Triac controller for DIN-rail mounting with setpoint adjustment for controlling 3-phase electric heating batteries, it is necessary to connect an external sensor to the controller. This can be and NTC sensor as well as 0-10V.
Application
Electric heating batteries
Specifications
Possible to connect 230 V or 400 V 3-phase electric heaters
Maximal load : 15,8 kW (230V) or 27 kW (400V)
Room temperature control : for slow temperature changes, works as P-controller (P = 2K)
Supply air temperature control : for rapid temperature changes, works as PI-controller (P = 20K, reset time = 6 min)
Settable cycle time : 6 to 60 s
Min/max limit possible : 0 to 60°C
Mounting
DIN-rail
Accessoires
Duct temperature sensors,type TG-K330
Min/max temperature sensors, type TG-K360
Room temperature sensors for external setpoint,type TG-R430
Technical data
Supply voltage: 230V AC or 400V AC, 3-phase. Automatic adaptation
Current: minimum 3 A - maximum 40 A
IP 20
Proportional band: 2K fixed (room control) / 20K fixed (supply air temperature control)
Reset time: 6 minutes, fixed (supply air temperature control)
Pulse period: 6 to 60 s
LED indication on the controller when the output is active
Two inputs for NTC sensors, one main sensor and one min/max limit
One input for an external 0-10V
Setpoint: selectable, either internal or external
Function
The controller pulses the entire power output ON/OFF. The controller utilises time-proportional control, the ratio between On-time and Off-time is varied to fit the prevailling heating requirement (exemple ON = 30s and OFF = 30s gives 50 % output power).
Settings
Setpoint range : 0 to 30°C, the choice of sensor determines the controller setpoint range