Available with 2 or 4 rows and various sizes: from 400 x 200 mm to 1000 x 500 mm
Application
The CWAR rectangular heating coils are designed for warming or heating the air in HVAC systems.
The CWAR must be installed in a dry environment with temperatures ranging from 5 ° C to 60 ° C, and a relative humidity of up to 80%. The CWAR is designed for the transportation of air which is free of raw materials, lipids, chemical fumes and other impurities. The casing is made of galvanized steel.
Specifications
The hot-water heat exchangers are designed for a maximum water temperature of 100 ° C and a maximum working pressure of 1.6 MPa.
The coils are composed of copper tubes with aluminium fins
The heaters are not equipped with a control system and require an external control system.
Articles
Article selection assistant
Connection diameter [mm]
Article number
Type
Connection diameter [mm]
E-shop
A06134T100000
GYP-SIDE ROUND 100
100
A06134T125000
GYP-SIDE ROUND 125
125
A06134T160000
GYP-SIDE ROUND 160
160
A06134T200000
GYP-SIDE ROUND 200
200
A06134T250000
GYP-SIDE ROUND 250
250
=> Stock product central warehouse, except sales
Technical data
Type
P[kW]
∆Ta [°C]
Q
∆Pw
Qw
∆Tw (80/60°C)
∆Tw (60/40°C)
∆Tw (45/35°C)
∆Tw (80/60°C)
∆Tw (60/40°C)
∆Tw (45/35°C)
m³/h
kPA
l/s
CWAR 400 x 200-2
11.7
7.5
6.6
26.9
17
15
1300
16,3/7,2/21,5
0,14/0,09/0,16
CWAR 400 x 200-4
19.3
12.6
10.9
44
29
25
1300
11,2/5,0/14,4
0,23/0,15/0,26
CWAR 500 x 250-2
19.4
13.6
10.7
29
20
16
2000
48,1/33,6/50,4
0,2/0,16/0,2
CWAR 500 x 250-4
32.3
22
18
48
33
27
2000
45,7/22,3/49,7
0,39/0,26/0,4
CWAR 500 x 300-2
22.6
14.5
12.8
29
19
17
2300
12,8/5,6/16,7
0,27/0,17/0,31
CWAR 500 x 300-4
34.8
22.7
19.7
45
29
25
2300
7,7/3,5/10,0
0,42/0,27/0,55
CWAR 600 x 300-2
26.5
17.3
15
29
19
17
2700
18,4/8,2/24,1
0,32/0,21/0,65
CWAR 600 x 300-4
43.2
28.7
24.4
47
32
27
2700
12,3/5,8/16,2
0,51/0,38/0,65
CWAR 600 x 350-2
28
18.7
16
27
18
15
3100
25,8/12,2/34,4
0,33/0,22/0,38
CWAR 600 x 350-4
46.7
30.9
26.5
45
30
25
3100
9,4/4,3/12,4
0,62/0,37/0,75
CWAR 700 x 400-2
38.4
23.9
21.6
25
15
14
4600
3,2/1,3/4,2
0,46/0,29/1,1
CWAR 700 x 400-4
68.5
44.7
38.7
44
29
25
4600
8,0/3,7/10,4
0,82/0,54/1,11
CWAR 800 x 500-2
66.7
42.2
37.6
25
16
14
7800
5,2/2,25/6,72
0,79/0,50/090
CWAR 800 x 500-4
109
68.7
61.2
41
26
23
7800
3,65/1,58/4,75
1,40/0,82/1,88
CWAR 1000 x 500-2
85.6
55.2
48.5
27
17
15
9500
9,2/4,2/12,2
1,02/0,66/2,29
CWAR 1000 x 500-4
139
89.9
78.4
43
28
24
9500
6,4/2,92/8,4
1,65/1,08/2,29
Symbols & specifications
ΔTw = Water regime
ΔTa = Temperature difference air at 0°C inlet air temperature