Technical data
|
|
Mounting heigth (Max.)
| m
| < 2,30
| < 2,60 | < 3,00 | Dimensions (HxL)°
| mm | 300x750
| Outlet range
| | +30°/-30°
| Air flow data of air curtain
| Effective air fow rate
| m³/h
| 1400 | 1800 | 2700 | 3600 | 1800 | 2700 | 3600 | 4500 | 2700 | 3600 | 5400 | 6300 | Sound pressure level**
| dB(A)
| 40-54 | 41-56
| 41-58 | 41-60 | 41-54 | 43-56 | 44-58 | 45-60 | 40-54 | 41-56 | 41-58 | 41-60 | Weight
| kg | 61 | 71
| 93 | 135 | 61 | 74 | 960 | 138 | 65 | 78 | 104 | 145 | Electrical data of fans
| Power supply (50 Hz)°°
| V | 230/1
| Absorbed power (Max.)
| kW | 0,33 | 0,33 | 0,5 | 0,66 | 0,33 | 0,54 | 0,66 | 0,83 | 0,52 | 0,66 | 0,99 | 1,16 | Absorbed current (Max.) | A | 2,4 | 2,4 | 3,6 | 4,8 | 2,4 | 3,6 | 4,8 | 6,0 | 3,6 | 4,8 | 7,2 | 8,4 | Power cable section | mm² | 3G 2,5 | Automatic fuse (Slow) | A | 10 | Technical data of DX battery (H) | Heating capacity @ 20/35°C***
| kW | 6,9 | 9,3 | 13,4 | 18,7 | 9,1 | 13,4 | 18,2 | 22,3 | 12,2 | 17,9 | 27,2 | 32,3 | Refrigerant
| | R410A | Battery diameter
| inch | 1/2-5/8 | 1/2-7/8 | 1/2-5/8 | 1/2-7/8 | Technical data of matching Fujitsu outdoor unit
| Type of unit (AOYG/A)
| | 30 LETL | 36 LETL
| 45 LATT | 60 LATT | 36 LETL
| 45 LATT | 60 LATT | 72 LRLA | 36 LATT | 60 LATT | 72 LRLA | 90 LRLA | Type of ACA-DX-BOX | | ACA-DX-BOX 30 | ACA-DX-BOX 36 | ACA-DX-BOX 45 | ACA-DX-BOX 60 | ACA-DX-BOX 36 | ACA-DX-BOX 45 | ACA-DX-BOX 60 | ACA-DX-BOX 72 | ACA-DX-BOX 36 | ACA-DX-BOX 60 | ACA-DX-BOX 72 | - | Power supply
| V | 230/1 | 400/3 | 230/1 | 400/3 | Absorbed capacity (Nom. - Max.)
| kW | 2,68-3,8 | 3,1-4,5 | 3,8-5,8
| 5,1-7,1
| 3,1-4,5 | 3,8-5,8
| 5,1-7,1
| 6,2-9,8 | 2,8-5,1 | 5,1-7,1
| 6,2-9,8 | 8,2-12,1 | Absorbed current (Nom. - Max.)
| A | 11,7-17 | 13,6-20 | 5,5-11
| 7,6-12,5 | 13,6-2 | 5,5-11
| 7,6-12,5 | 9,6-22,8 | 4,4-8,5 | 7,6-12,5 | 9,6-22,8 | 12-25,8 | Dimemsions (Heigth)
| mm | 830 | 830 | 1290 | 1290 | 830 | 1290 | 1290 | 1690 | 1290 | 1290 | 1690 | 1690 | Dimnsions (Length)
| mm | 900 | 900 | 900 | 900 | 900 | 900 | 900 | 930 | 900 | 900 | 930 | 930 | Dimensions (Depth)
| mm | 330 | 330 | 330 | 330 | 330 | 330 | 330 | 765 | 330 | 330 | 765 | 765 | Sound pressure level
| dB(A) | 55 | 55
| 54 | 56
| 55 | 54 | 56 | 57 | 53 | 56 | 57 | 59 | Weight
| kg | 61 | 61
| 104
| 104
| 61 | 104 | 104 | 215 | 104 | 104 | 215 | 215 | Cooling pipes1
| inch | 3/8-5/8 | 1/2-7/8 | 3/8-5/8 | 1/2-7/8 | Amount of prefilled refrigerant
| g | 2100 | 2100 | 3450 | 3450 | 2100 | 3450 | 3450 | 11200 | 3450 | 3450 | 11200 | 11200 | Extra amount of refrigerant
| g/m
| 40 | 40 | 50 | 50 | 40 | 50 | 50 | 110 | 50 | 50 | 110 | 110 | Number of prefilled meters
| m | 4 | 0
| 2
| 0 | 4 | 9 | 0 | 5 | 17 | 9 | 7,5 | 5 | Maximum length/heigth of cooling pipes²
| m | 40/20 | 30/30
| 45/30
| 40/30
| 40/30 | 65/30 | 50/30 | 65/30 | 75/30 | 65/30 | 70/30 | 65/30 | Minimum length of cooling pipes | m | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | 5 | Cable section between air curtain and outdoor unit
| mm² | 4G 1,5 | Power cable section
| mm² | 3G 4 | 3G 4 | 5G 2,5 | 5G 2,5 | 3G 4 | 5G 2,5 | 5G 2,5 | 5G 4 | 5G 2,5 | 5G 2,5 | 5G 4 | 5G 4 | Automatic fuse (Slow)
| A | 25
| 25 | 16 | 16 | 25 | 16 | 16 | 25 | 16 | 16 | 25 | 25 | * Specifications and design are subject to change for further improvement without prior notice
| ** = The sound pressure level is measured at 3m distance of the air curtain's air intake at high speed
| *** = Heating capacity at 20°C air intake temperature and 35°C air outlet temperature at a condensation temperature between 43 and 50°C
| ° = Fan connection on the left side when standing in front of the device
| 1 = Always use the same cooling pipes as the outdoor unit
|
Technical data
|
|
5m | 30 | 430 | 140 | 410 | 30 | x | 140 | x | x | x | x | x | 10m | 230 | 630 | 390 | 660 | 230 | 30 | 390 | 560 | x | 30 | 290 | 560 | 15m | 430 | 830 | 640 | 910 | 430 | 280 | 640 | 1110 | x | 280 | 840 | 1110 | 20m | 630 | 1030 | 890 | 1160 | 630 | 530 | 890 | 1660 | 130 | 530 | 1390 | 1660 | 25m | 830 | 1230 | 1140 | 1410 | 830 | 780 | 1140 | 2210 | 380 | 780 | 1940 | 2210 | 30m | 1030 | 1430 | 1390 | 1660 | 1030 | 1030 | 1390 | 2760 | 630 | 1030 | 2490 | 2760 | 35m | 1230 | - | 1640 | 1910 | 1230 | 1280 | 1640 | 3310 | 880 | 1280 | 3040 | 3310 | 40m | 1430 | - | 1890 | 2160 | 1430 | 1530 | 1890 | 3860 | 1130 | 1530 | 3590 | 3860 | 45m | - | - | 2140 | - | - | 1780 | 2140 | 4410 | 1380 | 1780 | 4140 | 4410 | 50m | - | - | - | - | - | 2030 | 2390 | 4960 | 1630 | 2030 | 4690 | 4960 | 55m | - | - | - | - | - | 2280 | - | 5510 | 1880 | 2280 | 5240 | 5510 | 60m | - | - | - | - | - | 2530 | - | 6060 | 2130 | 2530 | 5790 | 6060 | 65m | - | - | - | - | - | 2780 | - | 6610 | 2380 | 2780 | 6340 | 6610 | 70m | - | - | - | - | - | - | - | - | 2630 | - | 6890 | - | 75m | - | - | - | - | - | - | - | - | 2880 | - | - | - | gr/m | 40 | 40 | 50 | 50 | 40 | 50 | 40 | 110 | 50 | 50 | 110 | 110 | x = No extra refill required | - = Unauthorized length of cooling pipes still possible for this combination | * = Minimum 5m of cooling pipes between the air curtain and the Fujitsu outdoor unit |
|