PRODUCTS
EShop-number
Password
Welcome to CAIROX BELGIUM

CVA - MPE • Electrical heating batteries

  • Circular heater
  • Electrical
  • 1 or 3-phase
  • Built in Triac pulser with external setpoint
  • Duct
  • NTC

Circular electrical heating battery with built-in pulser for proportional control, the setpoint of the temperature is set by means of an external room temperature sensor, maximal outlet temperature of 50°C. The minimal air velocity of 1,5 m/s trough the battery is required. Available in diameter 100 up to 400 mm and in power range from 300 up to 9000 W. Operating voltage 230 or 400 V AC.

Application

  • Pre-heater
  • Zone heater
  • Constant supply air temperatuur

Material

  • Casing made of aluzinc coated steel, with rubber rings on either side for air tightness
  • Heating elements made of stainless steel ASI 304

Specifications

  • Two-stage overheat protection : the first stage switches on when the temperature reaches 50°C (resets automatically), the second stage switches on when the temperature reaches 100°C (is reset manually with pushbutton on the casing).

Accessoires

  • Probes for room temperature (adjustable), type TR-5-K

Mounting

  • Circulair ducts

Text for tender

Copy
  • The heating batteries shall be electrical, of the circular type, made of steel. The heating elements shall be made of stainless steel AISI 304. They shall be equipped with a two-stage overheat protection with automatic reset and manual reset button. Rubber rings shall be fixed on either side for air tightness when mounted to the duct.

Order example

CVA, 200, 1f, 2400, -MPE

Explanation

CVA - MPE = Electrical heater with built-in control and external setpoint

200 = Diameter in mm, (see table)

1f = Supply voltage single phase 230V, 2f = Single phase 400V, 3f = 3 phase 400V

2400 = Heating power in W, (see table)

Technical data

Ø [mm]Min. Qv [m3/h]V/50Hz]P [kW]In [A]
CV-MPE 100401~2300,3/0,6/0,9/1,21,4/2,8/4,1/5,5
CV-MPE 125701~2300,3/0,6/0,9/1,2/1,5/1,81,4/2,8/4,1/5,5/6,8/8,2
CV-MPE 1601101~2301,2/2,0/2,45,5/9,1/10,9
2~4003,0/5,0/6,07,9/13,2/15,8
3~40068.70
CV-MPE 2001701~2301,2/2,0/2,45,5/9,1/10,9
2~4003,0/5,0/6,07,9/13,2/15,8
3~40068.70
CV-MPE 2502701~2301,2/2,0/2,45,5/9,1/10,9
2~4003,0/5,0/6,07,9/13,2/15,8
3~4006,0/9,08,7/13,0
CV-MPE 3154151~2301,2/2,0/2,45,5/9,1/10,9
2~4003,0/5,0/6,07,9/13,2/15,8
3~4006,0/9,0/12,08,7/13,0/17,3
CV-MPE 4006902~4003,0/5,0/6,07,9/13,2/15,8
3~4006,0/9,0/12,08,7/13,0/17,3
HELPCopyrightSales conditionsCookie policyfujitsu-airco.be