kW (230/1/50)HOEL.29-
Electrical post-heating battery 3 kW (230/1/50)-HOEL.30-
Electrical post-heating battery 4,5 kW (230/1/50)-
Electrical post-heating battery 6 kW (230/1/50)-HOEL.62
Built-in electronic temperature/humidity sensorRGDD.05
Mechanical humidistatHYGR.20
Remote control panelPCRL.10
Serial card RS485-MODBUSINSE.10
Built-in 3-way valveKIVM.75KIVM.76
Cu-Ni Partial heat recovery watercondensor-RP01.75RP01.10RP01.20
Louver kit and case with subframeKGBH.50KGBH.75KGBH.15
AC fan with available static pressure up to 150 PaStandard
EC fan with available static pressure up to 200 PaV1CE.10V1CE.20