This site uses cookies and related technologies, as described in our privacy policy, for purposes that may include site operation, analytics, enhanced user experience, or advertising. You may choose to consent to our use of these technologies, or manage your own preferences.
Available with 2 or 4 rows and various sizes: from 400 x 200 mm to 1000 x 500 mm
Application
The CWAR rectangular heating coils are designed for warming or heating the air in HVAC systems.
The CWAR must be installed in a dry environment with temperatures ranging from 5 ° C to 60 ° C, and a relative humidity of up to 80%. The CWAR is designed for the transportation of air which is free of raw materials, lipids, chemical fumes and other impurities. The casing is made of galvanized steel.
Specifications
The hot-water heat exchangers are designed for a maximum water temperature of 100 ° C and a maximum working pressure of 1.6 MPa.
The coils are composed of copper tubes with aluminium fins
The heaters are not equipped with a control system and require an external control system.
Order example
CWAR 400x200-2
CWAR = Battery type
400 = Width dimension in mm
200 = Height dimension in mm
-2 = Number of rows
Artikelen
Article selection assistant
Type
Colour
Article number
Type
Colour
E-shop
J050102110700
SPCA-B-H 700
Black RAL 9004
J050102110800
SPCA-B-H 800
Black RAL 9004
J050102111100
SPCA-B-H 1100
Black RAL 9004
J050102120700
SPCA-A-H 700
Anthracite RAL 7037
J050102120800
SPCA-A-H 800
Anthracite RAL 7037
J050102121100
SPCA-A-H 1100
Anthracite RAL 7037
J050102130700
SPCA-W-H 700
White RAL 9003
J050102130800
SPCA-W-H 800
White RAL 9003
J050102131100
SPCA-W-H 1100
White RAL 9003
=> Stock product central warehouse, except sales
=> Stock product local warehouses, except sales
Price per piece
Technical data
Type
P[kW]
∆Ta [°C]
Q
∆Pw
Qw
∆Tw (80/60°C)
∆Tw (60/40°C)
∆Tw (45/35°C)
∆Tw (80/60°C)
∆Tw (60/40°C)
∆Tw (45/35°C)
m³/h
kPA
l/s
CWAR 400 x 200-2
11.7
7.5
6.6
26.9
17
15
1300
16,3/7,2/21,5
0,14/0,09/0,16
CWAR 400 x 200-4
19.3
12.6
10.9
44
29
25
1300
11,2/5,0/14,4
0,23/0,15/0,26
CWAR 500 x 250-2
19.4
13.6
10.7
29
20
16
2000
48,1/33,6/50,4
0,2/0,16/0,2
CWAR 500 x 250-4
32.3
22
18
48
33
27
2000
45,7/22,3/49,7
0,39/0,26/0,4
CWAR 500 x 300-2
22.6
14.5
12.8
29
19
17
2300
12,8/5,6/16,7
0,27/0,17/0,31
CWAR 500 x 300-4
34.8
22.7
19.7
45
29
25
2300
7,7/3,5/10,0
0,42/0,27/0,55
CWAR 600 x 300-2
26.5
17.3
15
29
19
17
2700
18,4/8,2/24,1
0,32/0,21/0,65
CWAR 600 x 300-4
43.2
28.7
24.4
47
32
27
2700
12,3/5,8/16,2
0,51/0,38/0,65
CWAR 600 x 350-2
28
18.7
16
27
18
15
3100
25,8/12,2/34,4
0,33/0,22/0,38
CWAR 600 x 350-4
46.7
30.9
26.5
45
30
25
3100
9,4/4,3/12,4
0,62/0,37/0,75
CWAR 700 x 400-2
38.4
23.9
21.6
25
15
14
4600
3,2/1,3/4,2
0,46/0,29/1,1
CWAR 700 x 400-4
68.5
44.7
38.7
44
29
25
4600
8,0/3,7/10,4
0,82/0,54/1,11
CWAR 800 x 500-2
66.7
42.2
37.6
25
16
14
7800
5,2/2,25/6,72
0,79/0,50/090
CWAR 800 x 500-4
109
68.7
61.2
41
26
23
7800
3,65/1,58/4,75
1,40/0,82/1,88
CWAR 1000 x 500-2
85.6
55.2
48.5
27
17
15
9500
9,2/4,2/12,2
1,02/0,66/2,29
CWAR 1000 x 500-4
139
89.9
78.4
43
28
24
9500
6,4/2,92/8,4
1,65/1,08/2,29
Symbols & specifications
ΔTw = Water regime
ΔTa = Temperature difference air at 0°C inlet air temperature